12.07.2015 Views

CABLE SYSTEMS Cable fittings for high voltage ... - Elektroskandia

CABLE SYSTEMS Cable fittings for high voltage ... - Elektroskandia

CABLE SYSTEMS Cable fittings for high voltage ... - Elektroskandia

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Cable</strong> Fittings <strong>for</strong> High VoltageNetworks.Our range of cable accessories offers solutions <strong>for</strong> virtually all applications in the area of <strong>high</strong>-<strong>voltage</strong>engineering up to 300 kV. All accessories use silicone rubber as insulating medium because of itsoutstanding properties. We offer components and complete systems, as well as worldwide installation andadvisory services.HV-CONNEX. A Dry, Separable Connector System <strong>for</strong> High-Voltage Networks.CONNEX meets all your requirements to an universal system of separable connectors: fully insulated with metalhousing and providing touch-proof properties. It is maintenance-free, suitable <strong>for</strong> outdoor use and waterproof.This means CONNEX can be used even in the most extreme conditions.HV-CONNEX components <strong>for</strong> <strong>high</strong>-<strong>voltage</strong> systems up to 245 kV are factory tested and are surprisingly simple toinstall. Complex oil and gas work during installation and commissioning of trans<strong>for</strong>mers is finally a thing of thepast.IXOSIL <strong>Cable</strong> Terminations.The comprehensive range of terminations suits all applications: the use of silicone rubber as the insulating mediummeans they are ideally suited to outdoor use, and special designs <strong>for</strong> indoor use are available as well. In addition, oilfilledand dry models are also available. Standard components with porcelain insulators complete the range.


IXOSIL Slip-on Joints.IXOSIL silicone-rubber joints can be used to join all XLPE and EPR insulated cables within the 72.5 kV to 300 kV<strong>voltage</strong> range. There are two designs: the compact, one-piece version and a threepart version <strong>for</strong> connecting cablesof different types and diameters.IXOLINE. Factory-Assembled <strong>Cable</strong>s Ready-to-Use.IXOLINE cable links are supplied with IXOSIL or CONNEX terminations. No special tools are required <strong>for</strong> installation.Result: increased efficiency in less time and at lower cost.Silicone – a Key Material in High-Voltage Engineering.Water, dirt, grease and oil-resistant, completely maintenance-free, shock-resistant and unbreakable: siliconerubber is the perfect material <strong>for</strong> cable terminations and far superior to traditional materials such as porcelain.When used as a stress-relief device in sealed applications, silicone evens out temperature variations and unevennessin the cable surface much better than harder materials such as EPDM do. Dangerous partial dischargescaused by air gaps are safely avoided. PFISTERER makes silicone products primarily using advanced LSR (LiquidSilicone Rubber) designs; special variations are designed using RTV (room-temperature vulcanising silicone).Worldwide Installation Services.The installation of <strong>high</strong>-<strong>voltage</strong> components requires knowledge and care. We share our know-how in practicalapplications training courses. If requested we can of course carry out the installation by ourselves <strong>for</strong> you, whereverin the world you may be.


ContentsIXOSIL- Slip-on Joints Page | 8 – 9IIXOSIL- <strong>Cable</strong> Terminations Page | 10 – 35IIHV-CONNEX Pluggable Connection System Page | 36 – 69IIIIXOSIL Trans<strong>for</strong>mer and GIS connectors Page | 70 – 79 IVwww.pfisterer.com


ContentsPage | 8 – 9IOne-piecePage 9Three-piecePage 9Page | 10 – 35IIESSPage 10 – 16ESPPage 17 – 23ESFPage 24 – 28ESTPage 29 – 32ESKPage 33 – 35Page | 36 – 69IIISize 4Page 40 – 45Size 5-SPage 46 – 52Size 6Page 53 – 59Size 6-SPage 60 – 66Mounting AccessoriesPage 68 – 69Page | 70 – 79IVESGPage 70 – 74ESUPage 75 – 79www.pfisterer.com


IXOSIL Slip-on JointOne-piece Slip-on JointThe one-piece MSA slip-on joint is available <strong>for</strong> a <strong>voltage</strong> range from 72,5 kV to 300 kV.Due to the one-piece construction the joints are extremely compact in size. The space requiredin a joint bay is there<strong>for</strong>e reduced to a minimum. Each size of silicone body coversa wide range of cable insulation diameters.MSAIMaterial:Joint body: silicone rubberConductor connection:compressed or screwedNote:The weight depends on the diameter of the cable insulation (prepared) and the type ofdesign.The joints are tailored according to the customer‘s specification. Thus, more detailedtechnical in<strong>for</strong>mation including dimensions are only available on request.Max. operating<strong>voltage</strong>Standards Rated <strong>voltage</strong> Rated lightningimpulse withstand<strong>voltage</strong>(BIL)Partial dischargemeasurementConductor crosssectionDiameter overcable insulation(prepared)U m(kV) U (kV) (kV) (pC) (mm 2 ) (mm) (kg)Net weightapprox.72.5 IEC60840 60 - 69 325 < 5 150 - 1200 37 - 87 72 - 90123 IEC60840 110 - 115 550 < 5 240 - 2000 45 - 103 50 - 130145 IEC60840 132 - 138 650 < 5 240 - 2000 45 - 103 80 - 160170 IEC60840 150 - 161 750 < 5 240 - 2000 45 - 103 80 - 160245 IEC62067 220 - 230 1050 < 5 240 - 2000 69 - 102 80 - 200300 IEC62067 275 - 287 1050 < 5 240 - 2000 69 - 102 80 - 220Three-piece Slip-on JointThe three-piece MSA slip-on joint is available <strong>for</strong> <strong>voltage</strong>s from 72,5 kV to 170 kV. Thewell-tried three-piece construction of this joint enables cables of different types anddimensions to be connected. For example a 630 mm 2 EPR cable can be connected to a500 mm 2 XLPE cable.Materials:Joint body: silicone rubberConductor connection:compressed or screwedNote:The joints are tailored according to the customer‘s specifications. Thus, more detailedtechnical in<strong>for</strong>mation are available on request.Max. operating<strong>voltage</strong>Standards Rated <strong>voltage</strong> Rated lightningimpulse withstand<strong>voltage</strong>(BIL)Partial dischargemeasurementConductorcross sectionDiameter overcable insulation(prepared)U m(kV) U (kV) (kV) (pC) (mm 2 ) (mm) (kg)Net weightapprox.72.5 IEC60840 60 - 69 325 < 5 on request on request on request123 IEC60840 110 - 115 550 < 5 on request on request on request145 IEC60840 132 - 138 650 < 5 on request on request on request170 IEC60840 150 - 161 750 < 5 on request on request on requestwww.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsOutdoor <strong>Cable</strong> Termination (Composite)ESS terminations are available <strong>for</strong> a <strong>voltage</strong> range from 72,5 kV to 300 kV with variouscreepage distances. A glass fibre rein<strong>for</strong>ced tube equipped with silicone sheds provides<strong>high</strong>est mechanical strength. The FRP tube is filled with an insulating compound. Aneasy-to-fit head armature completes the ESS to a maintenance-free system.IIESSMaterial:Insulator: composite hollow insulator (silicone-sheded FRP tube)Stress relief cone: silicone rubberConductor connection:compressed or screwedOptional accessories:Earthing setNote:Optional material is not within scope of supply and has to be ordered seperately.Max. operating <strong>voltage</strong> U m(kV) 72.5 123 145 170 245 300StandardsIEC60840IEC60815IEC60840IEC60815IEC60840IEC60815IEC60840IEC60815IEC62067IEC60815IEC62067IEC60815Rated <strong>voltage</strong> U (kV) 60 - 69 110 - 115 132 - 138 150 - 161 220 - 230 275 - 287Rated lightning impulsewithstand <strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 325 550 650 750 1050 1050(pC) < 5 < 5 < 5 < 5 < 5 < 510 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESS72IIESSProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESS72-C19 95-2000 37 - 84 120 60 1813 3 25ESS72-C23 95-2000 37 - 84 120 62 2248 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESS72-C19 320 (420) 270 (345) 19 ~550 882 100 30,40,50 282ESS72-C23 320 (420) 270 (345) 19 ~550 882 100 30,40,50 282www.pfisterer.com11


