Appendix B: <strong>Modbus</strong> Slave Module Factory Default <strong>Modbus</strong> Register MapAppendix B: <strong>Modbus</strong> Slave Module Factory DefaultNOTEIf your <strong>ION</strong> meter's <strong>for</strong>m factor does not support the parameter, it will be undefined. For example, lineto-neutralvalues from a Form 35S <strong>ION</strong> 8500 will be undefined.<strong>Modbus</strong> Slave Module #1Format: Unsigned 16 bitBase Address: 40011Scaling: YesIn Zero, In Full: 0, +6553Out Zero, Out Full: 0, +65530Input <strong>Modbus</strong> Register ParameterSource #1 40011 Vln aSource #2 40012 Vln bSource #3 40013 Vln cSource #4 40014 Vln avgSource #5 40015 Vll abSource #6 40016 Vll bcSource #7 40017 Vll caSource #8 40018 Vll avgSource #9 40019 I aSource #10 40020 I bSource #11 40021 I cSource #12 40022 I avgSource #13 40023 V unbalSource #14 40024 I unbalSource #15 40025 FreqSource #16 40026 I 4Page 26