Transition Plan


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316 3-Signage: North 1st<strong>Life</strong> Floor Entry at <strong>Life</strong><strong>Science</strong> <strong>Science</strong> Building.BuildingUCR P5316 4-Tactile Exit Signage:<strong>Life</strong> North 1st Floor Entry at<strong>Science</strong> <strong>Life</strong> <strong>Science</strong> Building.BuildingUCR P5316 5-Floors and Levels: <strong>Life</strong><strong>Life</strong> <strong>Science</strong> Psychology<strong>Science</strong> North Entrance Door.BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building7-Electrical Controls &Receptacles/Fire AlarmBoxes: North to SouthCorridor on 1st Floor of<strong>Life</strong> <strong>Science</strong>.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Each grade-level exterior exit door shall beidentified by a tactile sign with the word "EXIT".Carpets or carpet tiles are securely attachedand do not exceed 1/2" in height. Carpet'sexposed edges are fastened to floor surfacesand have trim along entire length.The center of electrical outlets intended to beused by the room occupant are located a min. of15" above the floor or working platform. Theheight of the manual fire alarm box is a minimumof 42" and a maximum of 48", measuredvertically, from the floor level to the highest pointof the activating handle or lever of the box.Install permanent ID sign tolatch side of door.1 $183.75Provide compliant sign. 1 $183.75Secure loose doormat. 1 $245.01Relocate electrical receptacle.Relocate fire alarm initiatingdevice.1 $4,747.55UCR P5316 8-Visual/Audible Alarms:<strong>Life</strong> North to South Corridor<strong>Science</strong> on 1st Floor of <strong>Life</strong>Building <strong>Science</strong>.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building9-Hazards: North toSouth Corridor on 1stFloor of <strong>Life</strong> <strong>Science</strong>.[One clock.]10-Doors: WestEntrance to <strong>Life</strong><strong>Science</strong>s Psychology.[One set of doubledoors.]The appliance is placed 80" above the highestfloor level within the space or 6" below theceiling, whichever is lower.Any obstrution that overhangs a pedestrian wayis a minimum 80" above the walking surface(measured from the bottom of the obstruction).Sidewalks are clear of hazards. If verticalclearance of an area adjoining an accessibleroute is reduced to less than 80", a barrier towarn blind or visually impaired persons isprovided.5 lb. maximum pressure to operate exteriordoors. The international symbol of accessibilityis posted at all primary entrances.Review the entire alarmsystem.Install cane detectable barrierbelow clock.Provide a sign/decal displayingthe international symbol ofaccessibility.Adjust dooropening pressure / closing timeunless accepted by DSA Fire /<strong>Life</strong> Safety. Consider issuesconnected with buildingpressure / climate control.1 $7,115.621 $122.511 $330.766/1/2012 Page 1 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316 12-Signage: West<strong>Life</strong> Entrance to <strong>Life</strong><strong>Science</strong> <strong>Science</strong>s Psychology.BuildingUCR P5316 13-Floors and Levels: At<strong>Life</strong> West Entrance to <strong>Life</strong><strong>Science</strong> <strong>Science</strong>s Psychology.BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building14-Elevators: 1st Floorof <strong>Life</strong> <strong>Science</strong>sPsychology. [SeeSequence #16 foradditionalrecommendations.]15-Elevator Control(Panel & Hall Call): 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Carpets or carpet tiles are securely attachedand do not exceed 1/2" in height. Carpet'sexposed edges are fastened to floor surfacesand have trim along entire length.32" (+or- 1") height of the handrail from the floor.Minimum of 1-1/2" clearance of the handrailfrom the wall. Door jambs at all landings identifythe floor by both raised Arabic numerals(minimum of 2" in height) and Braille symbols(immediately to left of numerals).Control buttons are square shouldered, and area minimum of 3/4" and raised 1/8" plus of minus1/32" above the sorrounding surface. All buttonsare designated by a 5/8" minimum ArabicNumeral, alphabet or other standard sans serifuppercase character, or standard raised symbolimmediately to the left of the control button. Allraised characters are white on a blackbackground. Grade 2 Braille symbols arelocated immediately below the raisedcharacters. The centerline of hall call buttons inelevator lobbies are located at 42" above thefloor. Hall call buttons are a minimum of 3/4" insize and raised 1/8" plus or minus 1/32" abovethe sorrounding surface. Hall call buttonprovides visual indication that shows each callregistered and extinguishes when answered.Hall call buttons are internally illuminated with awhite light over the entire surface of the button.Install permanent ID sign tolatch side of door.1 $183.75Secure loose doormat. 1 $245.01Replace handrail on rear wallof elevator cab.1 $735.02Replace elevator control panel. 1 $33,075.706/1/2012 Page 2 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building16-Visual and AudibleSignals For Elevators:1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Elevator has visual and audible signalsindicating the position of the car on or betweenfloors. The indication is positioned above the carcontrol panel or over the door. The visual signalfor each direction is a minimum of 2-1/2" x 2-1/2", and visible from the proximity of the hallcall button. NOTE: An automatic verbalannouncement of the floor number at which acar stops or which a car passes may besubstituted for the audible signal. Audible signalsounds are once for up and twice for down. (orequivalent) Audible signal is no less than 10 dbsabove ambient and does not exceed 20 dbs witha frequency no higher than 1500 Hz.Install audible signals. Installnew jamb signage.1 $2,327.54UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building17-Water Fountains(Drinking): North toSouth Corridor at 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.18-Protruding Objects:North to South Corridorat 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.32" minimum wide and 18" minimum deepalcove provided. 27" high x 8" deep clear kneespace under fountain. Stream of bubbler isparallel to front edge. 4" minimum height ofstream.Objects projecting from walls (i.e. telephones,etc.) have 4" maximum projection into walks,halls, corridors, passageways or aisles if loweredge of object is above 27" and below 80".Install new single drinkingfountain. Install canedetectablebarrier aroundfountain.Install cane detectable barrierbelow two light fixtures.2 $6,640.81 Defer.1 $245.01UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building19-Protruding Objects:Near the SoutherExterior Door at 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.20-Doors: SouthwestEntrance to MiddleLanding of Stairs at <strong>Life</strong><strong>Science</strong> Psychology.[One set of doubledoors.]Objects projecting from walls (i.e. telephones,etc.) have 4" maximum projection into walks,halls, corridors, passageways or aisles if loweredge of object is above 27" and below 80".5 lb. maximum pressure to operate exteriordoors. Bottom 10" of door (except automatic orsliding doors) has a smooth uninterruptedsurface that allows door to be opened by awheelchair footrest without creating a trap orhazardous condition (kick plate).Install cane detectable barrierbelow lighting control box.Install kick-plate to bottom ofdoor. Adjust door openingpressure / closing time unlessaccepted by DSA Fire / <strong>Life</strong>Safety. Consider issuesconnected with buildingpressure / climate control.1 $245.012 $404.26UCR P5316<strong>Life</strong><strong>Science</strong>Building22-Signage: SouthwestEntrance to MiddleLanding of Stairs at <strong>Life</strong><strong>Science</strong> Psychology.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Install permanent ID sign tolatch side of door.1 $183.756/1/2012 Page 3 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building23-Tactile Exit Signage:North to South Corridoron 1st Floor of <strong>Life</strong><strong>Science</strong> Psychology.24-Floors and Levels:Southwest Entrance toMiddle Landing of Stairsat <strong>Life</strong> <strong>Science</strong>Psychology.25-Doors: Room #1447on 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Each exit door that leads directly to a gradelevelexterior exit by means of a stairway orramp is identified by a tactile exit sign that states"EXIT STAIR DOWN", "EXIT RAMP DOWN","EXIT STAIR UP", or "EXIT RAMP UP", asappropriate.Carpets or carpet tiles are securely attachedand do not exceed 1/2" in height. Carpet'sexposed edges are fastened to floor surfacesand have trim along entire length.32" minimum clear width of doorway. 5 lb.maximum pressure to operate interior doors.Door hardware is operable with a single effort(lever type, panic bar or push pull type). 3seconds minimum for door closer to close from70 degree position to within 3" of the latch[ADAAG 404.2.8.1 Door & gate closers requirea 5 second minimum closing time from openposition of 90 degree to 12 degree position].Provide compliant sign. 1 $183.75Secure loose doormat. 1 $245.01Adjust door opening pressure /closing time unless acceptedby DSA Fire / <strong>Life</strong> Safety.Consider issues connectedwith building pressure / climatecontrol. Replace doorhardware with complianthardware.1 $784.01UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building27-Signage: Room#1447 on 1st Floor of<strong>Life</strong> <strong>Science</strong>sPsychology.28-Doors: Southwest ofCorridor Leading toRooms #1450 B - L at<strong>Life</strong> <strong>Science</strong>Psychology.Permanent I.D. signs, when provided, areinstalled on the wall adjacent to the latch side ofthe door NOTE: At double leaf doors, and whenthere is no room on the latch side, signs shall beplaced on the nearest adjacent wall, preferablyon the right.5 lb. maximum pressure to operate interiordoors. Door hardware is operable with a singleeffort (lever type, panic bar or push pull type).Bottom 10" of door (except automatic or slidingdoors) has a smooth uninterrupted surface thatallows door to be opened by a wheelchairfootrest without creating a trap or hazardouscondition (kick plate).Install permanent ID sign tolatch side of door.Adjust door opening pressure /closing time unless acceptedby DSA Fire / <strong>Life</strong> Safety.Consider issues connectedwith building pressure / climatecontrol. Replace doorhardware with complianthardware. Remove door stop.1 $183.751 $845.27UCR P5316<strong>Life</strong><strong>Science</strong>Building29-Clear Space atDoors: Southwest ofCorridor Leading toRooms #1450 B - L at<strong>Life</strong> <strong>Science</strong>Psychology.Minimum strike side clearance on PUSH side ofdoor: 12" front approach with latch and closer.Remove door latch and/or doorcloser.2 $245.016/1/2012 Page 4 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316 30-Signage: Doors<strong>Life</strong> Leading to Rooms<strong>Science</strong> #1450 B - L at <strong>Life</strong>Building <strong>Science</strong> Psychology.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building31-Doors: Room #1427on 1st Floor at <strong>Life</strong><strong>Science</strong> Psychology.[Two single doors.]32-Clear Space atDoors: Room #1427 on1st Floor at <strong>Life</strong> <strong>Science</strong>Psychology. [Two singledoors.]33-Signage: Room#1427 on 1st Floor at<strong>Life</strong> <strong>Science</strong>Psychology.UCR P5316 35-Aisles: Room #1427<strong>Life</strong> on 1st Floor at <strong>Life</strong><strong>Science</strong> <strong>Science</strong> Psychology.BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building36-Sales and ServiceCounters: Room #1427on 1st Floor at <strong>Life</strong><strong>Science</strong> Psychology.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.5 lb. maximum pressure to operate interiordoors. Door hardware is operable with a singleeffort (lever type, panic bar or push pull type).Minimum strike side clearance on PUSH side ofdoor: 12" front approach with latch and closer.Permanent I.D. signs, when provided, areinstalled on the wall adjacent to the latch side ofthe door NOTE: At double leaf doors, and whenthere is no room on the latch side, signs shall beplaced on the nearest adjacent wall, preferablyon the right.Install permanent ID sign tolatch side of door.Replace door hardware withcompliant hardware. Adjustdoor opening pressure /closing time unless acceptedby DSA Fire / <strong>Life</strong> Safety.Consider issues connectedwith building pressure / climatecontrol.Remove door latch and/or doorcloser.Install permanent ID sign tolatch side of door.36" minimum width of aisles. Clear aisle width(s) to complywith minimum 36" width.A portion of the counter is a minimum of 36" inlength, at a height between 28" - 34" above thefloor and; A minimum 30" x 48" clear floor spaceis provided at the counter and; One fullunobstructed side of the clear floor spaceadjoins or overlaps an accessible route.1 $183.751 $1,261.772 $245.011 $367.512 $0.00Provide accessible counter. 2 $1,592.536/1/2012 Page 5 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building37-Sinks: Room #1427on 1st Floor at <strong>Life</strong><strong>Science</strong> Psychology.Minimum 30" x 48" clear space is provided infront of sink that allows forward approach.Required clear space adjoins or overlaps anaccessible route. 