IXOSIL <strong>Cable</strong> TerminationsESS123IIESSProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESS123-C31 150-1600 46 - 96 120 104 3075 3 25ESS123-C34 150-2000 46 - 99 120 105 3383 3 25ESS123-C39 150-1600 46 - 96 120 98 3813 4 31ESS123-C42 150-2000 46 - 99 120 125 4194 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESS123-C31 420 (320, 500) 345 (270, 400) 19 ~550 1402 100 30,40,50 326ESS123-C34 420 (500) 345 (400) 19 ~550 1412 100 30,40,50 376ESS123-C39 420 (320, 500) 345 (270, 400) 19 ~550 1402 100 30,40,50 326ESS123-C42 420 (500) 345 (400) 19 ~550 1412 100 30,40,50 41612 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESS145IIESSProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESS145-C37 150-1200 46 - 84 120 111 3625 3 25ESS145-C40 150-2000 46 - 99 120 128 3988 3 25ESS145-C45 150-1200 46 - 84 120 118 4495 4 31ESS145-C50 150-2000 46 - 99 120 144 4945 4 31ESS145-C72 150-2000 46 - 99 120 206 7178 - 45ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESS145-C37 420 (500) 345 (400) 19 ~550 1612 100 30,40,50 326ESS145-C40 420 (500) 345 (400) 19 ~550 1622 100 30,40,50 376ESS145-C45 420 (500) 345 (400) 19 ~550 1612 100 30,40,50 326ESS145-C50 420 (500) 345 (400) 19 ~550 1622 100 30,40,50 416ESS145-C72 420 (500) 345 (400) 19 ~550 2232 100 30,40,50 416www.pfisterer.com13


IXOSIL <strong>Cable</strong> TerminationsESS170IIESSProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESS170-C47 150-2000 46 - 99 120 155 4675 3 25ESS170-C58 150-2000 46 - 99 120 175 5797 4 31ESS170-C72 150-2000 49 - 99 120 206 7106 - 38ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESS170-C47 500 (420) 400 (345) 19 ~550 1842 100 30,40,50 376ESS170-C58 500 (420) 400 (345) 19 ~550 1842 100 30,40,50 416ESS170-C72 500 (420) 400 (345) 19 ~550 2232 100 30,40,50 41614 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESS245IIESSProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESS245-C84 240-2000 52 - 99 120 321 8355 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESS245-C84 500 400 19 ~550 2729 100 30,40,50 470www.pfisterer.com15


IXOSIL <strong>Cable</strong> TerminationsESS300IIESSProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESS300-C83 240 - 2000 52 - 99 120 321 8250 3 25ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESS300-C83 500 400 19 ~550 2729 100 30,40,50 47016 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsOutdoor <strong>Cable</strong> Termination (Porcelain)The ESP termination can be supplied <strong>for</strong> <strong>voltage</strong>s from 72,5 kV to 300 kV. The ESPstress relief system is the same as that of the ESS termination.Material:Insulator: PorcelainStress relief cone: silicone rubberConductor connection:compressed or screwedIIOptional accessories:Earthing set, spark conductorsESPNote:Optional material is not within scope of supply and has to be ordered seperately.Max. operating <strong>voltage</strong> U m(kV) 72.5 123 145 170 245 300StandardsIEC60840IEC60815IEC60840IEC60815IEC60840IEC60815IEC60840IEC60815IEC62067IEC60815IEC62067IEC60815Rated <strong>voltage</strong> U (kV) 60 - 69 110 - 115 132 - 138 150 - 161 220 - 230 275 - 287Rated lightning impulsewithstand <strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 325 550 650 750 1050 1050(pC) < 5 < 5 < 5 < 5 < 5 < 5www.pfisterer.com17


IXOSIL <strong>Cable</strong> TerminationsESP72IIESPProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESP72-C23 95-2000 37 - 84 120 132 2270 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESP72-C23 320 (420) 270 (345) 19 ~550 982 100 30,40,50 34218 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESP123IIESPProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESP123-C39 150-1600 46 - 94 120 200 3813 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESP123-C39 420 (320, 500) 345 (270, 400) 19 ~550 1392 100 30,40,50 342www.pfisterer.com19


IXOSIL <strong>Cable</strong> TerminationsESP145IIESPProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESP145-C45 150-1200 46 - 84 120 220 4540 4 31ESP145-C50 150-2000 46 - 99 120 250 4994 4 31ESP145-C58 150-2000 46 - 99 120 315 5828 - 36ESP145-C73 150-2000 46 - 99 120 330 7335 - 45ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESP145-C45 420 (500) 345 (400) 19 ~550 1612 100 30,40,50 342ESP145-C50 420 (500) 345 (400) 19 ~550 1631 100 30,40,50 390/310ESP145-C58 500 (420) 400 (345) 19 ~550 2232 100 30,40,50 365/285ESP145-C73 500 (420) 400 (345) 19 ~550 2232 100 30,40,50 390/31020 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESP170IIESPProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESP170-C58 150-2000 46 - 99 120 421 5828 4 31ESP170-C73 150-2000 46 - 99 120 465 7335 - 38ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESP170-C58 500 (420) 400 (345) 19 ~550 2232 100 30,40,50 365/285ESP170-C73 500 (420) 400 (345) 19 ~550 2232 100 30,40,50 390/310www.pfisterer.com21


IXOSIL <strong>Cable</strong> TerminationsESP245IIESPProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESP245-C103 240-2000 52 - 99 120 705 10339 - 38ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESP245-C103 500 400 19 ~550 2941 100 30,40,50 334/50622 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESP300IIESPProductdesignationConductorcross sectionDiameter overcable insulation(prepared)max. diameterover outercable sheathNet weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (mm) (kg) (mm) (mm/kV)ESP300-C103 240-2000 52 - 99 120 705 10339 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)ESP300-C103 500 400 19 ~550 2941 100 30,40,50 334/506www.pfisterer.com23


