InfeedSmart InfeedKey parameters for line and DC link identification (see List Manual) p3410 Infeed identification method p3421 Infeed inductance p3422 Infeed DC link capacity1.2.3 Smart Infeed open-loop controlDescriptionThe Smart Line Module can be controlled via the BICO interconnection by meansof terminals or the field bus. The operating status is indicated on the operating displayr0002. The missing enable signals for operation (r0002 = 00) are mapped inparameter r0046. The EP terminals (enable pulses) must be connected in accordancewith the Equipment Manual.Acknowledge errorErrors that are still present but the causes of which have been rectified can be acknowledgedby means of a 0 –> 1 edge at the “Acknowledge error” (p2103.5) signal.© Siemens AG 2006 All Rights Reserved<strong>SINAMICS</strong> <strong>S120</strong> <strong>Functi</strong>on Manual, 03/2006 Edition1-31