34" maximum height of rim orcounter above floor surfaces. Sink is amaximum of 6-1/2" deep. Knee clearance undersink is a minimum of 27" high and 30" wide, andprovides an absolute depth of 19" underneaththe sink [ADAAG 606.2 Exception 6 The dip ofthe overflow shall not be considered indetermining knee and toe clearance]. Drain andhot water piping is insulated or configured toprevent contact. Faucets are lever type,electronically activated or approved self-closingvalves (minimum 10 second open flow). Faucetsare operable with one hand and do not requiretight grasping, pinching or twisting of the wrist.Replace with accessible sink.Insulate pipes under sink. Cutthe paneling under the sinkcounter to comply with kneeclearance.3 $3,920.09UCR P5316<strong>Life</strong><strong>Science</strong>Building38-Seating, Tables andWork Surfaces: Room#1427 on 1st Floor at<strong>Life</strong> <strong>Science</strong>Psychology.30" x 48" min. clear floor space is provided. Onefull unobstructed side of clear floor spaceadjoins or overlaps an accessible route oranother wheelchair clear floor space. 27" high,30" wide and 19" deep knee clearance provided.Provide accessible tables. 1M $490.00 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.6/1/2012 Page 6 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building39-Hazards: Room#1427 on 1st Floor at<strong>Life</strong> <strong>Science</strong>Psychology.40-Doors: Room #1419Survey Research Centerat <strong>Life</strong> <strong>Science</strong>sPsychology.41-Clear Space atDoors: Room #1419Survey Research Centerat <strong>Life</strong> <strong>Science</strong>sPsychology.42-Signage: Room#1419 Survey ResearchCenter at <strong>Life</strong> <strong>Science</strong>sPsychology.Any obstrution that overhangs a pedestrian wayis a minimum 80" above the walking surface(measured from the bottom of the obstruction). Ifvertical clearance of an area adjoining anaccessible route is reduced to less than 80", abarrier to warn blind or visually impaired personsis provided.5 lb. maximum pressure to operate interiordoors. 3 seconds minimum for door closer toclose from 70 degree position to within 3" of thelatch [ADAAG 404.2.8.1 Door & gate closersrequire a 5 second minimum closing time fromopen position of 90 degree to 12 degreeposition].Minimum strike side clearance on PUSH side ofdoor: 12" front approach with latch and closer.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Raise ceiling suspended plugs. 1 $4,900.10Adjust door opening pressure /closing time unless accepted byDSA Fire / <strong>Life</strong> Safety. Considerissues connected with buildingpressure / climate control.Remove door latch and/or doorcloser.Install permanent ID sign tolatch side of door.2 $306.262 $245.011 $183.75UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building46-Doors: Room #1419Survey Research Centerat <strong>Life</strong> <strong>Science</strong>sPsychology. [Interioroffices (one withcloser).]48-Signage: Room#1419 Survey ResearchCenter at <strong>Life</strong> <strong>Science</strong>sPsychology. [Interioroffices.]5 lb. maximum pressure to operate interiordoors. Door hardware is operable with a singleeffort (lever type, panic bar or push pull type).Permanent I.D. signs, when provided, areinstalled on the wall adjacent to the latch side ofthe door NOTE: At double leaf doors, and whenthere is no room on the latch side, signs shall beplaced on the nearest adjacent wall, preferablyon the right.Replace door hardware withcompliant hardware. Adjustdoor opening pressure /closing time unless acceptedby DSA Fire / <strong>Life</strong> Safety.Consider issues connectedwith building pressure / climatecontrol.Install permanent ID sign tolatch side of door.1 $1,261.771 $367.516/1/2012 Page 7 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building50-Electrical Controls &Receptacles/Fire AlarmBoxes: East Corridor onthe 2nd Floor of <strong>Life</strong><strong>Science</strong>s. SeeSequence #8 for action.The height of the manual fire alarm box is aminimum of 42" and a maximum of 48",measured vertically, from the floor level to thehighest point of the activating handle or lever ofthe box.Relocate fire alarm initiatingdevice.1 $0.00UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building51-Visual/AudibleAlarms: North / SouthCorridor on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.See Sequence #8 foraction.52-Tactile Exit Signage:Near the South Stairwayon the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.53-Protruding Objects:South End of Corridor byStairs on the 2nd Floorof <strong>Life</strong> <strong>Science</strong>s. [Onelight sconce.]54-Doors: South Men'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.[See Sequence #55 foradditionalrecommendation.]55-Clear Space atDoors: South Men'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.The appliance is placed 80" above the highestfloor level within the space or 6" below theceiling, whichever is lower. There are no placesin common corridors or hallways that are morethan 50' from required signaling appliances.Each exit door that leads directly to a gradelevelexterior exit by means of a stairway orramp is identified by a tactile exit sign that states"EXIT STAIR DOWN", "EXIT RAMP DOWN","EXIT STAIR UP", or "EXIT RAMP UP", asappropriate.Objects projecting from walls (i.e. telephones,etc.) have 4" maximum projection into walks,halls, corridors, passageways or aisles if loweredge of object is above 27" and below 80".32" minimum clear width of doorway. 5 lb.maximum pressure to operate interior doors.Bottom 10" of door (except automatic or slidingdoors) has a smooth uninterrupted surface thatallows door to be opened by a wheelchairfootrest without creating a trap or hazardouscondition (kick plate).Requiresengineering/architecturalevaluation.1 $0.00Provide compliant sign. 1 $183.75Install cane detectable barrierbelow object.Replace door and frame(concrete or block wall). Installkick-plate to bottom of door.60" min. clear space in direction of door swing. Install automatic door openingdevice.1 $122.511 $5,365.611 $6,489.456/1/2012 Page 8 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building56-IdentificationSymbols, Restrooms:South Men's Restroomon the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.57-MultipleAccommodation Toilets:South Men's Restroomon the 2nd Floor of <strong>Life</strong><strong>Science</strong>s. [Provide anaccessible stall.]Door mounted signage: Men's - Equilateraltriangle with 12" sides, 1/4" thick with the vertexpointing up. The triangle symbol contrasts withthe door, light on dark background or dark onlight background. Wall mounted signage:Symbol of accessibility is mounted on wall signadjacent to latch side of door [ADAAG 703.6.1 &CBC 1117B.5.5 Item 4 Pictograms shall have afield height of 6" ADAAG 703.6.1 Charactersand Braille shall not be located in the pictogramfield].44" min. clear path provided throughout facility.Door latch is a flip-over style, sliding or otherhardware not requiring tight grasping or twisting.Door has loop or U-shaped handle immediatelybelow latch on both inside and outside of door.32" minimum opening at end. The clear floorarea on the pull side of the door within the stallis the width of the door and a minimum 60"deep. The clear floor area on the strike side ofthe door within the stall is a minimum 18" wideand a minimum 60" deep. The clear floor areaon the push side of the door is a minimum 48"deep., measured perpendicular to the door in itsclosed position, and 24" wide, measured fromthe strike edge of the door frame past the hingeside of the door. If the compartment has an endopening outward-swinging door (facing the watercloset), a minimum 60" wide x 48"deep clearfloor space is provided in front of the watercloset. 60" minimum width of stall [ADAAG604.8.1.4 toe clearances - The front partitionand at least one side partition shall provide a toeclearance of 9 inches minimum above the finishfloor and 6 inches deep minimum beyond thecompartment side face of the partition exclusiveof partition support members]. 18" betwencenterline of water closet and side wall orpartition [ADAAG 604.2 16" - 18" to centerline ofwater closet].. 32" minimum from side of watercloset to opposite wall or partition. 42" minimumfrom centerline of water closet to opposite wallor partition. The top of the toilet seat is 17" - 19"f th fl f d t th t fInstall door-mounted sign onsingle door. Install wallmountedsign at singleentrance.Requiresengineering/architecturalevaluation. Provide majorrenovation (including movingplumbing locations and walls).1 $367.511 $41,270.626/1/2012 Page 9 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316 58-Toilet Grab Bars:<strong>Life</strong> South Men's Restroom<strong>Science</strong> on the 2nd Floor of <strong>Life</strong>Building <strong>Science</strong>s.UCR P5316 59-Lavatories: South<strong>Life</strong> Men's Restroom on the<strong>Science</strong> 2nd Floor of <strong>Life</strong>Building <strong>Science</strong>s.UCR P5316<strong>Life</strong><strong>Science</strong>Building60-Urinals: South Men'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.UCR P5316 61-Alcoves: South Men's<strong>Life</strong> Restroom on the 2nd<strong>Science</strong> Floor of <strong>Life</strong> <strong>Science</strong>s.BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building62-Accessories: SouthMen's Restroom on the2nd Floor of <strong>Life</strong><strong>Science</strong>s.64-Doors: Women'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.1-1/4" to 1-1/2" diameter of bars. Side bar has42" min. length. Back bar has 36" min. length.34" max. height to rim or counter above floorsurface. Drain and piping is insulated orconfigured to prevent contact.A clear floor space that is a minimum 30" wideby 48" deep is provided in front of the urinal toallow forward approach. 17" maximum urinal rimheight above the finished floor. 44" maximumheight to flush valve above finished floor.36" x 48" clear floor space for front accessalcoves greater than 24" depth.40" maximum height to bottom of reflectivesurface of mirror. Mirrors not located abovelavatories or counters are required to measureno greater than 35" above the finished floor. 40"max. height to all other fixtures (i.e., soapdispensers, towels, toilet seat covers, autodryers, sanitary napkins, waste recepatacles,etc.).32" minimum clear width of doorway. 5 lb.maximum pressure to operate interior doors.Install grab bars. 1 $735.02Lower existing lavatory.Insulate pipes under lavatory.Replace urinal. Widenpartitions around urinal.1 $2,450.051 $3,430.07See Sequence #60 for actions. 1 $0.00Install new accessible mirror.Relocate the paper toweldispenser. Relocate the soapdispenser. Remove existingshelf/mirror.Adjust door opening pressure /closing time unless acceptedby DSA Fire / <strong>Life</strong> Safety.Consider issues connectedwith building pressure / climatecontrol. Replace door andframe (concrete or block wall).1 $980.021 $5,573.87UCR P5316<strong>Life</strong><strong>Science</strong>Building65-Clear Space atDoors: Women'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.Minimum strike side clearance on PULL side of Reverse door swing pending Firedoor: 18" wide x 60" depth at interior doors, front Marshall determination.approach.1 $1,923.316/1/2012 Page 10 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building66-IdentificationSymbols, Restrooms:Women's Restroom onthe 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Women's - 12" diameter circle 1/4" thick. Thecircle symbol contrasts with the door, light ondark background or dark on light background.Wall mounted signage: Symbol of accessibility ismounted on wall sign adjacent to latch side ofdoor [ADAAG 703.6.1 & CBC 1117B.5.5 Item 4Pictograms shall have a field height of 6"ADAAG 703.6.1 Characters and Braille shall notbe located in the pictogram field].Install door-mounted sign onsingle door. Install wallmountedsign at singleentrance.1 $367.51UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building67-Doors: Women'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.68-Clear Space atDoors: Women'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.[See Sequence #67 forrecommendations.]32" minimum clear width of doorway. 5 lb.maximum pressure to operate interior doors.Bottom 10" of door (except automatic or slidingdoors) has a smooth uninterrupted surface thatallows door to be opened by a wheelchairfootrest without creating a trap or hazardouscondition (kick plate).44" min. clear space opposite direction of doorswing (48" with latch and closer). Minimumstrike side clearance on PULL side of door: 18"wide x 60" depth at interior doors, frontapproach.Remove door and frame.Widen existing doorway.1 $3,185.07Remove existing shelf/mirror. 1 $245.006/1/2012 Page 11 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building70-MultipleAccommodation Toilets:Women's Restroom onthe 2nd Floor of <strong>Life</strong><strong>Science</strong>s. [Noaccessible stall. Providean accessible stall.]UCR P5316 71-Toilet Grab Bars:<strong>Life</strong> Women's Restroom on<strong>Science</strong> the 2nd Floor of <strong>Life</strong>Building <strong>Science</strong>s.UCR P5316<strong>Life</strong><strong>Science</strong>Building72-Lavatories: Women'sRestroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.44" min. clear path provided throughout facility.Door has loop or U-shaped handle immediatelybelow latch on both inside and outside of door.32" minimum opening at end. The clear floorarea on the pull side of the door within the stallis the width of the door and a minimum 60"deep. The clear floor area on the strike side ofthe door within the stall is a minimum 18" wideand a minimum 60" deep. The clear floor areaon the push side of the door is a minimum 48"deep., measured perpendicular to the door in itsclosed position, and 24" wide, measured fromthe strike edge of the door frame past the hingeside of the door. If the compartment has an endopening outward-swinging door (facing the watercloset), a minimum 60" wide x 48"deep clearfloor space is provided in front of the watercloset. 