IXOSIL <strong>Cable</strong> TerminationsFlexible Outdoor <strong>Cable</strong> TerminationESF flexible terminations are dry, slip-on terminations <strong>for</strong> modular assembly. The use ofsilicone sheds makes them ideally suited <strong>for</strong> applications in outdoor installations and areavailable <strong>for</strong> a <strong>voltage</strong> range from 52 kV to 145 kV. Medium <strong>voltage</strong> versions <strong>for</strong> 10 kV,20 kV and 30 kV are available on request.IIESFMaterial:Insulator: silicone rubberStress relief cone: silicone rubberConductor connection:compressed or screwedNote:Various connection optionsPollution class 1 (16 mm/kV) on requestMax. operating <strong>voltage</strong> U m(kV) 52 72.5 123 145StandardsIEC60840IEC60815IEC60840IEC60815IEC60840IEC60815IEC60815Rated <strong>voltage</strong> U (kV) 45 - 47 60 - 69 110 - 115 132 - 138Rated lightning impulsewithstand <strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 250 325 550 550(pC) < 5 < 5 < 5 < 524 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESF52IIESFProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)ESF52-C11 95-1000 28 - 76.2 10 1040 2 20ESF52-C13 95-1000 28 - 76.2 12 1300 3 25ESF52-C17 95-1000 28 - 76.2 13 1612 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm)ESF52-C11 ~250 ~764 213 - 222 110 - 135ESF52-C13 ~250 ~824 - 884 213 - 222 110 - 135ESF52-C17 ~250 ~944 - 1004 213 - 222 110 - 135www.pfisterer.com25


IXOSIL <strong>Cable</strong> TerminationsESF72IIESFProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)ESF72-C15 95-1000 28 - 76.2 12 1450 2 20ESF72-C19 95-1000 28 - 76.2 14 1813 3 25ESF72-C23 95-1000 28 - 76.2 17 2248 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm)ESF72-C15 ~250 ~884 - 944 213 - 222 110 - 135ESF72-C19 ~250 ~1004 - 1064 213 - 222 110 - 135ESF72-C23 ~250 ~1184 - 1244 213 - 222 110 - 13526 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESF123IIESFProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)ESF123-C25 95-1000 28 - 76.2 19 2460 2 20ESF123-C31 95-1000 28 - 76.2 21 3075 3 25ESF123-C39 95-1000 28 - 76.2 22 3813 4 31ProductdesignationA (mm) B (mm) C (mm) D (mm)ESF123-C25 ~250 ~1300 - 1360 190 180ESF123-C31 ~250 ~1480 - 1600 190 180ESF123-C39 ~250 ~1480 - 1600 190 180www.pfisterer.com27


IXOSIL <strong>Cable</strong> TerminationsESF145IIESFProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)ESF145-C29 240-1000 52.7 - 92.3 20 2900 2 20ESF145-C45 240-1000 52.7 - 92.3 24 4495 4 31ESF145-C37 240-1000 52.7 - 92.3 23 3625 3 25ProductdesignationA (mm) B (mm) C (mm) D (mm)ESF145-C29 ~250 ~1480 220 210ESF145-C45 ~250 ~2020 - 2140 220 210ESF145-C37 ~250 ~1720 - 1780 220 21028 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsOutdoor <strong>Cable</strong> Termination (Dry Type)The EST termination is ideally suited <strong>for</strong> outdoor and indoor use. It is available <strong>for</strong> <strong>voltage</strong>sfrom 72,5 kV to 145 kV and consists of one flexible ESF termination and three postinsulators. It contains no liquid insulating materials, can be installed in any position and isself-supporting.The EST is of modular construction <strong>for</strong> rapid, easy installation. The base plate designallows installations on existing units.Material:Insulator: silicone shielded fibre glass rein<strong>for</strong>ced rodStress relief cone: silicone rubberShed material: silicone rubberESTIIConductor connection:compressed or screwedNote:Various connection optionsVersions in pollution class 1 (16mm/kV) on requestThe terminations are tailored according to the customer‘s specifications. Thus, moredetailed technical in<strong>for</strong>mation are available on request.Max. operating <strong>voltage</strong> U m(kV) 72.5 123 145StandardsIEC60815IEC60840IEC60815IEC60840IEC60815Rated <strong>voltage</strong> U (kV) 60 - 69 110 - 115 132 - 138Rated lightning impulse withstand<strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 325 550 550(pC) < 5 < 5 < 5www.pfisterer.com29


IXOSIL <strong>Cable</strong> TerminationsEST72IIESTProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)EST72-C15 95-1000 28 - 76.2 63 1450 2 20EST72-C23 95-1000 28 - 76.2 68 2248 4 31EST72-C19 95-1000 28 - 76.2 65 1813 3 2530 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsEST123IIESTProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)EST123-C25 95-1000 28 - 76.2 53 2460 2 20EST123-C31 95-1000 28 - 76.2 58 3075 3 25EST123-C39 95-1000 28 - 76.2 66 3813 4 31www.pfisterer.com31


IXOSIL <strong>Cable</strong> TerminationsEST145IIESTProductdesignationConductor crosssectionDiameter overcable insulation(prepared)Net weightapprox.minimalcreepagedistancePollution classPollution class(mm 2 ) (mm) (kg) (mm) (mm/kV)EST145-C29 240-1000 52.7 - 92.3 64 2900 2 20EST145-C45 240-1000 52.7 - 92.3 76 4495 4 31EST145-C37 240-1000 52.7 - 92.3 69 3625 3 2532 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsFlexible Indoor <strong>Cable</strong> TerminationESK terminations are dry, modular, slide-on terminations <strong>for</strong> 52 kV and 72,5 kV. The useof silicone shields makes them ideally suited <strong>for</strong> applications in indoor installations.Material:Stress relief cone: silicone rubberShed material: silicone rubberConductor connection:compressed or screwed.IINote:Various connection optionsThe creepage distance depends on the diameter of the prepared cable insulationESKMax. operating <strong>voltage</strong> U m(kV) 52 72.5Standards IEC60815 IEC60815Rated <strong>voltage</strong> U (kV) 45 60Rated lightning impulse withstand<strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 250 350(pC) < 5 < 5www.pfisterer.com33


IXOSIL <strong>Cable</strong> TerminationsESK52IIESKProductdesignationConductor crosssectionDiameter over cableinsulation (prepared)Net weightapprox.(mm 2 ) (mm) (kg) (mm)min. creepagedistanceESK52-N1 95-1000 28 - 76.2 8 758 - 800 1ESK52-N2 95-1000 28 - 76.2 10 1031 - 1100 2Number of shedsProductdesignationA (mm) B (mm) C (mm) D (mm)ESK52-N1 ~250 700 140-200 110-135ESK52-N2 ~250 935 140-200 110-13534 www.pfisterer.com


IXOSIL <strong>Cable</strong> TerminationsESK72IIESKProductdesignationConductor crosssectionDiameter over cableinsulation (prepared)Net weightapprox.(mm 2 ) (mm) (kg) (mm)min. creepagedistanceESK72-N2 95-1000 28 - 76.2 10 1031 - 1100 2ESK72-N3 95-1000 28 - 76.2 12 1303 - 1400 3Number of shedsProductdesignationA (mm) B (mm) C (mm) D (mm)ESK72-N2 ~250 935 140-200 110-135ESK72-N3 ~250 1170 140-200 110-135www.pfisterer.com35


