BUREAU OF INDIAN STANDARDSMarks Department Delhi IIIAGENDAREVIEW MEETING OF XLPE INSULATED CABLE LICENSEES OF CENTRALREGIONDate of Meeting Friday, 23 March 2007TimeVenue1030 hr<strong>BIS</strong> AuditoriumManak Bhavan9 Bahadur Shah Zafar MargNew Delhi - 110002CHAIRMAN: Shri S.K.Gupta, Deputy Director General (Central Region)SECRETARY: Dr R.K.Singh, Scientist ‘E’ & Head (MDD-III)1 INAUGURAL SESSION (1030 hr)1.1 Welcome Address and Programme Objectives: Dr R.K.Singh, Scientist ‘E’ & Head(MDD-III)1.2 Inaugural Address: Shri S.K.Gupta, Deputy Director General (Central Region)Tea Break (1100 hr to 1130 hr)2 TECHNICAL SESSION (1130 hr – 1330 hr)2.1 Presentation on the Operation of licenses under CRO2.2 Discussion on Comments and Queries2.2.1 Comments on Indian StandardsComments received are given at Annexure 1. Comments may please be examined/discussed.(Note – Recommendations requiring any amendment shall be forwarded to the concernedTechnical department/Sectional committee for their scrutiny/examination towards issue ofamendment, if any)


2.2.2 Comments on the Schemes of Testing and Inspection (STI)Comments received on STIs are given at Annexure 2(Note – Recommendations requiring any amendment shall be forwarded to the Central MarksDepartment, <strong>BIS</strong> for changes in STIs, if any)3 BRIEF ON SIMPLIFIED PROCEDURE FOR GRANT OF <strong>BIS</strong> PRODUCTCERTIFICATION LICENSE: Presentation by MDD-III, <strong>BIS</strong>4 BRIEF ON <strong>BIS</strong> HALLMARKING SCHEME FOR GOLD AND SILVER: Presentation byMDD-III, <strong>BIS</strong>.5 BRIEF ON <strong>BIS</strong> MANAGEMENT SYSTEM CERTIFICATION SCHEME: Presentationby MDD-III, <strong>BIS</strong>.6 BRIEF ON CE MARKING: Presentation by IR & TISD, <strong>BIS</strong>.7 ANY OTHER BUSINESS8 CONCLUDING REMARKS BY THE CHAIRMAN9 VOTE OF THANKSLunch (1330 hr)(Note – Technical session may be continued post lunch, if required)


6.2, Page3 & IS397510.1 c)Page -4RKEIVCCThe manufacturer of cable armour wires/stripsissues test certificates without chemicalcomposition. The clause A-3.2 Line No. 6 ofIS 3975 : 1999 clearly states that all selectedsamples shall be tested for all the chemicalrequirements.Here, we would like <strong>BIS</strong> to clarify whetherchemical composition of metal is to bementioned in the test reports of manufacturer ornot.During third party inspections, some agenciesare asking for manufacturers test certificates forchemical analysis as per IS 3975 : 1999.Core identification of three core cables bynumerals has been indicated as 0,1,2,3. Thisshould have been 0,1,2.11.2,Table 4,Page-411.2,Table 4,Page-411.2,Table 4,Page-413.2,Page-5,VCC For 23 cores lay up has been shown as 2-7-13.This should have been 2-8-13.VCC For 37 cores lay up has been shown as 0-6-12-18. This should have been 1-6-12-18.VCC For 62 cores lay up has been shown as 1-6-12-18-24. This should have been 1-6-12-18-25.RKEINote under this clause states : “It may bedesirable for single core cables intended foruse in ac system, to be armoured with nonmagneticmaterial” whereas IS 1554 (Pt-1)Clause No. 13.2.1 states that : “ In case ofsingle core cable intended for use in acsystems, the armouring shall be of nonmagneticmaterial”.15.1 c)vii, Page7HILSince the application of cables is same, wewould like <strong>BIS</strong> to clarify this point.Which procedure is to be followed for thermalstability test on outer sheath; as per Annexure–A of IS 5831 or test method of IS 10810 (Pt-60).


16.2.1,Page 817.2.1,Page 9VCCVCC“An ac voltage of 7.2 kV” should be replacedby “ dc voltage of 7.2 kV”.The sentence “ Cables with heat resistinginsulation suitable for 85 degree C conductortemperature shall be identified by the lettersHR 85” should be deleted as insulation is ofXLPE compound.IS 7098 (Part 2):1985ClauseNo. ofStandardAppendixACommentator Comments DecisionHIL The sampling plant of IS 7098 (Pt-1) and 7098(Pt-2) is different. In IS 7098 (Pt-2) min.number of sample upto 25 drums should bethree samples as in other IS also.


IS 7098 (Part 3):1993ClauseNo. ofStandard8.3, Page38.3, Page3Commentator Comments DecisionVCC Elongation at break before ageing (min) 300%and after ageing Min. 300%. How it is possiblethat before and after ageing value is same.VCC Tensile strength before ageing specified as 12.5N/mm 2 (Min.), however specified value oftensile strength after ageing not mentioned.13.3,Page 3Table 6,Page 419.1,Page 619.1,Page 6VCCVCCVCCHILContrarily, Page 6, Clause 19.1. Sl. No. 3 (II)mention tensile strength and elongation at breakbefore and after ageing and refers to clause 8.3.Last line mentions more than 0.1 ti it shouldhave been 0.1 mm + 0.1x ti .Calculated diameter under metallic sheathmentioned in line 3 as (45-45) and mentionedin line 10 and 11 as (80-85) & (85-90).The <strong>above</strong> should be corrected to (45-50) inline 3 and (80-90) in 10 & 11.In list of type test Partial discharge test andHigh Voltage test have not been mentioned.These two tests should be mentioned in typetest as : -- Partial discharge test; clause 20.10 andRef. : 10810 (Pt-46).- High Voltage test ; clause 20.17 andRef. 10810 (Pt-45).PD test should be as type test.


IS 10810Clause ofStandard1, Scope,Line 2 ofPt-304, Table 1of Pt-304.5, Table1 of Pt-306.1 and15.1. d)v) of Part33 &Table 1,vi of IS7098 (Pt-1)Commentator Comments DecisionVCCInsulation of electric cables should be replacedby insulation and sheath of electric cables.VCC Apparatus for hot set test should be includedwith conditioning chamber.VCC Range of thermometer for hot set testmentioned as 200 degree Celsius. It shouldhave range of 250 degree Celsius.MDD-III For smaller diameter tubular samples,preparation of test specimen for carrying outwater absorption test as per dimension given inthe specification is not possible and thereforethis test is not being carried out by <strong>BIS</strong>Laboratory. Size of test specimen suitable forsmaller diameter tubular samples should bespecified in the IS.


ANNEXURE -2(Ref Item 2.2.2)Comments on Scheme of Testing and InspectionStandard Commentator Comments DecisionIS 7098(Pt-1) :1988HILPlease clarify whether we can mark ISI onFRLS outer sheath cable.