60" minimum width of stall [ADAAG604.8.1.4 toe clearances - The front partitionand at least one side partition shall provide a toeclearance of 9 inches minimum above the finishfloor and 6 inches deep minimum beyond thecompartment side face of the partition exclusiveof partition support members]. 18" betwencenterline of water closet and side wall orpartition [ADAAG 604.2 16" - 18" to centerline ofwater closet].. 32" minimum from side of watercloset to opposite wall or partition. 42" minimumfrom centerline of water closet to opposite wallor partition. The top of the toilet seat is 17" - 19"from the floor surface as measured to the top ofa maximum 2" high toilet seat (a 3" high seat1-1/4" h ll b to 1-1/2" itt diameter d l i of ltbars. ti Side h bar has th42" min. length. Back bar has 36" min. length.Required clear space extends 19" max.underneath the lavatory and adjoins or over lapsan accessible route. 29" min. clearance frombottom of apron to floor surface. 27" high x 8"deep knee clearance under front lip. Drain andpiping is insulated or configured to preventcontact.Requiresengineering/architecturalevaluation. Provide majorrenovation (including movingplumbing locations and walls).1 $41,270.62Install new grab bars. 1 $735.02Replace with accessiblelavatory. Insulate pipes underlavatory.1 $3,430.076/1/2012 Page 12 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building73-Accessories:Women's Restroom onthe 2nd Floor of <strong>Life</strong><strong>Science</strong>s.75-Water Fountains(Drinking): At 2nd Floorof <strong>Life</strong> <strong>Science</strong>sPsychology Corridor.77-Protruding Objects:2nd Floor <strong>Life</strong> <strong>Science</strong>sNext to the Elevator.[One emergency phone.]40" maximum height to bottom of reflectivesurface of mirror. Mirrors not located abovelavatories or counters are required to measureno greater than 35" above the finished floor. 40"max. height to all other fixtures (i.e., soapdispensers, towels, toilet seat covers, autodryers, sanitary napkins, waste recepatacles,etc.).32" minimum wide and 18" minimum deepalcove provided. 27" high x 8" deep clear kneespace under fountain. Stream of bubbler isparallel to front edge. 4" minimum height ofstream. Two fountains are provided, one that iswheelchair accessible and one at normal heightfor those persons having difficulty bending orstooping.Objects projecting from walls (i.e. telephones,etc.) have 4" maximum projection into walks,halls, corridors, passageways or aisles if loweredge of object is above 27" and below 80".Lower mirror. Lower the papertowel dispenser.Install new single drinkingfountain. Install canedetectablebarrier aroundfountain. Install paper cupdispenser at existing fountain.Install cane detectable barrierbelow object.1 $245.012 $6,824.57 Defer.1 $122.51UCR P5316<strong>Life</strong><strong>Science</strong>Building78-Doors: SoutheastEntrance on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>.5 lb. maximum pressure to operate exteriordoors. 3 seconds minimum for door closer toclose from 70 degree position to within 3" of thelatch [ADAAG 404.2.8.1 Door & gate closersrequire a 5 second minimum closing time fromopen position of 90 degree to 12 degreeposition]. The international symbol ofaccessibility is posted at all primary entrances.Provide a sign/decal displayingthe international symbol ofaccessibility. Adjust dooropening pressure / closing timeunless accepted by DSA Fire /<strong>Life</strong> Safety. Consider issuesconnected with buildingpressure / climate control.1 $330.76UCR P5316 80-Signage: Southeast<strong>Life</strong> Entrance on the 2nd<strong>Science</strong> Floor of <strong>Life</strong> <strong>Science</strong>.BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building81-Hazards: Clock at theEast Corridor of <strong>Life</strong><strong>Science</strong>s.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Any obstrution that overhangs a pedestrian wayis a minimum 80" above the walking surface(measured from the bottom of the obstruction). Ifvertical clearance of an area adjoining anaccessible route is reduced to less than 80", abarrier to warn blind or visually impaired personsis provided.Install permanent ID sign tolatch side of door.Install cane detectable barrierbelow clock.1 $183.751 $122.516/1/2012 Page 13 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building83-Hazards: WestCorridor Running Northto South on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.84-Doors: Rooms#2400, #2405, #2410,#2415, #2420, #2425and #2430 at <strong>Life</strong><strong>Science</strong>s Psychology.85-Clear Space atDoors: Rooms #2400,#2405, #2410, #2415,#2420, #2425 and#2430 at <strong>Life</strong> <strong>Science</strong>sPsychology.86-Signage: Rooms#2400, #2405, #2410,#2415, #2420, #2425and #2430 at <strong>Life</strong><strong>Science</strong>s Psychology.87-Doors: Room #2418on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.88-Clear Space atDoors: Room #2418 onthe 2nd Floor of <strong>Life</strong><strong>Science</strong>s.89-Signage: Room#2418 on the 2nd Floorof <strong>Life</strong> <strong>Science</strong>sPsychology.Any obstrution that overhangs a pedestrian wayis a minimum 80" above the walking surface(measured from the bottom of the obstruction). Ifvertical clearance of an area adjoining anaccessible route is reduced to less than 80", abarrier to warn blind or visually impaired personsis provided.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Install cane detectable barrierbelow clock.Replace door hardware withcompliant hardware.Minimum strike side clearance on PULL side of Relocate furniture to providedoor: 18" wide x 60" depth at interior doors, front clear space. University staff shallapproach.be instructed to place andmaintain the placement offurniture to provide a clear pathof travel and avoid theobstruction of accessiblerequired clear spaces.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.5 lb. maximum pressure to operate interiordoors.44" min. clear space opposite direction of doorswing (48" with latch and closer).Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Install permanent ID sign tolatch side of door.Adjust door opening pressure /closing time unless accepted byDSA Fire / <strong>Life</strong> Safety. Considerissues connected with buildingpressure / climate control.Relocate furniture to provideclear space. University staff shallbe instructed to place andmaintain the placement offurniture to provide a clear pathof travel and avoid theobstruction of accessiblerequired clear spaces.Install permanent ID sign tolatch side of door.1 $122.511 $3,344.301M $61.251 $1,286.272 $306.261M $61.251 $183.756/1/2012 Page 14 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building90-Seating, Tables andWork Surfaces: Room#2418 on the 2nd Floorof <strong>Life</strong> <strong>Science</strong>sPsychology. [22 totalseats.]30" x 48" min. clear floor space is provided. 27"high, 30" wide and 19" deep knee clearanceprovided.Provide accessible table. 1M $490.00 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building91-Aisles: Room #2418on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[Relocate the fixedtables to provide clearspace.]93-Controls, OperatingMechanisms & VendingMachines.: Room #2418on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[One phone. Relocatethe telephone. Relocatethe fixed table to provideclear space.]36" minimum width of aisles. Relocate furniture to provideclear space. University staff shallbe instructed to place andmaintain the placement offurniture to provide a clear pathof travel and avoid theobstruction of accessiblerequired clear spaces.Side Reach to Objects: Minimum 30" x 48" clearfloor space for side approach is provided at theobject. Side Reach to Objects: Clear floor spacebegins a maximum of 10" from the wall/surfacethe object is mounted on. Side Reach OverObstructions: The maximum height of theobstruction is 34" from the floor surface.Install accessible counter.Relocate furniture to provideclear space. University staffshall be instructed to place andmaintain the placement offurniture to provide a clear pathof travel and avoid theobstruction of accessiblerequired clear spaces.1M $245.012 $1,286.276/1/2012 Page 15 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building94-Sinks: Room #2418on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Minimum 30" x 48" clear space is provided infront of sink that allows forward approach. 34"maximum height of rim or counter above floorsurfaces. Knee clearance under sink is aminimum of 27" high and 30" wide, and providesan absolute depth of 19" underneath the sink[ADAAG 606.2 Exception 6 The dip of theoverflow shall not be considered in determiningknee and toe clearance]. Faucets are lever type,electronically activated or approved self-closingvalves (minimum 10 second open flow). Faucetsare operable with one hand and do not requiretight grasping, pinching or twisting of the wrist. 5lb. maximum force required to activate controls.Replace with accessible sink.Cut the paneling under the sinkcounter to comply with kneeclearance. Insulate pipesunder sink.4 $3,920.09UCR P5316 95-Doors: Room #2445<strong>Life</strong> on the 2nd Floor of <strong>Life</strong><strong>Science</strong> <strong>Science</strong>s Psychology.BuildingUCR P5316 96-Clear Space at<strong>Life</strong> Doors: Room #2445 on<strong>Science</strong> the 2nd Floor of <strong>Life</strong>Building <strong>Science</strong>s Psychology.UCR P5316 97-Signage: Room<strong>Life</strong> #2445 on the 2nd Floor<strong>Science</strong> of <strong>Life</strong> <strong>Science</strong>sBuilding Psychology.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building98-Doors: Rooms#2505, #2510, #2515,#2520, #2525, #2530and #2535 at <strong>Life</strong><strong>Science</strong>s Psychology.100-Signage: Rooms#2505, #2510, #2515,#2520, #2525, #2530and #2535 at <strong>Life</strong><strong>Science</strong>s Psychology.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Replace door hardware withcompliant hardware.Minimum strike side clearance on PULL side of Reverse door swing pending Firedoor: 18" wide x 60" depth at interior doors, front Marshall determination.approach.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Install permanent ID sign tolatch side of door.Replace door hardware withcompliant hardware.Install permanent ID sign tolatch side of door.1 $477.762 $1,923.311 $183.751 $3,344.301 $1,286.276/1/2012 Page 16 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building101-Doors: Rooms#2600, #2605, #2610,#2615, #2620, #2625,#2630, #2635 and#2640 on the 2nd Floorat <strong>Life</strong> <strong>Science</strong>sPsychology.103-Signage: Rooms#2600, #2605, #2610,#2615, #2620, #2625,#2630, #2635 and#2640 on the 2nd Floorat <strong>Life</strong> <strong>Science</strong>sPsychology.104-Doors: BNNAdministrative Officeson the 2nd Floor at <strong>Life</strong><strong>Science</strong>s. [Two sets ofdouble doors swinging inboth directions.]106-Signage: BNNAdministrative Officeson the 2nd Floor at <strong>Life</strong><strong>Science</strong>s. [Two sets ofdouble doors.]107-Tactile ExitSignage: BNNAdministrative Officeson the 2nd Floor at <strong>Life</strong><strong>Science</strong>s. [Two sets ofdouble doors.]108-Protruding Objects:Time Sheet Box West ofRoom #2705 on the 2ndFloor at <strong>Life</strong> <strong>Science</strong>s.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.5 lb. maximum pressure to operate interiordoors. 3 seconds minimum for door closer toclose from 70 degree position to within 3" of thelatch [ADAAG 404.2.8.1 Door & gate closersrequire a 5 second minimum closing time fromopen position of 90 degree to 12 degreeposition].Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Each grade-level exterior exit door shall beidentified by a tactile sign with the word "EXIT".Objects projecting from walls (i.e. telephones,etc.) have 4" maximum projection into walks,halls, corridors, passageways or aisles if loweredge of object is above 27" and below 80".Replace door hardware withcompliant hardware.Install permanent ID sign tolatch side of door.Adjust door opening pressure /closing time unless accepted byDSA Fire / <strong>Life</strong> Safety. Considerissues connected with buildingpressure / climate control.Install permanent ID sign tolatch side of door.1 $4,299.821 $1,653.792 $612.511 $367.51Provide compliant sign. 1 $367.51Install cane detectable barrierbelow object.1 $245.01UCR P5316<strong>Life</strong><strong>Science</strong>Building109-Doors: Room #2705at the West Wing on the2nd Floor of <strong>Life</strong><strong>Science</strong>s.