HV-CONNEX Pluggable Connection SystemHV-CONNEX 72.5 kV – 245 kVThe advantages of the CONNEX system come to the <strong>for</strong>e in particular in the area of <strong>high</strong><strong>voltage</strong>systems: simple on-site installation and factory-tested components save moneyand provide additional safety. Plug-in HV-CONNEX systems make costly oil and gas workduring the installation and commissioning of trans<strong>for</strong>mers and gas-insulated switchgeara thing of the past. Thanks to their plug-in connectors, cable joints from the HV-CONNEXrange are much more flexible than traditional solutions when it comes to building andconverting electrical systems. Needless to say, the range includes all the connection componentsneeded to test the system and the attached equipment.AdvantagesIIIHV-CONNEX Pluggable Connection SystemA Bushing1 female contact part2 insulating bushing3 housingB Contact system4 contact ring5 tension cone6 thrust piecen approx. 50 % shorter mounting length compared with conventional systemsin accordance with IEC60859 and IEC62271-209n no opening of the cable termination and associated costly gas or oil workn horizontal, vertical and angled versions <strong>for</strong> connection to GIS and trans<strong>for</strong>mersn considerably reduced installation timesn the use of pre-assembled and tested components means maximum safetyand efficiencyn installation errors are minimisedn if a fault does arise, rapid separation of cable and equipmentA B C DC Insulating and field-control partD Housing7 pressure sleeve8 pressure spring9 bell flange10 gasket11 threaded counter ring12 heat-shrink13 cable screen1 2 3 4 5 6 7Sample drawing: <strong>Cable</strong> connecting System Size 5-S89 10 11 12 1336 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemGIS EquipmentHV-CONNEX bushings require less space than conventionaltype connectors. All well-known manufacturers have sincebegun to offer equipment which exploits this advantage. Anextension adapter <strong>for</strong> conventional cable connector modulesis required when HV- CONNEX is used with traditional GISequipment.Trans<strong>for</strong>mersThe installation of two connectors on the equipment makes itpossible to have one cable connector on the side, facing down.If it is necessary to connect this kind of trans<strong>for</strong>mer using anoverhead line, an HV-CONNEX plug-in insulator <strong>for</strong> overheadlines can be installed and the downward facing cable connectorthen terminated with a dummy connector. This plug-in insulatoralso makes it very easy to carry out simple <strong>voltage</strong> tests on trans<strong>for</strong>mersfitted with HV-CONNEX equipment connectors, either inthe factory or on site.Plug-in Joint BoxesThe HV-CONNEX cable connection system means plug-in joint boxes<strong>for</strong> various geometric configurations can be assembled usingfewer components. The advantage of these joint boxes is that thejoint body is a single unit which is completely manufactured andtested at the factory. Solutions of this kind bring enormous benefitsif, <strong>for</strong> example, cables need to be bent back multiple timesduring the installation and conversion phase.HV-CONNEX Pluggable Connection SystemIIIwww.pfisterer.com37


HV-CONNEX Pluggable Connection SystemHV-CONNEX Seperable Connector Size 4 - 6-STechnical Data and Size Classification List*)Packing Unit = 1 pieceIIIHV-CONNEX Pluggable Connection SystemSize 4 5-S 6 6-SMax. operating <strong>voltage</strong> U m(kV) 72.5 145 170 245Nominal current I N(A) 2500 2500 2500 2500Cross section range (mm 2 ) 95 - 1600 95 - 1600 240 - 2000 240 - 2000Minimum conductordiameterØ (mm) 9.3 9.3 15.3 15.3Max. conductor diameter Ø (mm) 50.4 50.4 58.4 58.4Min. diameter overinsulationMax. diameter overinsulationØ (mm) 33.0 36.0 53.0 53.0Ø (mm) 71.0 76.0 110.0 110.0Gross weight(kg) 18.5 22.0 27.0 27.0per packing unit *)Rated power frequencywithstand <strong>voltage</strong>1min (kV) 140 275 325 460Partial discharge 2 x U 0(pC) ≤ 2 ≤ 2 ≤ 2 ≤ 2Rated lightning impulsewithstand <strong>voltage</strong> (BIL)(kV) 325 650 750 1050DC <strong>voltage</strong> test 15 min 6 x U 0(kV) 144 304 348 508Rated short-time withstandcurrentRated short-time withstandcurrent0,5 s (kA) 63 63 63 631 s (kA) 50 50 50 50Rated impulse current (kA) 160 160 160 16038 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemForm to determine HV-Separable ConnectorsCompany:Telephone:E-mail:Name:Date:Signature:<strong>Cable</strong> manufacturer:<strong>Cable</strong> type:Voltages: U O(phase/earth) kV U N(phase/phase) kV Max. operating <strong>voltage</strong> U M(2 x U O) kVShort circuit current: 1 sec. short circuit current screen/sheath kA<strong>Cable</strong> design: single core cable three core cable single core superflexible cable three core superflexible cableSize of bushing: Size 4 Size 5-S Size 6 Size 6-S1 Conductor: Material: Cu Al Cross section: mm 2 Diameter: ø mmType: stranded circular RM solid circular REstranded circular, segment RMS superflexible stranded RF2 Insulation: XLPE PVC EPR Diameter over insulation: ø mm3 Semi-conducting layer: Type: fully bonded easy strip graphite Diameter over semi-conducting layer: ø mm4 Metallic sheath/screen: yes noType: Copper wire Copper band Lead sheath Lead sheath/Copper wireCopper-corrugated sheath Al-corrugated sheathCross section: mm 2 Section thickness: mm Diameter over screen: ø mmFibre optic cable in the pipe: yes no5 Inner sheath: yes no Metallic screen: yes no Diameter over inner sheath: ø mmHV-CONNEX Pluggable Connection SystemIII6 Armouring: 1. Armouring: yes no Material: Steel other materialType: Flat conductors Circular conductors Band Diameter over 1. armouring: ø mm2. Armouring: yes no Material: Steel other materialType: Flat conductors Circular conductors Band Diameter over 2. armouring: ø mm7 Outer sheath: Metallic screen: yes no Overall diameter: ø mmConductibility: yes noOutdoor installation vertical from on <strong>high</strong>: yesno1 2 3 45 6 7www.pfisterer.com39


HV-CONNEX Pluggable Connection SystemHV-CONNEX <strong>Cable</strong> Connectors, Size 4, up to 72,5 kV*)Individual article number determined according to actual cable dimensions (see <strong>for</strong>m todetermine HV-Separable Connectors).Important:Special tools are required <strong>for</strong> the assembly of HV-CONNEX cable connectors, size 4.(see mounting accessories)IIISize 4No. Version NominalcurrentCross sectionrangeConductordiameterDiameter overinsulationI N(A) (mm 2 ) Ø (mm) Ø (mm)849 999 999 XXXX *) 2500 95 - 1600 9,3 - 50,4 33,0 - 71,040 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemHV-CONNEX Sockets, Size 4, up to 72.5 kVFor installation in:power circuit-breaker units, trans<strong>for</strong>mers, E-Coils, joints and other equipmentincluding fixing materialIIISize 4No.Capacitive <strong>voltage</strong>tap(pF)O-ring sealingsystemWeight(kg)827 682 001 with without 17.5827 682 002 without without 17.5IEC Extension Adapter, Size 4To adapt traditional GIS units into conventional cable connection components.No. IEC dimensions Weight827 704 002 583 7.5(kg)www.pfisterer.com41


