User manual 09/2009 - Schneider Electric

schneider.electric.dk

User manual 09/2009 - Schneider Electric

The RSU Parameter Setting SoftwareSetting the SDx Module Output ParametersPresentationAll alarms on a trip, failure and maintenance event and all alarms associated with a measurement,activated beforehand in the Alarms tab, can be assigned to an SDx module output.The SDx module output parameter settings can be accessed using the RSU software under thetab:Default Assignment of the SDx Module OutputsThe figure below illustrates the Outputs tab for a Micrologic 6 trip unit:The SDx module output assignment depends on the type of Micrologic trip unit installed on the module.Both outputs are assigned by default as follows:• Micrologic 5 trip unit:• Output 1 is assigned to the thermal fault indication (SDT) function.• Output 2 is assigned to the long time pre-alarm (PAL Ir) function.• Micrologic 6 trip unit:• Output 1 is assigned to the thermal fault indication (SDT) function for electrical distributionapplications.Output 1 is assigned to None for motor-feeder applications.• Output 2 is assigned to the ground fault indication (SDG) function.LV434104 09/2009 127