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Replace door hardware withcompliant hardware.1 $477.766/1/2012 Page 17 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316 111-Signage: Room<strong>Life</strong> #2705 at the West Wing<strong>Science</strong> on the 2nd Floor of <strong>Life</strong>Building <strong>Science</strong>s.UCR P5316<strong>Life</strong><strong>Science</strong>Building115-Water Fountains(Drinking): West Wingon the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.32" minimum wide and 18" minimum deepalcove provided. 18" - 19" depth of fountain. 27"high x 8" deep clear knee space under fountain.Bubbler outlet is 36" maximum from floor.Stream of bubbler is parallel to front edge.Install permanent ID sign tolatch side of door.Install new single drinkingfountain. Install canedetectablebarrier aroundfountain.1 $183.752 $6,640.81 Defer.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building116-Doors: Rooms#2710, #2715, #2720,#2725, #2730, #2735,#2740, #2745, #2805and #2840 on the 2ndFloor West Wing of <strong>Life</strong><strong>Science</strong>s.118-Signage: Rooms#2710, #2715, #2720,#2725, #2730, #2735,#2740, #2745, #2805and #2840 on the 2ndFloor West Wing of <strong>Life</strong><strong>Science</strong>s.119-Tactile ExitSignage: Stairs at theWest Wing on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.120-Doors: West WingEntrance to <strong>Life</strong><strong>Science</strong>s Psychology onthe 1st Floor. [One set ofdouble doors.]Door hardware is operable with a single effort(lever type, panic bar or push pull type).Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Each exit door that leads directly to a gradelevelexterior exit by means of a stairway orramp is identified by a tactile exit sign that states"EXIT STAIR DOWN", "EXIT RAMP DOWN","EXIT STAIR UP", or "EXIT RAMP UP", asappropriate.1/4" maximum vertical threshold or 1/2" beveledat 1:2. 5 lb. maximum pressure to operateexterior doors. 3 seconds minimum for doorcloser to close from 70 degree position to within3" of the latch [ADAAG 404.2.8.1 Door & gateclosers require a 5 second minimum closingtime from open position of 90 degree to 12degree position]. The international symbol ofaccessibility is posted at all primary entrances.Replace door hardware withcompliant hardware.Install permanent ID sign tolatch side of door.1 $4,777.571 $1,837.54Provide compliant sign. 1 $183.75Replace or modify thethreshold. Adjust door openingpressure / closing time unlessaccepted by DSA Fire / <strong>Life</strong>Safety. Consider issuesconnected with buildingpressure / climate control. Posta sign/decal displaying the"International Symbol ofAccessibility" at the primaryentrance.1 $575.776/1/2012 Page 18 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building121-Clear Space atDoors: West WingEntrance to <strong>Life</strong><strong>Science</strong>s Psychology onthe 1st Floor.UCR P5316 122-Signage: West<strong>Life</strong> Wing Entrance to <strong>Life</strong><strong>Science</strong> <strong>Science</strong>s Psychology onBuilding the 1st Floor.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building123-Tactile ExitSignage: West WingEntrance to <strong>Life</strong><strong>Science</strong>s Psychology onthe 1st Floor.124-Floors and Levels:West Wing Entrance to<strong>Life</strong> <strong>Science</strong>sPsychology on the 1stFloor.128-Controls, OperatingMechanisms & VendingMachines.: West WingCorridor at <strong>Life</strong> <strong>Science</strong>sPsychology on the 1stFloor. [One telephone.Lower the telephone.]Floor or landing is level and clear (2% max.slope).Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Each grade-level exterior exit door shall beidentified by a tactile sign with the word "EXIT".Carpets or carpet tiles are securely attachedand do not exceed 1/2" in height. Carpet'sexposed edges are fastened to floor surfacesand have trim along entire length.Forward Reach to Objects: Highest operablepart of object is a maximum of 48" above thefloor surface.Install level exterior doorlanding.Install permanent ID sign tolatch side of door.2 $1,225.311 $183.75Provide compliant sign. 1 $183.75Secure loose doormat. 1 $245.01Lower the house phone. 3 $213.46UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building130-Controls, OperatingMechanisms & VendingMachines.: West Wingat <strong>Life</strong> <strong>Science</strong>sPsychology on the 1stFloor.131-Water Fountains(Drinking): West Wing at<strong>Life</strong> <strong>Science</strong>sPsychology on the 1stFloor.Forward Reach to Objects: Highest operablepart of object is a maximum of 48" above thefloor surface.32" minimum wide and 18" minimum deepalcove provided. 18" - 19" depth of fountain. 27"high x 8" deep clear knee space under fountain.9" high x 17" deep toe clearance. Bubbler outletis 36" maximum from floor.Lower the lever to theemergency eye wash.Install new single drinkingfountain. Install canedetectablebarrier aroundfountain.3 $250.002 $6,640.81 Defer.6/1/2012 Page 19 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building132-Doors: West WingExit Door to Stairwell onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.134-Signage: WestWing Exit Door toStairwell on the 1st Floorof <strong>Life</strong> <strong>Science</strong>sPsychology.135-Tactile ExitSignage: West WingExit Doors to Stairwellon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.136-Doors: Women'sRestroom #1517 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [SeeSequence #137 foradditional action.]137-Clear Space atDoors: Women'sRestroom #1517 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.138-IdentificationSymbols, Restrooms:Women's Restroom#1517 at the West Wingon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.5 lb. maximum pressure to operate interiordoors. 3 seconds minimum for door closer toclose from 70 degree position to within 3" of thelatch [ADAAG 404.2.8.1 Door & gate closersrequire a 5 second minimum closing time fromopen position of 90 degree to 12 degreeposition].Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Each exit door that leads directly to a gradelevelexterior exit by means of a stairway orramp is identified by a tactile exit sign that states"EXIT STAIR DOWN", "EXIT RAMP DOWN","EXIT STAIR UP", or "EXIT RAMP UP", asappropriate.32" minimum clear width of doorway. 5 lb.maximum pressure to operate interior doors.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Adjust door opening pressure /closing time unless accepted byDSA Fire / <strong>Life</strong> Safety. Considerissues connected with buildingpressure / climate control.Install permanent ID sign tolatch side of door.2 $306.261 $183.75Provide compliant sign. 1 $183.75Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Minimum strike side clearance on PULL side of Install a sign at the restroom doordoor: 18" wide x 60" depth at interior doors, front indicating the availability andapproach.location of an alternateaccessible restroom.Women's - 12" diameter circle 1/4" thick. The Install a sign at the restroom doorcircle symbol contrasts with the door, light on indicating the availability anddark background or dark on light background. location of an alternateWall mounted signage: Symbol of accessibility is accessible restroom.mounted on wall sign adjacent to latch side ofdoor [ADAAG 703.6.1 & CBC 1117B.5.5 Item 4Pictograms shall have a field height of 6"ADAAG 703.6.1 Characters and Braille shall notbe located in the pictogram field].1 $183.751 $0.003 $0.006/1/2012 Page 20 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building139-MultipleAccommodation Toilets:Women's Restroom#1517 at the West Wingon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[No accessible stall.Provide an accessiblestall.]140-Toilet Grab Bars:Women's Restroom#1517 at the West Wingon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.60" min. diameter turning circle clear of objectsfrom floor height to 27" in room. 44" min. clearpath provided throughout facility. The accessiblestall door shall have an automatic closingdevice. Door has loop or U-shaped handleimmediately below latch on both inside andoutside of door. 34" minimum opening at side.The clear floor area on the pull side of the doorwithin the stall is the width of the door and aminimum 60" deep. The clear floor area on thestrike side of the door within the stall is aminimum 18" wide and a minimum 60" deep.The clear floor area on the push side of the dooris the width of the door and a minimum 48"deep., measured perpendicular to the door in itsclosed position. If the compartment has aninward swinging, side opening door and containsa floor mounted water closet, the clearancearound the water closet is a minimum of 60"wide and and a minimum 59" deep that is clearof the stall door swing. 60" minimum width ofstall [ADAAG 604.8.1.4 toe clearances - Thefront partition and at least one side partition shallprovide a toe clearance of 9 inches minimumabove the finish floor and 6 inches deepminimum beyond the compartment side face ofthe partition exclusive of partition supportmembers]. 18" betwen centerline of water closetand side wall or partition [ADAAG 604.2 16" -18" to centerline of water closet].. 32" minimumfrom side of water closet to opposite wall orpartition. 42" minimum from centerline of waterl t t it ll titi Th t f th1-1/4" to 1-1/2" diameter of bars. Side bar has42" min. length. Back bar has 36" min. length.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.1 $0.001 $0.006/1/2012 Page 21 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building141-Lavatories:Women's Restroom#1517 at the West Wingon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.142-Accessories:Women's Restroom#1517 at the West Wingon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[See Sequence #139 foradditionalrecommendations.]144-Doors: Men'sRestroom #1522 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.145-Clear Space atDoors: Men's Restroom#1522 at the West Wingon the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[See Sequence #147 foradditional actions.]146-IdentificationSymbols, Restrooms:Men's Restroom #1522at the West Wing on the1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Required clear space extends 19" max. Install a sign at the restroom doorunderneath the lavatory and adjoins or over laps indicating the availability andan accessible route. 29" min. clearance from location of an alternatebottom of apron to floor surface. 27" high x 8" accessible restroom.deep knee clearance under front lip. Drain andpiping is insulated or configured to preventcontact.40" maximum height to bottom of reflectivesurface of mirror. Mirrors not located abovelavatories or counters are required to measureno greater than 35" above the finished floor. 40"max. height to all other fixtures (i.e., soapdispensers, towels, toilet seat covers, autodryers, sanitary napkins, waste recepatacles,etc.). A minimum 30" x 48" minimum clear flooror ground space is provided to allow forward orparallel approach to accessories.32" minimum clear width of doorway. 5 lb.maximum pressure to operate interior doors.Door hardware is operable with a single effort(lever type, panic bar or push pull type).60" min. clear space in direction of door swing.Minimum strike side clearance on PULL side ofdoor: 18" wide x 60" depth at interior doors, frontapproach.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Door mounted signage: Men's - Equilateral Install a sign at the restroom doortriangle with 12" sides, 1/4" thick with the vertex indicating the availability andpointing up. The triangle symbol contrasts with location of an alternatethe door, light on dark background or dark on accessible restroom.light background. Wall mounted signage:Symbol of accessibility is mounted on wall signadjacent to latch side of door [ADAAG 703.6.1 &CBC 1117B.5.5 Item 4 Pictograms shall have afield height of 6" ADAAG 703.6.1 Charactersand Braille shall not be located in the pictogramfield].1 $0.001 $0.001 $183.751 $0.001 $0.006/1/2012 Page 22 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building147-MultipleAccommodation Toilets:Men's Restroom #1522at the West Wing on the1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[Provide a compliantrestroom.]148-Toilet Grab Bars:Men's Restroom #1522at the West Wing on the1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.149-Lavatories: Men'sRestroom #1522 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [SeeSequence #147 foradditionalrecommendations.]60" min. diameter turning circle clear of objects Install a sign at the restroom doorfrom floor height to 27" in room. 44" min. clear indicating the availability andpath provided throughout facility. The accessible location of an alternatestall door shall have an automatic closing accessible restroom.device. Door has loop or U-shaped handleimmediately below latch on both inside andoutside of door. 34" minimum opening at side.60" minimum width of stall [ADAAG 604.8.1.4toe clearances - The front partition and at leastone side partition shall provide a toe clearanceof 9 inches minimum above the finish floor and 6inches deep minimum beyond the compartmentside face of the partition exclusive of partitionsupport members]. 18" betwen centerline ofwater closet and side wall or partition [ADAAG604.2 16" - 18" to centerline of water closet]..32" minimum from side of water closet toopposite wall or partition. 