HV-CONNEX Pluggable Connection SystemHV-CONNEX Joint, Size 4HV-CONNEX Joint <strong>for</strong> testing and connecting cables that are sealed with HV-CONNEXcable connectors.Insulation medium: SF 6gas.The joint has an anti-burst device.Dummy plugs to be ordered separately.IIISize 4No. Size Max.operating<strong>voltage</strong>Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Width Length WeightU m(kV) 1min (kV) (kV) (mm) (mm) (kg)827 049 010 4 72.5 140 325 450 1150 117.0Lead, Size 4The lead with flexible free air terminations can be used <strong>for</strong> electrical tests on equipmentfitted with HV-CONNEX sockets.<strong>Cable</strong> length can be changed on request.*)Values mentioned are maximum testing values, which will decrease the expected lifespan.No. Size Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Partialdischarge<strong>Cable</strong> crosssection1min (kV) (kV) 2 x U 0(pC) (mm 2 ) (m)Length810 105 410 4 140 325 72 kV ≤ 2 pC 240 6*)42 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemCurrent Testing Plug, Size 4This plug is used to carry out current tests on switchgear, trans<strong>for</strong>mers, transducers etc.fitted with HV-CONNEX sockets.IIISize 4No.Nominalcurrenta b c dI N(A) (mm) (mm) (mm) (mm)827 093 004 1600 177 40 301 435Dummy Plug, Size 4For sealing und <strong>voltage</strong>-proof closing of HV-CONNEX sockets.No.Weight(kg)827 700 004 5.0www.pfisterer.com43


HV-CONNEX Pluggable Connection SystemEarthing and Short-circuit Devices <strong>for</strong> HV-CONNEX Sockets,Size 4These devices are used to earth and short circuit equipment fitted with HV-CONNEXsockets (e. g. switchgear, trans<strong>for</strong>mers etc.).IIISize 4No. a b c d Weight(mm) (mm) (mm) (mm) (kg)827 086 004 177 40 301 435 10.5Earthing and Protective Cap, Size 4This device is used to earth and short circuit unplugged HV-CONNEX cable connectors.■ not <strong>voltage</strong> proof■ waterproofFor protection of unplugged HV-CONNEX cable connectors against damage and dirt.No. Weight a b c L(kg) (mm) (mm) (mm) (mm)827 708 002 5.7 210 240 97 37544 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemHV-CONNEX T-Joint, Size 4HV-CONNEX T-joint <strong>for</strong> branching cables terminated with HV-CONNEX cable connections.Insulation medium: SF 6gasThe T-joint has an anti-burst device.Dummy plugs to be ordered separately.Possible Applications:■ Plug-in branching joint <strong>for</strong> HV cable lengths■ Universal application options:T-branching one plastic cable onto two plastic cables or overhead line to twoplastic cablesProperties:■ metal-clad■ fully insulated■ <strong>high</strong> short-circuit resistance■ maintenance-free■ <strong>for</strong> outdoor use■ IP66■ maintenance-free gas density monitor (manometer) with remote monitoring option■ bursting disk■ plug sizes 4, 5-S and 6 can be combined■ insulation medium SF 6■ TÜV-tested housingSize 4IIINo. Size Max.operating<strong>voltage</strong>Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Width Length WeightU m(kV) 1min (kV) (kV) (mm) (mm) (kg)827 062 001 4 72.5 140 325 790 1190 475.0www.pfisterer.com45


HV-CONNEX Pluggable Connection SystemHV-CONNEX <strong>Cable</strong> Connectors, Size 5-S, up to 145 kV*)Individual article number determined according to actual cable dimensions (see <strong>for</strong>m todetermine HV-Separable Connectors).Important:Special tools are required <strong>for</strong> the assembly of HV-CONNEX cable connectors, size 5-SNo. Version NominalcurrentCross sectionrangeConductordiameterDiameter overinsulationI N(A) (mm 2 ) Ø (mm) Ø (mm)859 999 999 XXXX *) 2500 95 - 1600 9,3 - 50,4 36,0 - 76,0IIISize 5-SHV-CONNEX Sockets, Size 5-S, up to 145 kVFor installation in:power circuit-breaker units, trans<strong>for</strong>mers, E-Coils, joints and other devicesincluding fixing materialNo.Capacitive <strong>voltage</strong>tap(pF)O-ring sealingsystemWeight(kg)827 691 006 - without 32.0827 691 016 4 without 32.046 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemIEC Extension AdapterTo adapt traditional GIS units into conventional cable connection components.12IIISize 5-SNo. IEC dimensions Weight(kg)827 702 002 470 1.5 1827 704 001 757 8.4 2www.pfisterer.com47


HV-CONNEX Pluggable Connection SystemDummy Plug, Size 5-SFor sealing and <strong>voltage</strong>-proof closing of HV-CONNEX sockets.IIISize 5-SNo.Weight(kg)827 701 002 7.7Lead, Size 5-SThe lead can be used <strong>for</strong> electrical tests on equipment fitted with HV-CONNEX sockets.Ideal <strong>for</strong> <strong>voltage</strong> tests and partial discharge tests on:■ trans<strong>for</strong>mers■ gas-insulated switchgears*)Values mentioned are maximum testing values, which will decrease the expected lifespan.No. Size Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Partialdischarge<strong>Cable</strong>crosssection1min (kV) (kV) 2 x U 0(pC) (mm 2 ) (m)Length810 105 510 5-S 275 550 160 kV ≤ 5 pC 300 10*)48 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemTest Adapters, Size 5-SHV-CONNEX test adapters are used <strong>for</strong> electrical tests on equipment fitted with HV-CONNEX sockets.The test adapter has a capacitive <strong>voltage</strong> tap.12IIISize 5-SNo. Size NominalcurrentRatedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)PartialdischargeWeightI N(A) 1min (kV) (kV) 2 x U 0(pC) (kg)828 186 002 5-S 1250 275 650 160 kV ≤5 pC828 186 004 5-S 1250 275 650 160 kV ≤5 pC65.0 165.0 2www.pfisterer.com49


HV-CONNEX Pluggable Connection SystemCurrent Testing Plug, Size 5-SThis plug is used to carry out current tests on switchgear, trans<strong>for</strong>mers, transducers etc.fitted with HV-CONNEX sockets.IIISize 5-SNo.NominalcurrentMax.operating <strong>voltage</strong>a b c dI N(A) U m(kV) (mm) (mm) (mm) (mm)827 093 005 1600 3.5 188 40 416 550Earthing and Short-circuit Devices <strong>for</strong> HV-CONNEX Sockets,Size 5-SThese devices are used to earth and short circuit equipment fitted with HV-CONNEXsockets (e. g. switchgear, trans<strong>for</strong>mers etc.).No. a b c d(mm) (mm) (mm) (mm)827 086 005 188 40 416 55050 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemEarthing and Protective Cap, Size 5-SThis device is used to earth and short circuit unplugged HV-CONNEX cable connectors.■ not <strong>voltage</strong> proof■ waterproofFor protection of unplugged HV-CONNEX cable connectors against damage and dirt.IIINo. Size Weight a b c L(kg) (mm) (mm) (mm) (mm)827 708 001 5-S 6.5 220 355 97 490Size 5-SHV-CONNEX Joint, Size 5-SHV-CONNEX Joint <strong>for</strong> testing and connecting cables that are sealed with HV-CONNEXcable connectors.Insulation medium: SF 6gas.The joint has an anti-burst device.Dummy plugs to be ordered separately.No. Size Max.operating<strong>voltage</strong>Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Width Length WeightU m(kV) 1min (kV) (kV) (mm) (mm) (kg)827 052 010 5-S 145 275 550 450 1150 139.0www.pfisterer.com51


