User manual 09/2009 - Schneider Electric

schneider.electric.dk

User manual 09/2009 - Schneider Electric

Operating AssistanceIndication of Faults With Micrologic 6 E-MFor more information on definitions of the fault protections associated with indications, see Protection forMotor-Feeders, page 55.ScreenCauseTripped by long time protection: Up arrow pointing to Ir, triPdisplayed (1)Peak breaking current IsdTripped by short time protection: Up arrow pointing to Isd, breakingvalue displayedTripped by instantaneous protection or reflex protection: InstdisplayedTripped by ground fault protection: Up arrow pointing to Ig, triPdisplayedTripped by unbalance protection: Up arrow pointing to Iunbal, triPdisplayed (1)Tripped by jam motor protection: Up arrow pointing to Ijam, triPdisplayed (1)Tripped by underload protection: Undl displayed (1)Tripped by long start protection: Strt displayed(1) These trip causes can be managed automatically by SDTAM output 2 (OUT2) action on the contactor (seeSDTAM Module Option, page 57).LV434104 09/2009 135