42" minimum fromcenterline of water closet to opposite wall orpartition. The top of the toilet seat is 17" - 19"from the floor surface as measured to the top ofa maximum 2" high toilet seat (a 3" high seatshall be permitted only in alterations where theexisting fixture is less than 15" high). The toiletpaper dispenser is located on the side wallbelow the grab bar and within 7" - 9" of the frontof the toilet seat as measured to the centerlineof the dispenser.1-1/4" to 1-1/2" diameter of bars. Side bar has42" min. length. Back bar has 36" min. length.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Required clear space extends 19" max. Install a sign at the restroom doorunderneath the lavatory and adjoins or over laps indicating the availability andan accessible route. 18" minimum from center of location of an alternatefixture to side wall or partition. 29" min. accessible restroom.clearance from bottom of apron to floor surface.27" high x 8" deep knee clearance under frontlip. Drain and piping is insulated or configured toprevent contact.1 $0.001 $0.001 $0.006/1/2012 Page 23 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building150-Urinals: Men'sRestroom #1522 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.151-Alcoves: Men'sRestroom #1522 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.152-Accessories: Men'sRestroom #1522 at theWest Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.A clear floor space that is a minimum 30" wide Install a sign at the restroom doorby 48" deep is provided in front of the urinal to indicating the availability andallow forward approach. 17" maximum urinal rim location of an alternateheight above the finished floor. 14" minimum accessible restroom.projection and 17" maximum projection from thewall.36" x 48" clear floor space for front accessalcoves greater than 24" depth. One fullunobstructed side of clear floor space adjoinsaccessible route.40" maximum height to bottom of reflectivesurface of mirror. Mirrors not located abovelavatories or counters are required to measureno greater than 35" above the finished floor. 40"max. height to all other fixtures (i.e., soapdispensers, towels, toilet seat covers, autodryers, sanitary napkins, waste recepatacles,etc.). A minimum 30" x 48" minimum clear flooror ground space is provided to allow forward orparallel approach to accessories.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.Install a sign at the restroom doorindicating the availability andlocation of an alternateaccessible restroom.1 $0.001 $0.001 $0.00UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building154-Doors: West WingRoom #1521 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [SeeSequence #155 foradditional action.]155-Clear Space atDoors: West WingRoom #1521 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [SeeSequence #157 foradditional actions.]156-Signage: WestWing Room #1521 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.5 lb. maximum pressure to operate interiordoors. Door hardware is operable with a singleeffort (lever type, panic bar or push pull type).44" min. clear space opposite direction of doorswing (48" with latch and closer). Minimumstrike side clearance on PULL side of door: 18"wide x 60" depth at interior doors, frontapproach.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.Replace door hardware withcompliant hardware.Install automatic door openingdevice.Install permanent ID sign tolatch side of door.1 $477.761 $6,489.451 $183.756/1/2012 Page 24 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building157-Seating, Tables andWork Surfaces: WestWing Room #1521 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.30" x 48" min. clear floor space is provided. 28" -34" height of table or work surface that is 36"wide.Install accessible counter.Move built-in counter toprovide adequate clear space.3 $3,062.56UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building158-Sales and ServiceCounters: West WingRoom #1521 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.159-Sinks: West WingRoom #1521 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.A portion of the counter is a minimum of 36" inlength, at a height between 28" - 34" above thefloor and;Minimum 30" x 48" clear space is provided infront of sink that allows forward approach. 34"maximum height of rim or counter above floorsurfaces. Sink is a maximum of 6-1/2" deep.Knee clearance under sink is a minimum of 27"high and 30" wide, and provides an absolutedepth of 19" underneath the sink [ADAAG 606.2Exception 6 The dip of the overflow shall not beconsidered in determining knee and toeclearance]. Drain and hot water piping isinsulated or configured to prevent contact.Faucets are operable with one hand and do notrequire tight grasping, pinching or twisting of thewrist.Install accessible counter. 3 $1,225.03Replace with accessible sink.Cut the paneling under the sinkcounter to comply with kneeclearance. Insulate pipesunder sink.3 $3,920.09UCR P5316<strong>Life</strong><strong>Science</strong>Building160-Aisles: West WingRoom #1521 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.36" minimum width of aisles. Clear aisle width(s) to complywith minimum required aislewidth(s) listed above.2 $0.006/1/2012 Page 25 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building161-Seating, Tables andWork Surfaces: WestWing Room #1521 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[One fume hood.Highest control is at 63"high.]27" high, 30" wide and 19" deep knee clearanceprovided. 28" - 34" height of table or worksurface that is 36" wide.Replace the fume hood with anaccessible fume hoodworkstation.3 $18,216.00 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building163-Doors: West WingRoom #1523 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [No closeron door.]165-Signage: WestWing Room #1523 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.166-Sales and ServiceCounters: West WingRoom #1523 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.Door hardware is operable with a single effort(lever type, panic bar or push pull type).Permanent I.D. signs, when provided, areinstalled on the wall adjacent to the latch side ofthe door NOTE: At double leaf doors, and whenthere is no room on the latch side, signs shall beplaced on the nearest adjacent wall, preferablyon the right.A portion of the counter is a minimum of 36" inlength, at a height between 28" - 34" above thefloor and; Access to accessible seating spacesis provided by main aisles a minimum 36" inwidth.Replace door hardware withcompliant hardware.Install permanent ID sign tolatch side of door.1 $477.761 $183.75Provide accessible counters. 2 $2,450.066/1/2012 Page 26 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building167-Sinks: West WingRoom #1523 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.Minimum 30" x 48" clear space is provided infront of sink that allows forward approach. 34"maximum height of rim or counter above floorsurfaces. Sink is a maximum of 6-1/2" deep.Knee clearance under sink is a minimum of 27"high and 30" wide, and provides an absolutedepth of 19" underneath the sink [ADAAG 606.2Exception 6 The dip of the overflow shall not beconsidered in determining knee and toeclearance]. Drain and hot water piping isinsulated or configured to prevent contact.Faucets are lever type, electronically activatedor approved self-closing valves (minimum 10second open flow). Faucets are operable withone hand and do not require tight grasping,pinching or twisting of the wrist.Replace with accessible sink.Cut the paneling under the sinkcounter to comply with kneeclearance. Insulate pipesunder sink.3 $3,920.09UCR P5316<strong>Life</strong><strong>Science</strong>Building168-Seating, Tables andWork Surfaces: WestWing Room #1523 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[Work table.]30" x 48" min. clear floor space is provided. 27"high, 30" wide and 19" deep knee clearanceprovided.Provide accessible table. 1M $245.01 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.6/1/2012 Page 27 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building170-Doors: West WingRoom #1529 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.171-Clear Space atDoors: West WingRoom #1529 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.UCR P5316 172-Signage: West<strong>Life</strong> Wing Room #1529 on<strong>Science</strong> the 1st Floor of <strong>Life</strong>Building <strong>Science</strong>s Psychology.UCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building173-Sales and ServiceCounters: West WingRoom #1529 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.174-Sinks: West WingRoom #1529 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.5 lb. maximum pressure to operate interiordoors. Door hardware is operable with a singleeffort (lever type, panic bar or push pull type).Minimum strike side clearance on PULL side ofdoor: 18" interior doors, front approach.Signage for Permanent Rooms and Spaces:Letters are 1/32" raised, uppercase or sans serifw/ Grade II Braille.A portion of the counter is a minimum of 36" inlength, at a height between 28" - 34" above thefloor and;34" maximum height of rim or counter abovefloor surfaces. Sink is a maximum of 6-1/2"deep. Knee clearance under sink is a minimumof 27" high and 30" wide, and provides anabsolute depth of 19" underneath the sink[ADAAG 606.2 Exception 6 The dip of theoverflow shall not be considered in determiningknee and toe clearance]. Faucets are operablewith one hand and do not require tight grasping,pinching or twisting of the wrist.Adjust door opening pressure /closing time unless acceptedby DSA Fire / <strong>Life</strong> Safety.Consider issues connectedwith building pressure / climatecontrol. Replace doorhardware with complianthardware.1 $784.01Relocate fire extinguisher. 1 $0.00Install permanent ID sign tolatch side of door.1 $183.75Provide an accessible counter. 2 $1,225.03Replace with accessible sink.Cut the paneling under the sinkcounter to comply with kneeclearance. Insulate pipesunder sink.3 $3,920.096/1/2012 Page 28 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building175-Seating, Tables andWork Surfaces: WestWing Room #1529 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[Work stations.]30" x 48" min. clear floor space is provided. 27"high, 30" wide and 19" deep knee clearanceprovided.Provide accessible table. 1M $245.01 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.UCR P5316<strong>Life</strong><strong>Science</strong>Building176-Seating, Tables andWork Surfaces: WestWing Room #1529 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[Table at entrance.]27" high, 30" wide and 19" deep knee clearanceprovided.Provide accessible table. 1M $245.01 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.6/1/2012 Page 29 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>BuildingUCR P5316<strong>Life</strong><strong>Science</strong>Building178-Doors: West WingRoom #1535 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [Door hasno closer.]180-Signage: WestWing Room #1535 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.181-Sales and ServiceCounters: West WingRoom #1535 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.182-Sinks: West WingRoom #1535 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology.32" minimum clear width of doorway. Doorhardware is operable with a single effort (levertype, panic bar or push pull type).Permanent I.D. signs, when provided, areinstalled on the wall adjacent to the latch side ofthe door NOTE: At double leaf doors, and whenthere is no room on the latch side, signs shall beplaced on the nearest adjacent wall, preferablyon the right.A portion of the counter is a minimum of 36" inlength, at a height between 28" - 34" above thefloor and; Knee space at table(s) is at least 27"high, 30" wide and extends 19" under thetable(s) and;34" maximum height of rim or counter abovefloor surfaces. Knee clearance under sink is aminimum of 27" high and 30" wide, and providesan absolute depth of 19" underneath the sink[ADAAG 606.2 Exception 6 The dip of theoverflow shall not be considered in determiningknee and toe clearance]. Faucets are lever type,electronically activated or approved self-closingvalves (minimum 10 second open flow). Faucetsare operable with one hand and do not requiretight grasping, pinching or twisting of the wrist.Replace door hardware withcompliant hardware. Replacedoor and frame (concrete orblock wall).Install permanent ID sign tolatch side of door.1 $5,745.381 $183.75Install accessible counters. 2 $2,450.06Replace with accessible sink.Cut the paneling under the sinkcounter to comply with kneeclearance. Insulate pipesunder sink.3 $3,920.096/1/2012 Page 30 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building183-Seating, Tables andWork Surfaces: WestWing Room #1535 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[One fume hood.]27" high, 30" wide and 19" deep knee clearanceprovided. 28" - 34" height of table or worksurface that is 36" wide.Replace the fume hood with anaccessible fume hoodworkstation.3 $18,216.00 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.UCR P5316<strong>Life</strong><strong>Science</strong>Building184-Seating, Tables andWork Surfaces: WestWing Room #1535 onthe 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.[Computer desks.]30" x 48" min. clear floor space is provided. 27"high, 30" wide and 19" deep knee clearanceprovided.Provide accessible table. 1M $245.01 Until such timeas accessiblefurniture /stations areavailable in thisroom staff shallbe informed ofthe immediateavailability ofaccessiblefurniture /stations thatmay be placedin the room tomeet the needsof people withdisabilities.6/1/2012 Page 31 of 32