HV-CONNEX Pluggable Connection SystemHV-CONNEX T-joint, Size 5-SHV-CONNEX T-joint <strong>for</strong> branching cables terminated with HV-CONNEX cable connections.Insulation medium: SF 6gasThe T-joint has an anti-burst device.Dummy plugs to be ordered separately.Possible Applications:■ Plug-in branching joint <strong>for</strong> HV cable lengths■ Universal application options:T- branching one plastic cable onto two plastic cables or overhead line to two plasticcablesIIISize 5-SProperties:■ metal-clad■ fully insulated■ <strong>high</strong> short-circuit resistance■ maintenance-free■ <strong>for</strong> outdoor use■ IP66■ maintenance-free gas density monitor (manometer) with remote monitoring option■ bursting disk■ plug sizes 4, 5-S and 6 can be combined■ insulation medium SF 6■ TÜV-tested housingNo. Size Max.operating<strong>voltage</strong>Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Width Length WeightU m(kV) 1min (kV) (kV) (mm) (mm) (kg)827 047 101 5-S 145 275 650 780 1400 530.052 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemHV-CONNEX <strong>Cable</strong> Connectors, Size 6 / 6-S, up to 170 / 245 kV*)Individual article number determined according to actual cable dimensions (see <strong>for</strong>m todetermine HV-Separable Connectors).Important:Special tools are required <strong>for</strong> the assembly of HV-CONNEX cable connectors, size 6IIISize 6No. Version NominalcurrentCross sectionrangeConductordiameterDiameter overinsulationI N(A) (mm 2 ) Ø (mm) Ø (mm)869 999 999 XXXX *) 2500 240 - 2000 15,3 - 58,4 53,0 - 110,0HV-CONNEX Sockets, Size 6, up to 170 kVFor installation in:power circuit-breaker units, trans<strong>for</strong>mers, E-Coils, joints and other devicesincluding fixing materialNo.Capacitive <strong>voltage</strong>tap(pF)O-ring sealingsystemWeight(kg)827 692 002 - without 31.5827 692 004 7 without 31.5www.pfisterer.com53


HV-CONNEX Pluggable Connection System1IEC Extension AdapterTo adapt traditional GIS units into conventional cable connection components.2IIISize 6No. IEC dimensions Weight(kg)827 702 002 470 1.5 1827 704 001 757 8.4 254 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemDummy Plug, Size 6 / 6-SFor sealing and <strong>voltage</strong>-proof closing of HV-CONNEX sockets.IIISize 6No.Weight(kg)827 706 001 13.2www.pfisterer.com55


HV-CONNEX Pluggable Connection System1Test Adapters, Size 6HV-CONNEX test adapters are used <strong>for</strong> electrical tests on equipment fitted with HV-CONNEX sockets.The test adapter has a capacitive <strong>voltage</strong> tap.2IIISize 6No. Size NominalcurrentRatedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)PartialdischargeWeightI N(A) 1min (kV) (kV) 2 x U 0(pC) (kg)828 187 009 6 1250 325 750 170 kV ≤5 pC828 187 008 6 1250 325 750 170 kV ≤5 pC65.0 165.0 256 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemCurrent Testing Plug, Size 6 / 6-SThis plug is used to carry out current tests on switchgear, trans<strong>for</strong>mers, transducers etc.fitted with HV-CONNEX sockets.IIISize 6No.NominalcurrentMax.operating <strong>voltage</strong>a b c dI N(A) U m(kV) (mm) (mm) (mm) (mm)827 093 006 1600 5 245 40 451 585Earthing and Short-circuit Devices <strong>for</strong> HV-CONNEX Sockets,Size 6 / 6-SThese devices are used to earth and short circuit equipment fitted with HV-CONNEXsockets (e. g. switchgear, trans<strong>for</strong>mers etc.).No. a b c d(mm) (mm) (mm) (mm)827 086 006 245 40 451 585www.pfisterer.com57


HV-CONNEX Pluggable Connection SystemEarthing and Protective Cap, Size 6 / 6-SThis device is used to earth and short circuit unplugged HV-CONNEX cable connectors.■ not <strong>voltage</strong> proof■ waterproofFor protection of unplugged HV-CONNEX cable connectors against damage and dirt.IIISize 6No. a b c L(mm) (mm) (mm) (mm)827 708 003 270 410 105 550HV-CONNEX Joint, Size 6HV-CONNEX joint <strong>for</strong> testing and connecting cables that are sealed with HV-CONNEXcable connectors.Insulation medium: SF 6gas.The joint has an anti-burst device.Dummy plugs to be ordered separately.No. Size Max.operating<strong>voltage</strong>Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Width Length WeightU m(kV) 1min (kV) (kV) (mm) (mm) (kg)827 053 010 6 170 325 750 450 1150 186.058 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemHV-CONNEX T-Joint, Size 6HV-CONNEX T-joint <strong>for</strong> branching cables terminated with HV-CONNEX cable connections.Insulation medium: SF 6The T-joint has an anti-burst device.Dummy plugs to be ordered separately.Possible Applications:■ Plug-in branching joint <strong>for</strong> HV cable lengths■ Universal application options:T-branching one plastic cable onto two plastic cables or overhead line to two plasticcablesProperties:■ metal-clad■ fully insulated■ <strong>high</strong> short-circuit resistance■ maintenance-free■ <strong>for</strong> outdoor use■ IP66■ maintenance-free gas density monitor (manometer) with remote monitoring option■ bursting disk■ plug sizes 4, 5-S and 6 can be combined■ insulation medium SF 6■ TÜV-tested housingSize 6IIINo. Size Max.operating<strong>voltage</strong>Ratedpowerfrequencywithstand<strong>voltage</strong>Ratedlightningimpulsewithstand<strong>voltage</strong>(BIL)Width Length WeightU m(kV) 1min (kV) (kV) (mm) (mm) (kg)827 057 001 6 170 325 750 780 1670 475.0www.pfisterer.com59


HV-CONNEX Pluggable Connection SystemHV-CONNEX <strong>Cable</strong> Connectors, Size 6 / 6-S, up to 170 / 245 kV*)Individual article number determined according to actual cable dimensions (see <strong>for</strong>m todetermine HV-Separable Connectors).Important:Special tools are required <strong>for</strong> the assembly of HV-CONNEX cable connectors, size 6IIISize 6-SNo. Version NominalcurrentCross sectionrangeConductordiameterDiameter overinsulationI N(A) (mm 2 ) Ø (mm) Ø (mm)869 999 999 XXXX *) 2500 240 - 2000 15,3 - 58,4 53,0 - 110,060 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemHV-CONNEX Sockets, Size 6-S, up to 245 kVFor installation in:power circuit-breaker units, trans<strong>for</strong>mers, E-Coils, joints and other devicesincluding fixing materialIIINo.Capacitive<strong>voltage</strong> tap(pF)O-ring sealingsystemWeight(kg)Reducingflangeaccording toIEC60859Reducingflangeaccording toIEC62271-209827 693 002 - without 31.5 565554003 565554004827 693 005 1 without 31.5 565554003 565554004Size 6-Swww.pfisterer.com61


HV-CONNEX Pluggable Connection SystemFlange, Size 6-SIIISize 6-SNo. Dimension A Dimension B Dimension C Dimension D Suitable <strong>for</strong>socketA (mm) B (mm) C (mm) D (mm)565 554 003 255 582 620 17 827 693 002827 693 005565 554 004 255 454 500 13 827 693 002827 693 00562 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemIEC Extension Adapter, Size 6-STo adapt the size 6-S HV-CONNEX socket into conventional cable connection components<strong>for</strong> traditional GIS units.12IIISize 6-SNo. IEC dimensions Weight(kg)827 707 001 960 16.9 1827 707 002 620 13.7 2www.pfisterer.com63