Report #UCR P5316 <strong>Life</strong> <strong>Science</strong> BuildingReportNameItem/LocationBarrier(noted feature, item or area does not meet thenew construction criteria detailed below)Action Priority TargetDateEstimatedCostInterimSolutionActionCompletionDateUCR P5316<strong>Life</strong><strong>Science</strong>Building185-Controls, OperatingMechanisms & VendingMachines.: West WingRoom #1535 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>sPsychology. [Variouscontrols throughout thelab: outlets, spigots,paper towel dispenser,VWR machine, Milliporemachine and centrifuge.Relocate the paper toweldispenser. Relocate theMillipore machine.Relocate the outlets andspigots.]Controls and operating mechanisms (handles,coin slots, openings, buttons, etc.) are operablewith one hand and do not require tight grasping,pinching or twisting of the wrist to operate.Forward Reach to Objects: Highest operablepart of object is a maximum of 48" above thefloor surface. Side Reach Over Obstructions:The maximum height of the obstruction is 34"from the floor surface. Side Reach OverObstructions: Maximum depth of obstruction is24".Contact the provider to install acompliant machine.3 $0.00Grand Total $329,924.166/1/2012 Page 32 of 32


Cost Report


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal3. Signage - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.754. Tactile Exit Signage - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.755. Floors and Levels - <strong>Life</strong> <strong>Science</strong> Psychology North Entrance Door.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Secure loose doormat. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.017. Electrical Controls & Receptacles/Fire Alarm Boxes - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate electrical receptacle. 3 ea. $632.00 $1,896.00 $2,085.60 $2,346.30 $2,698.24 $2,698.24Relocate fire alarm initiating device. 3 ea. $480.00 $1,440.00 $1,584.00 $1,782.00 $2,049.30 $2,049.30TOTAL EST: $4,747.548. Visual/Audible Alarms - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>.Priority: 0RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62TOTAL EST: $7,115.629. Hazards - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $122.51Page 1 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal10. Doors - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless acceptedby DSA / Fire <strong>Life</strong> Safety.Provide a sign/decal displaying the international symbol of accessibility.1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.261 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51TOTAL EST: $330.7712. Signage - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7513. Floors and Levels - At West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Secure loose doormat. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0114. Elevators - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install/Replace handrail on rear wall of elevator cab. 1 ea. $516.48 $516.48 $568.13 $639.15 $735.02 $735.02TOTAL EST: $735.0215. Elevator Control (Panel & Hall Call) - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Replace elevator control panel. 1 ea. $23,241.60 $23,241.60 $25,565.76 $28,761.48 $33,075.70 $33,075.70Raise/Lower hall call buttons to 42” from floor. 2 ea. $1,239.55 $2,479.10 $2,727.01 $3,067.89 $3,528.07 $3,528.07TOTAL EST: $36,603.77Page 2 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal16. Visual and Audible Signals For Elevators - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install audible signals. 1 ea. $860.80 $860.80 $946.88 $1,065.24 $1,225.03 $1,225.03Replace/Install new jamb signage. 3 ea. $258.24 $774.72 $852.19 $958.71 $1,102.52 $1,102.52TOTAL EST: $2,327.5517. Water Fountains (Drinking) - North to South Corridor at 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install new single drinking fountain. 1 ea. $3,840.00 $3,840.00 $4,224.00 $4,752.00 $5,464.80 $5,464.80Install cane-detectable barrier around fountain. 2 ea. $413.18 $826.36 $909.00 $1,022.62 $1,176.01 $1,176.01TOTAL EST: $6,640.8118. Protruding Objects - North to South Corridor at 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0119. Protruding Objects - Near the Souther Exterior Door at 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0120. Doors - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Install kick-plate to bottom of door. 1 ea. $68.86 $68.86 $75.75 $85.22 $98.00 $98.00TOTAL EST: $404.26Page 3 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal22. Signage - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7523. Tactile Exit Signage - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7524. Floors and Levels - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Secure loose doormat. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0125. Doors - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76TOTAL EST: $784.0227. Signage - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75Page 4 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal28. Doors - Southwest of Corridor Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76Remove door stop. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25TOTAL EST: $845.2729. Clear Space at Doors - Southwest of Corridor Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Remove door latch and/or door closer. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0130. Signage - Doors Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7531. Doors - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware. 2 ea. $335.71 $671.42 $738.56 $830.88 $955.51 $955.51TOTAL EST: $1,261.7732. Clear Space at Doors - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Remove door latch and/or door closer. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01Page 5 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal33. Signage - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 2 ea. $129.12 $258.24 $284.06 $319.57 $367.51 $367.51TOTAL EST: $367.5135. Aisles - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Clear aisle width(s) to comply with minimum required aisle 7 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00width(s) listed above.TOTAL EST: $0.0036. Sales and Service Counters - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Lower 36” wide counter section or provide an auxiliary counter 1 ea. $1,119.04 $1,119.04 $1,230.94 $1,384.81 $1,592.53 $1,592.53with a maximum height of 34”.TOTAL EST: $1,592.5337. Sinks - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00knee clearance.TOTAL EST: $3,920.0838. Seating, Tables and Work Surfaces - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide accessible table. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00TOTAL EST: $490.00Page 6 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal39. Hazards - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Modify, relocate, replace or remove restricting objects. 20 ea. $172.16 $3,443.20 $3,787.52 $4,260.96 $4,900.10 $4,900.10TOTAL EST: $4,900.1040. Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.TOTAL EST: $306.2641. Clear Space at Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Remove door latch and/or door closer. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0142. Signage - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7546. Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware. 2 ea. $335.71 $671.42 $738.56 $830.88 $955.51 $955.51TOTAL EST: $1,261.77Page 7 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal48. Signage - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 2 ea. $129.12 $258.24 $284.06 $319.57 $367.51 $367.51TOTAL EST: $367.5150. Electrical Controls & Receptacles/Fire Alarm Boxes - East Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate fire alarm initiating device. 1 ea. $480.00 $480.00 $528.00 $594.00 $683.10 $683.10TOTAL EST: $683.1051. Visual/Audible Alarms - North / South Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 0RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62TOTAL EST: $7,115.6252. Tactile Exit Signage - Near the South Stairway on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7553. Protruding Objects - South End of Corridor by Stairs on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $122.5154. Doors - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61Install kick-plate to bottom of door. 1 ea. $68.86 $68.86 $75.75 $85.22 $98.00 $98.00TOTAL EST: $5,365.61Page 8 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal55. Clear Space at Doors - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install automatic door opening device. 1 ea. $4,560.00 $4,560.00 $5,016.00 $5,643.00 $6,489.45 $6,489.45TOTAL EST: $6,489.4556. Identification Symbols, Restrooms - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $367.5057. Multiple Accommodation Toilets - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62Provide major renovation (including moving plumbing locations 75 s.f. $320.00 $24,000.00 $26,400.00 $29,700.00 $34,155.00 $34,155.00and walls).TOTAL EST: $41,270.6258. Toilet Grab Bars - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install grab bar. 2 ea. $258.24 $516.48 $568.13 $639.15 $735.02 $735.02TOTAL EST: $735.0259. Lavatories - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Raise/Lower existing lavatory. 1 ea. $1,549.44 $1,549.44 $1,704.38 $1,917.43 $2,205.04 $2,205.04Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $2,450.05Page 9 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal60. Urinals - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install urinal. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Widen partitions around urinal. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,430.0862. Accessories - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install new accessible mirror. 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $735.0264. Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61TOTAL EST: $5,573.8765. Clear Space at Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Reverse door swing. 1 ea. $1,351.46 $1,351.46 $1,486.61 $1,672.44 $1,923.31 $1,923.31TOTAL EST: $1,923.3166. Identification Symbols, Restrooms - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $367.50Page 10 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal67. Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Remove door and frame. 1 ea. $516.48 $516.48 $568.13 $639.15 $735.02 $735.02Widen existing doorway. 1 ea. $1,721.60 $1,721.60 $1,893.76 $2,130.48 $2,450.05 $2,450.05TOTAL EST: $3,185.0770. Multiple Accommodation Toilets - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62Provide major renovation (including moving plumbing locations 75 s.f. $320.00 $24,000.00 $26,400.00 $29,700.00 $34,155.00 $34,155.00and walls).TOTAL EST: $41,270.6271. Toilet Grab Bars - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install grab bar. 2 ea. $258.24 $516.48 $568.13 $639.15 $735.02 $735.02TOTAL EST: $735.0272. Lavatories - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,430.0873. Accessories - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate mirror. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $245.02Page 11 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal75. Water Fountains (Drinking) - At 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology Corridor.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install new single drinking fountain. 1 ea. $3,840.00 $3,840.00 $4,224.00 $4,752.00 $5,464.80 $5,464.80Install cane-detectable barrier around fountain. 2 ea. $413.18 $826.36 $909.00 $1,022.62 $1,176.01 $1,176.01Install paper cup dispenser at existing fountain. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $6,824.5677. Protruding Objects - 2nd Floor <strong>Life</strong> <strong>Science</strong>s Next to the Elevator.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $122.5178. Doors - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Provide a sign/decal displaying the international symbol of accessibility.1 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51TOTAL EST: $330.7780. Signage - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7581. Hazards - Clock at the East Corridor of <strong>Life</strong> <strong>Science</strong>s.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $122.51Page 12 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal83. Hazards - West Corridor Running North to South on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $122.5184. Doors - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and #2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 7 ea. $335.71 $2,349.97 $2,584.97 $2,908.09 $3,344.30 $3,344.30TOTAL EST: $3,344.3085. Clear Space at Doors - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and #2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25TOTAL EST: $61.2586. Signage - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and #2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 7 ea. $129.12 $903.84 $994.22 $1,118.50 $1,286.27 $1,286.27TOTAL EST: $1,286.2787. Doors - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless acceptedby DSA / Fire <strong>Life</strong> Safety.1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26TOTAL EST: $306.2688. Clear Space at Doors - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25TOTAL EST: $61.25Page 13 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal89. Signage - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7590. Seating, Tables and Work Surfaces - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide accessible table. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00TOTAL EST: $490.0091. Aisles - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Relocate furniture to provide clear space. 4 ea. $43.04 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.0193. Controls, Operating Mechanisms & Vending Machines. - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install accessible counter. 1 ea. $860.80 $860.80 $946.88 $1,065.24 $1,225.03 $1,225.03Relocate furniture to provide clear space. 1 ea. $43.04 $43.04 $47.34 $53.26 $61.25 $61.25TOTAL EST: $1,286.2894. Sinks - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00knee clearance.Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,920.08Page 14 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal95. Doors - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76TOTAL EST: $477.7696. Clear Space at Doors - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Reverse door swing. 1 ea. $1,351.46 $1,351.46 $1,486.61 $1,672.44 $1,923.31 $1,923.31TOTAL EST: $1,923.3197. Signage - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.7598. Doors - Rooms #2505, #2510, #2515, #2520, #2525, #2530 and #2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 7 ea. $335.71 $2,349.97 $2,584.97 $2,908.09 $3,344.30 $3,344.30TOTAL EST: $3,344.30100. Signage - Rooms #2505, #2510, #2515, #2520, #2525, #2530 and #2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 7 ea. $129.12 $903.84 $994.22 $1,118.50 $1,286.27 $1,286.27TOTAL EST: $1,286.27101. Doors - Rooms #2600, #2605, #2610, #2615, #2620, #2625, #2630, #2635 and #2640 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 9 ea. $335.71 $3,021.39 $3,323.53 $3,738.97 $4,299.82 $4,299.82TOTAL EST: $4,299.82Page 15 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal103. Signage - Rooms #2600, #2605, #2610, #2615, #2620, #2625, #2630, #2635 and #2640 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 9 ea. $129.12 $1,162.08 $1,278.29 $1,438.08 $1,653.79 $1,653.79TOTAL EST: $1,653.79104. Doors - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 2 ea. $215.20 $430.40 $473.44 $532.62 $612.51 $612.51by DSA / Fire <strong>Life</strong> Safety.TOTAL EST: $612.51106. Signage - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 2 ea. $129.12 $258.24 $284.06 $319.57 $367.51 $367.51TOTAL EST: $367.51107. Tactile Exit Signage - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 2 ea. $129.12 $258.24 $284.06 $319.57 $367.51 $367.51TOTAL EST: $367.51108. Protruding Objects - Time Sheet Box West of Room #2705 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s.Priority: 1RECOMMENDATIONS AND RETROFIT COSTS:Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01109. Doors - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76TOTAL EST: $477.76Page 16 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal111. Signage - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75113. Electrical Controls & Receptacles/Fire Alarm Boxes - West Wing Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate fire alarm initiating device. 1 ea. $480.00 $480.00 $528.00 $594.00 $683.10 $683.10TOTAL EST: $683.10114. Visual/Audible Alarms - West Wing Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 0RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62TOTAL EST: $7,115.62115. Water Fountains (Drinking) - West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install new single drinking fountain. 1 ea. $3,840.00 $3,840.00 $4,224.00 $4,752.00 $5,464.80 $5,464.80Install cane-detectable barrier around fountain. 2 ea. $413.18 $826.36 $909.00 $1,022.62 $1,176.01 $1,176.01TOTAL EST: $6,640.81116. Doors - Rooms #2710, #2715, #2720, #2725, #2730, #2735, #2740, #2745, #2805 and #2840 on the 2nd Floor West Wing of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 10 ea. $335.71 $3,357.10 $3,692.81 $4,154.41 $4,777.57 $4,777.57TOTAL EST: $4,777.57118. Signage - Rooms #2710, #2715, #2720, #2725, #2730, #2735, #2740, #2745, #2805 and #2840 on the 2nd Floor West Wing of <strong>Life</strong> <strong>Science</strong>s.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 10 ea. $129.12 $1,291.20 $1,420.32 $1,597.86 $1,837.54 $1,837.54TOTAL EST: $1,837.54Page 17 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal119. Tactile Exit Signage - Stairs at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75120. Doors - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace or modify the threshold. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Post a sign/decal displaying the ”International Symbol of Accessibility”1 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51at the primary entrance.TOTAL EST: $575.78121. Clear Space at Doors - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install level exterior door landing. 50 s.f. $17.22 $861.00 $947.10 $1,065.49 $1,225.31 $1,225.31TOTAL EST: $1,225.31122. Signage - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75123. Tactile Exit Signage - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75Page 18 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal124. Floors and Levels - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Secure loose doormat. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01126. Electrical Controls & Receptacles/Fire Alarm Boxes - West Wing Main Corridor at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate fire alarm initiating device. 1 ea. $480.00 $480.00 $528.00 $594.00 $683.10 $683.10TOTAL EST: $683.10127. Visual/Audible Alarms - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 0RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62TOTAL EST: $7,115.62128. Controls, Operating Mechanisms & Vending Machines. - West Wing Corridor at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Lower the house phone. 1 ea. $150.00 $150.00 $165.00 $185.62 $213.46 $213.46TOTAL EST: $213.46130. Controls, Operating Mechanisms & Vending Machines. - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Contact the provider to install a compliant machine. 1 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00TOTAL EST: $0.00131. Water Fountains (Drinking) - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install new single drinking fountain. 1 ea. $3,840.00 $3,840.00 $4,224.00 $4,752.00 $5,464.80 $5,464.80Install cane-detectable barrier around fountain. 2 ea. $413.18 $826.36 $909.00 $1,022.62 $1,176.01 $1,176.01TOTAL EST: $6,640.81Page 19 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal132. Doors - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.TOTAL EST: $306.26134. Signage - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75135. Tactile Exit Signage - West Wing Exit Doors to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide compliant sign. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75136. Doors - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61TOTAL EST: $5,745.37137. Clear Space at Doors - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install automatic door opening device. 1 ea. $4,560.00 $4,560.00 $5,016.00 $5,643.00 $6,489.45 $6,489.45TOTAL EST: $6,489.45Page 20 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal138. Identification Symbols, Restrooms - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $367.50139. Multiple Accommodation Toilets - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62Provide major renovation (including moving plumbing locations 75 s.f. $320.00 $24,000.00 $26,400.00 $29,700.00 $34,155.00 $34,155.00and walls).TOTAL EST: $41,270.62140. Toilet Grab Bars - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install grab bar. 2 ea. $258.24 $516.48 $568.13 $639.15 $735.02 $735.02TOTAL EST: $735.02141. Lavatories - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,430.08142. Accessories - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate mirror. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $245.02Page 21 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal144. Doors - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61TOTAL EST: $6,051.63145. Clear Space at Doors - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00TOTAL EST: $0.00146. Identification Symbols, Restrooms - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install door-mounted sign on single door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $367.50147. Multiple Accommodation Toilets - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62Provide major renovation (including moving plumbing locations 75 s.f. $320.00 $24,000.00 $26,400.00 $29,700.00 $34,155.00 $34,155.00and walls).TOTAL EST: $41,270.62148. Toilet Grab Bars - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install grab bar. 2 ea. $258.24 $516.48 $568.13 $639.15 $735.02 $735.02TOTAL EST: $735.02Page 22 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal149. Lavatories - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible lavatory. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,430.08150. Urinals - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install urinal. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Widen partitions around urinal. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,430.08152. Accessories - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Relocate mirror. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51TOTAL EST: $245.02154. Doors - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76TOTAL EST: $477.76155. Clear Space at Doors - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install automatic door opening device. 1 ea. $4,560.00 $4,560.00 $5,016.00 $5,643.00 $6,489.45 $6,489.45TOTAL EST: $6,489.45Page 23 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal156. Signage - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75157. Seating, Tables and Work Surfaces - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Install accessible counter. 1 ea. $860.80 $860.80 $946.88 $1,065.24 $1,225.03 $1,225.03Move built-in counter to provide adequate clear space. 1 ea. $1,291.20 $1,291.20 $1,420.32 $1,597.86 $1,837.54 $1,837.54TOTAL EST: $3,062.57158. Sales and Service Counters - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install accessible counter. 1 ea. $860.80 $860.80 $946.88 $1,065.24 $1,225.03 $1,225.03TOTAL EST: $1,225.03159. Sinks - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00knee clearance.Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,920.08160. Aisles - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Clear aisle width(s) to comply with minimum required aisle 1 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00width(s) listed above.TOTAL EST: $0.00Page 24 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal161. Seating, Tables and Work Surfaces - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00TOTAL EST: $18,216.00162. Controls, Operating Mechanisms & Vending Machines. - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Contact the provider to install a compliant machine. 1 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00TOTAL EST: $0.00163. Doors - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76TOTAL EST: $477.76165. Signage - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75166. Sales and Service Counters - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Lower 36” wide counter section or provide an auxiliary counter 2 ea. $1,119.04 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07with a maximum height of 34”.TOTAL EST: $3,185.07Page 25 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal167. Sinks - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00knee clearance.Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,920.08168. Seating, Tables and Work Surfaces - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01169. Controls, Operating Mechanisms & Vending Machines. - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Contact the provider to install a compliant machine. 2 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00TOTAL EST: $0.00170. Doors - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Adjust door for opening pressure/closing times unless accepted 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76TOTAL EST: $784.02172. Signage - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75Page 26 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal173. Sales and Service Counters - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Lower 36” wide counter section or provide an auxiliary counter 1 ea. $1,119.04 $1,119.04 $1,230.94 $1,384.81 $1,592.53 $1,592.53with a maximum height of 34”.TOTAL EST: $1,592.53174. Sinks - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00knee clearance.Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,920.08175. Seating, Tables and Work Surfaces - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01176. Seating, Tables and Work Surfaces - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01178. Doors - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Replace door hardware with compliant hardware. 1 ea. $335.71 $335.71 $369.28 $415.44 $477.76 $477.76Replace door and frame (concrete or block wall). 1 ea. $3,701.44 $3,701.44 $4,071.58 $4,580.53 $5,267.61 $5,267.61TOTAL EST: $5,745.37Page 27 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal180. Signage - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install permanent ID sign to latch side of door. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75TOTAL EST: $183.75181. Sales and Service Counters - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 2RECOMMENDATIONS AND RETROFIT COSTS:Install accessible counter. 2 ea. $860.80 $1,721.60 $1,893.76 $2,130.48 $2,450.05 $2,450.05TOTAL EST: $2,450.05182. Sinks - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00knee clearance.Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $3,920.08183. Seating, Tables and Work Surfaces - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Replace the fume hood with an accessible fume hood workstation. 1 ea. $12,800.00 $12,800.00 $14,080.00 $15,840.00 $18,216.00 $18,216.00TOTAL EST: $18,216.00184. Seating, Tables and Work Surfaces - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01TOTAL EST: $245.01Page 28 of 29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue Qty UnitSubContractorSubTotal(10%)ConcealedConditions(12.5%)SecurityConditions(15%)GeneralConditionsTotal185. Controls, Operating Mechanisms & Vending Machines. - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Priority: 3RECOMMENDATIONS AND RETROFIT COSTS:Contact the provider to install a compliant machine. 2 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00TOTAL EST: $0.00REPORT TOTALS: $330,720.29 $363,792.32 $409,266.36 $470,656.31 $470,656.31Page 29 of 29


Survey


Americans with Disabilities Act of 1990Site Assessment ReportReport: UCR P5316 <strong>Life</strong><strong>Science</strong> Building900 University AvenueRiverside, CA 92521Inspection Date: 09/08/2009Prepared for:University of California at RiversidePrepared by:National Access Consultants, LLC2321 Abbot Kinney Blvd. Suite 200Venice, California 90291(805)497-6116