HV-CONNEX Pluggable Connection SystemDummy Plug, Size 6 / 6-SFor sealing and <strong>voltage</strong>-proof closing of HV-CONNEX sockets.IIISize 6-SNo.Weight(kg)827 706 001 13.2Current Testing Plug, Size 6 / 6-SThis plug is used to carry out current tests on switchgear, trans<strong>for</strong>mers, transducers etc.fitted with HV-CONNEX sockets.No.NominalcurrentMax.operating <strong>voltage</strong>a b c dI N(A) U m(kV) (mm) (mm) (mm) (mm)827 093 006 1600 5 245 40 451 58564 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemEarthing and Short-circuit Devices <strong>for</strong> HV-CONNEX Sockets,Size 6 / 6-SThese devices are used to earth and short circuit equipment fitted with HV-CONNEXsockets (e. g. switchgear, trans<strong>for</strong>mers etc.).IIISize 6-SNo. a b c d(mm) (mm) (mm) (mm)827 086 006 245 40 451 585Earthing and Protective Cap, Size 6 / 6-SThis device is used to earth and short circuit unplugged HV-CONNEX cable connectors.■ not <strong>voltage</strong> proof■ waterproofFor protection of unplugged HV-CONNEX cable connectors against damage and dirt.No. a b c L(mm) (mm) (mm) (mm)827 708 003 270 410 105 550www.pfisterer.com65


HV-CONNEX Pluggable Connection SystemHV-CONNEX Joint, Size 6-SHV-CONNEX joint <strong>for</strong> testing and connecting cables that are sealed with HV-CONNEXcable connectors.Insulation medium: SF 6gas.The joint has an anti-burst device.Dummy plugs to be ordered separately.IIISize 6-SNo. Size Max.operating <strong>voltage</strong>Rated powerfrequencywithstand<strong>voltage</strong>Rated lightningimpulse withstand<strong>voltage</strong>(BIL)WeightU m(kV) 1min (kV) (kV) (kg)827 059 010 6-S 245 460 1050 345.066 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemApplicationsIIIHV-CONNEX Pluggable Connection Systemwww.pfisterer.com67


HV-CONNEX Pluggable Connection SystemAssembly AccessoriesTools <strong>for</strong> HV-CONNEX, Sizes 4, 5-S, 6 and 6-SPush-on Device<strong>for</strong> assembly of insulating partNo. Size Weight(kg)827 103 002 4 - 6-S 8.5IIIMounting AccessoriesImpact Head<strong>for</strong> pre-assembly of contact part.No. Size Weight(kg)559 214 004 4, 5-S 0.4559 214 006 6, 6-S 0.6Hydraulic Hand-Operated Compression Toolwith compression head <strong>for</strong> axial compression of the contact ring <strong>for</strong> HV-CONNEX cableconnectors.No. Size Weight(kg)827 017 003 4, 5-S 6.5827 017 004 6, 6-S 6.5Spacing Bolt with Eye-bolt<strong>for</strong> mounting of the block and tackleNo. Size Weight(kg)564 471 001 4 - 6-S 0.5Block and Tackleinsulated, used <strong>for</strong> plug-in of HV-CONNEX cable connector into socket.No. Size Weight(kg)619 891 001 4 - 6-S 3.268 www.pfisterer.com


HV-CONNEX Pluggable Connection SystemHook Wrench<strong>for</strong> screwing of the bell flanges threaded counter ring.No. Size Weight(kg)827 087 001 4 - 6-S 1.2Hexagonal Wrench<strong>for</strong> screwing on the bell flange.No. Size Weight(kg)546 004 018 4 0.1546 004 010 5-S, 6, 6-S 0.2HV Special Greasegreasing of insulating part, socket etc.No. Size Weight(g)002 854 002 4 - 6-S 8Mounting AccessoriesIIIHV-CONNEX Sealing Set <strong>for</strong> Outdoor Vertical Installation fromabovee.g. on trans<strong>for</strong>mers <strong>for</strong> sizes 4, 5-S, 6 and 6-SNo.Size545 051 001 4 - 6-SHV <strong>Cable</strong> Stripper <strong>for</strong> <strong>Cable</strong> FinishingNo.827 976 001SF 6gas refill deviceFor filling of HV Test- and T-JointsNo.827 017 100www.pfisterer.com69


IXOSIL Trans<strong>for</strong>mer and GIS ConnectorsGIS <strong>Cable</strong> TerminationESG terminations: the conventional solution <strong>for</strong> inserting XLPE insulated cables directlyinto gas filled equipment. They are available in vertical, horizontal or upside-down versionsfrom 72,5 kV to 170 kV.Material:Insulator: cast resinStress relief cone: silicone rubberConductor connection:compressed or screwedOptional accessories:Adapter FlangeNote:Horizontal version is equipped with an expansion vessel.Upside-down version on request.Optional material is not within scope of supply and has to be ordered seperately.IVESGMax. operating <strong>voltage</strong> U m(kV) 72.5 123 145 170StandardsIEC60840IEC60859IEC62271IEC60840IEC60859IEC62271IEC60840IEC60859IEC62271IEC60840IEC60859IEC62271Rated <strong>voltage</strong> U (kV) 60 - 69 110 - 115 132 - 138 150 - 161Rated lightning impulsewithstand <strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 325 550 650 750(pC) < 5 < 5 < 5 < 570 www.pfisterer.com


IXOSIL Trans<strong>for</strong>mer and GIS ConnectorsESG72 12IVESGProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESG72-H 95-2000 37 - 89 120 55 1ESG72-V 95-2000 37 - 89 120 52 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESG72-H 270 80 ± 0,3 295 8 x Ø11 255 245 ± 0,3 184 583 ± 1 100 4 x M10 24 7ESG72-V 270 80 ± 0,3 295 8 x Ø11 255 245 ± 0,3 184 583 ± 1 100 4 x M10 24 7www.pfisterer.com71


IXOSIL Trans<strong>for</strong>mer and GIS Connectors1ESG1232IVESGProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESG123-H 150-2000 46 - 99 120 78 1ESG123-V 150-2000 46 - 99 120 72 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESG123-H 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7ESG123-V 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 772 www.pfisterer.com


IXOSIL Trans<strong>for</strong>mer and GIS ConnectorsESG145 12IVESGProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESG145-H 150-2000 46 - 99 120 78 1ESG145-V 150-2000 46 - 99 120 72 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESG145-H 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7ESG145-V 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7www.pfisterer.com73


IXOSIL Trans<strong>for</strong>mer and GIS Connectors1ESG1702IVESGProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESG170-H 150-2000 46 - 99 120 78 1ESG170-V 150-2000 46 - 99 120 72 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESG170-H 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7ESG170-V 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 774 www.pfisterer.com


IXOSIL Trans<strong>for</strong>mer and GIS ConnectorsTrans<strong>for</strong>mer <strong>Cable</strong> TerminationESU terminations: the conventional solution <strong>for</strong> inserting XLPE insulated cables directlyinto oil filled equipment. They are available in vertical, horizontal or upside-down versionsfrom 72,5 kV to 170 kV.Material:Insulator: cast resinStress relief cone: silicone rubberConductor connection:compressed or screwedOptional accessories:Adapter Flange, Stress Control ElectrodeNote:Horizontal version is equipped with an expansion vessel.Upside-down version on request.Optional material is not within scope of supply and has to be ordered seperately.Max. operating <strong>voltage</strong> U m(kV) 72.5 123 145 170StandardsIEC60840EN50299IEC60840EN50299IEC60840EN50299IEC60840EN50299Rated <strong>voltage</strong> U (kV) 60 - 69 110 - 115 132 - 138 150 - 161Rated lightning impulsewithstand <strong>voltage</strong> (BIL)Partial dischargemeasurement(kV) 325 550 650 750(pC) < 5 < 5 < 5 < 5ESUIVwww.pfisterer.com75


IXOSIL Trans<strong>for</strong>mer and GIS Connectors1ESU722IVESUProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESU72-H 95-2000 37 - 89 120 55 1ESU72-V 95-2000 37 - 89 120 52 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESU72-H 270 80 ± 0,3 295 8 x Ø11 255 245 ± 0,3 184 583 ± 1 100 4 x M10 24 7ESU72-V 270 80 ± 0,3 295 8 x Ø11 255 245 ± 0,3 184 583 ± 1 100 4 x M10 24 776 www.pfisterer.com


IXOSIL Trans<strong>for</strong>mer and GIS ConnectorsESU123 12IVESUProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESU123-H 150-2000 46 - 99 120 78 1ESU123-V 150-2000 46 - 99 120 72 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESU123-H 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7ESU123-V 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7www.pfisterer.com77


IXOSIL Trans<strong>for</strong>mer and GIS Connectors1ESU1452IVESUProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESU145-H 150-2000 46 - 99 120 78 1ESU145-V 150-2000 46 - 99 120 72 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESU145-H 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7ESU145-V 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 778 www.pfisterer.com


IXOSIL Trans<strong>for</strong>mer and GIS ConnectorsESU170 12IVESUProductdesignationConductor cross sectionDiameter over cableinsulation (prepared)max. diameter over outercable sheath(mm 2 ) (mm) (mm) (kg)Net weightapprox.ESU170-H 150-2000 46 - 99 120 78 1ESU170-V 150-2000 46 - 99 120 72 2ProductdesignationA (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) I (mm) J (mm) K (mm) L (mm)ESU170-H 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7ESU170-V 320 80 ± 0,3 345 12 x Ø13,5 303 298 ± 0,3 200 757 ± 1 100 4 x M10 24 7www.pfisterer.com79


PFISTERER worldwidePFISTERERKontaktsysteme GmbH & Co. KGRosenstraße 4473650 WinterbachGermanyPhone +49 (0) 7181 7005 0Fax +49 (0) 7181 7005 565E-mail dialog@pfi sterer.dePFISTERER IXOSIL AGGotthardstrasse 316460 AltdorfSwitzerlandPhone +41 (0) 41 874 75 75Fax +41 (0) 41 874 75 76E-mail power@ixosil.chPFISTERER S.A.Av. Velez Sarsfi eld 464C1282AFR Buenos AiresArgentinaPhone +54 (0) 11 4306 3595Fax +54 (0) 11 4362 2381E-mail pfi sterer@pfi sterer.com.arPFISTERER Ges.m.b.H.Augasse 171090 WienAustriaPhone +43 (0) 1 3176531 0Fax +43 (0) 1 3176531 12E-mail info@pfi sterer.atPFISTERER Ltda.Rua Frei Caneca, 30, sl. 01/ 0206706 015 Cotia, São PauloBrazilPhone +55 (0) 11 4612 9733Fax +55 (0) 11 4612 3856E-mail pfi sterer@pfi sterer.com.brPFISTERERRepresentative OfficeUnit 520, Landmark Tower 28 North Dongsanhuan RoadChaoyang District100004 BeijingChinaPhone +86 10 6590 6272Fax +86 10 6590 6105E-mail info.cn@pfi sterer.comPFISTERERRepresentative OfficeRoom 2606, 26/ F., Paul Y. Centre51 Hung To RoadKwun Tong, KowloonHong Kong, ChinaPhone +852 2687 2826Fax +852 2688 0663E-mail info.hk@pfi sterer.comwww.pfisterer.comPFISTERERRepresentative Office17. listopadu c.p. 342Zelene Predmesti530 02 PardubiceCzech RepublicPhone +420 (0) 466 657490Fax +420 (0) 466 613581E-mail dialog@pfi sterer.czPFISTERER Sàrl.35 avenue d’ItalieBP 1004568311 lllzach CedexFrancePhone +33 (0) 389 319029Fax +33 (0) 389 319028E-mail info@pfi sterer.frPFISTERERHandelsgesellschaft mbHRosenstraße 4473650 WinterbachGermanyPhone +49 (0) 7181 7005 301Fax +49 (0) 7181 7005 333E-mail dialog@pfi sterer.dePFISTERER Kereskedelmi Kft.Gyarmat u. 67/ C1147 BudapestHungaryPhone +36 (0) 1 2513441Fax +36 (0) 1 2511713E-mail offi ce@pfi sterer.huPFISTERER s.r.l.Via Sirtori 45 d20017 Passirana di Rho (MI)ItalyPhone +39 02 93158 11Fax +39 02 93158 27E-mail pfi sterer@pfi sterer.itPFISTERER Sp. z o.o.Ul. Poznanska 25805-850 Ozarów MazowieckiPolandPhone +48 (0) 22 72241 68Fax +48 (0) 22 72127 81E-mail info@pfi sterer.plPFISTERER ABFlygfältsgatan 212822 SkarpnäckSwedenPhone +46 (0) 8 7240 150Fax +46 (0) 8 6054 750E-mail info.se@pfi sterer.comPFISTERERRepresentative Office132 Tanjong Rhu Road03 – 12 Pebble BaySingapore 436919SingaporePhone +65 6346 4042Fax +65 6346 7110E-mail info@pfi sterer.sgPFISTERER (Pty.) Ltd.9 Willowton RoadPietermaritzburg 3201South AfricaPhone +27 (0) 33 397 5400Fax +27 (0) 33 387 6377E-mail info@pfi sterer.co.zaPFISTERER UPRESA S.A.U.Calle Industria 90-9208025 BarcelonaSpainPhone +34 (0) 93 4367409Fax +34 (0) 93 4367701pfi sterer.upresa@pfi stererupresa.euPFISTERER SEFAG AGWerkstrasse 76102 Malters, LuzernSwitzerlandPhone +41 (0) 41 4997 272Fax +41 (0) 41 4972 269E-mail connect@sefag.chPFISTERER INTERNATIONAL AGWerkstrasse 76102 Malters, LuzernSwitzerlandPhone +41 (0) 41 4997 474Fax +41 (0) 41 4973 473E-mail export@sefag.chPFISTERERRepresentative OfficePO Box 184090Gate 7, Floor 3Hamarain CenterDubaiUnited Arab EmiratesPhone +971 4 2690147Fax +971 4 2690148E-mail info@pfi sterer.aePFISTERER Ltd.29 Pillings RoadOakham LE15 6QFUnited KingdomPhone +44 (0) 15 7277 1300Fax +44 (0) 15 7277 1269E-mail info.uk@pfi sterer.com042 381 301/4,0 (EN) 2008 © 2008 PFISTERER Kontaktsysteme GmbH & Co. KG | www.pfisterer.com Concept and Design: VISCHER & BERNET Stuttgart We Can Assume no Liability <strong>for</strong> Printing Errors/Subject to Technical Modifi cation