Contents1. Doors - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building. . . . . . . . . . . . . . . . . . . . . . . . . . 12. Clear Space at Doors - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building. . . . . . . . . . . . . . . . . 33. Signage - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building. . . . . . . . . . . . . . . . . . . . . . . . . 54. Tactile Exit Signage - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building. . . . . . . . . . . . . . . . . . 75. Floors and Levels - <strong>Life</strong> <strong>Science</strong> Psychology North Entrance Door. . . . . . . . . . . . . . . . . . . . 86. Corridors - North to South Corridor on the 1st Floor of <strong>Life</strong> <strong>Science</strong> Building. . . . . . . . . . . . . 97. Electrical Controls & Receptacles/Fire Alarm Boxes - North to South Corridor on 1st Floor of <strong>Life</strong><strong>Science</strong>. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108. Visual/Audible Alarms - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>. . . . . . . . . . . . . 129. Hazards - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>. . . . . . . . . . . . . . . . . . . . . 1310. Doors - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1411. Clear Space at Doors - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . 1612. Signage - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . 1813. Floors and Levels - At West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . 2014. Elevators - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2115. Elevator Control (Panel & Hall Call) - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . 2416. Visual and Audible Signals For Elevators - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 2617. Water Fountains (Drinking) - North to South Corridor at 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . 2718. Protruding Objects - North to South Corridor at 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . 2919. Protruding Objects - Near the Souther Exterior Door at 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . 3020. Doors - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . 3121. Clear Space at Doors - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology. 3322. Signage - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . 3523. Tactile Exit Signage - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . 3624. Floors and Levels - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong> <strong>Science</strong> Psychology. . . 3725. Doors - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . 3826. Clear Space at Doors - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . 4027. Signage - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . 42


28. Doors - Southwest of Corridor Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . 4329. Clear Space at Doors - Southwest of Corridor Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong>Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4530. Signage - Doors Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . . 4731. Doors - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . . . . . . . . . . 4832. Clear Space at Doors - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . 5033. Signage - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . . . . . . . . . 5234. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong>Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5335. Aisles - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . . . . . . . . . . 5436. Sales and Service Counters - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . 5637. Sinks - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . . . . . . . . . . 5738. Seating, Tables and Work Surfaces - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . 5939. Hazards - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology. . . . . . . . . . . . . . . . . . . . . 6040. Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . 6141. Clear Space at Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . 6342. Signage - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . 6543. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #1419 Survey Research Center at <strong>Life</strong><strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6644. Seating, Tables and Work Surfaces - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. 6745. Controls, Operating Mechanisms & Vending Machines. - Room #1419 Survey Research Center at<strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6846. Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . 6947. Clear Space at Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . 7148. Signage - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . 7349. Corridors - East Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . 7450. Electrical Controls & Receptacles/Fire Alarm Boxes - East Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. 7651. Visual/Audible Alarms - North / South Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . 7852. Tactile Exit Signage - Near the South Stairway on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . 8053. Protruding Objects - South End of Corridor by Stairs on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . 8154. Doors - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . 8255. Clear Space at Doors - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . 84


56. Identification Symbols, Restrooms - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . 8657. Multiple Accommodation Toilets - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . 8758. Toilet Grab Bars - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . 9059. Lavatories - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . 9160. Urinals - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . 9361. Alcoves - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . 9462. Accessories - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . 9563. Electrical Controls & Receptacles/Fire Alarm Boxes - South Men’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9764. Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . 9965. Clear Space at Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . 10166. Identification Symbols, Restrooms - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . 10367. Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . 10468. Clear Space at Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . 10669. Signage - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . 10870. Multiple Accommodation Toilets - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . 10971. Toilet Grab Bars - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . 11272. Lavatories - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . 11373. Accessories - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . 11574. Electrical Controls & Receptacles/Fire Alarm Boxes - Women’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11775. Water Fountains (Drinking) - At 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology Corridor. . . . . . . . . . . . 11876. Signage - At 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology Corridor. . . . . . . . . . . . . . . . . . . . . . . 12077. Protruding Objects - 2nd Floor <strong>Life</strong> <strong>Science</strong>s Next to the Elevator. . . . . . . . . . . . . . . . . . . . 12178. Doors - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>. . . . . . . . . . . . . . . . . . . . . . . 12279. Clear Space at Doors - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>. . . . . . . . . . . . . . 12480. Signage - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>. . . . . . . . . . . . . . . . . . . . . 12681. Hazards - Clock at the East Corridor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . . . 12882. Corridors - West Corridor Running North to South on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . 12983. Hazards - West Corridor Running North to South on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . 130


84. Doors - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and #2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13185. Clear Space at Doors - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and #2430 at <strong>Life</strong><strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13386. Signage - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and #2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13587. Doors - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . 13688. Clear Space at Doors - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . 13889. Signage - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . 14090. Seating, Tables and Work Surfaces - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . 14191. Aisles - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . 14292. Controls, Operating Mechanisms & Vending Machines. - Room #2418 on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14493. Controls, Operating Mechanisms & Vending Machines. - Room #2418 on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14594. Sinks - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . 14695. Doors - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . 14896. Clear Space at Doors - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . 14997. Signage - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . 15098. Doors - Rooms #2505, #2510, #2515, #2520, #2525, #2530 and #2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15199. Clear Space at Doors - Rooms #2505, #2510, #2515, #2520, #2525, #2530 and #2535 at <strong>Life</strong><strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153100.Signage - Rooms #2505, #2510, #2515, #2520, #2525, #2530 and #2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155101.Doors - Rooms #2600, #2605, #2610, #2615, #2620, #2625, #2630, #2635 and #2640 on the2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156102.Clear Space at Doors - Rooms #2600, #2605, #2610, #2615, #2620, #2625, #2630, #2635 and#2640 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . 158103.Signage - Rooms #2600, #2605, #2610, #2615, #2620, #2625, #2630, #2635 and #2640 on the2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160104.Doors - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . 161105.Clear Space at Doors - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s. . . . . . . . 163106.Signage - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . 165107.Tactile Exit Signage - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . 167


108.Protruding Objects - Time Sheet Box West of Room #2705 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s. . . 168109.Doors - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . 169110.Clear Space at Doors - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . 171111.Signage - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . 173112.Corridors - West Wing Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . 174113.Electrical Controls & Receptacles/Fire Alarm Boxes - West Wing Corridor on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175114.Visual/Audible Alarms - West Wing Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . 176115.Water Fountains (Drinking) - West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . 177116.Doors - Rooms #2710, #2715, #2720, #2725, #2730, #2735, #2740, #2745, #2805 and #2840on the 2nd Floor West Wing of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179117.Clear Space at Doors - Rooms #2710, #2715, #2720, #2725, #2730, #2735, #2740, #2745,#2805 and #2840 on the 2nd Floor West Wing of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . 181118.Signage - Rooms #2710, #2715, #2720, #2725, #2730, #2735, #2740, #2745, #2805 and #2840on the 2nd Floor West Wing of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183119.Tactile Exit Signage - Stairs at the West Wing on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s. . . . . . . . . . . 184120.Doors - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . . . . . . . . 185121.Clear Space at Doors - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . 188122.Signage - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . . . . . . . 190123.Tactile Exit Signage - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . 192124.Floors and Levels - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . 193125.Corridors - West Wing Main Corridor at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . . . 194126.Electrical Controls & Receptacles/Fire Alarm Boxes - West Wing Main Corridor at <strong>Life</strong> <strong>Science</strong>sPsychology on the 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195127.Visual/Audible Alarms - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . . . . 196128.Controls, Operating Mechanisms & Vending Machines. - West Wing Corridor at <strong>Life</strong> <strong>Science</strong>s Psychologyon the 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197129.Protruding Objects - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . . . . . . 198130.Controls, Operating Mechanisms & Vending Machines. - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology onthe 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199131.Water Fountains (Drinking) - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor. . . . . . . . 200132.Doors - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . 202133.Clear Space at Doors - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 204


134.Signage - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . 206135.Tactile Exit Signage - West Wing Exit Doors to Stairwell on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 207136.Doors - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 208137.Clear Space at Doors - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210138.Identification Symbols, Restrooms - Women’s Restroom #1517 at the West Wing on the 1st Floorof <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212139.Multiple Accommodation Toilets - Women’s Restroom #1517 at the West Wing on the 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213140.Toilet Grab Bars - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216141.Lavatories - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 217142.Accessories - Women’s Restroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219143.Electrical Controls & Receptacles/Fire Alarm Boxes - Women’s Restroom #1517 at the West Wingon the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220144.Doors - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . 222145.Clear Space at Doors - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224146.Identification Symbols, Restrooms - Men’s Restroom #1522 at the West Wing on the 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226147.Multiple Accommodation Toilets - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227148.Toilet Grab Bars - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230149.Lavatories - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 231150.Urinals - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . 233151.Alcoves - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . 234152.Accessories - Men’s Restroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 235153.Electrical Controls & Receptacles/Fire Alarm Boxes - Men’s Restroom #1522 at the West Wing onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236154.Doors - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 238155.Clear Space at Doors - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . 240156.Signage - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . 242


157.Seating, Tables and Work Surfaces - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243158.Sales and Service Counters - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 244159.Sinks - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . 246160.Aisles - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 248161.Seating, Tables and Work Surfaces - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250162.Controls, Operating Mechanisms & Vending Machines. - West Wing Room #1521 on the 1st Floorof <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251163.Doors - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 253164.Clear Space at Doors - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . 255165.Signage - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . 257166.Sales and Service Counters - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 258167.Sinks - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . 259168.Seating, Tables and Work Surfaces - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261169.Controls, Operating Mechanisms & Vending Machines. - West Wing Room #1523 on the 1st Floorof <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262170.Doors - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 264171.Clear Space at Doors - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . 266172.Signage - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . 268173.Sales and Service Counters - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 269174.Sinks - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . 270175.Seating, Tables and Work Surfaces - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272176.Seating, Tables and Work Surfaces - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273177.Aisles - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 274178.Doors - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . 275179.Clear Space at Doors - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . 277180.Signage - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . 279181.Sales and Service Counters - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. 280182.Sinks - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . 281


183.Seating, Tables and Work Surfaces - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283184.Seating, Tables and Work Surfaces - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284185.Controls, Operating Mechanisms & Vending Machines. - West Wing Room #1535 on the 1st Floorof <strong>Life</strong> <strong>Science</strong>s Psychology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue1. Doors - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building.Memo:Automatic door.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clearance with automatic doors fully open.The international symbol of accessibility is posted at all primary entrances.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-1-1 (originally 1-400)1


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-1-2 (originally 2-400)2


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue2. Clear Space at Doors - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-2-1 (originally 3-400)3


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-2-2 (originally 4-400)4


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue3. Signage - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-3-1 (originally 5-400)5


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-3-2 (originally 6-400)6


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue4. Tactile Exit Signage - North 1st Floor Entry at <strong>Life</strong> <strong>Science</strong> Building.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-4-1 (originally 7-400)7


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue5. Floors and Levels - <strong>Life</strong> <strong>Science</strong> Psychology North Entrance Door.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not fastened.)Recommendation:Secure loose doormat.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-5-1 (originally 8-400)8


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue6. Corridors - North to South Corridor on the 1st Floor of <strong>Life</strong> <strong>Science</strong>Building.Memo:Areas noted in compliance:44” minimum width for occupant loads of 10 or more.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-6-1 (originally 9-400)9


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue7. Electrical Controls & Receptacles/Fire Alarm Boxes - North to SouthCorridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.Areas not meeting new construction standards:The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the floor orworking platform. (12” (3).)The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from thefloor level to the highest point of the activating handle or lever of the box. (61-1/2” (3).)Recommendation:Relocate electrical receptacle.Relocate fire alarm initiating device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-7-1 (originally 10-400)10


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-7-2 (originally 11-400)11


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue8. Visual/Audible Alarms - North to South Corridor on 1st Floor of <strong>Life</strong><strong>Science</strong>.Memo:Areas noted in compliance:The alarm is integrated into the building or facility alarm system.Lamp is a xenon strobe type or equivalent.The color is clear and nominal white (unfiltered) or clear filtered white light.The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.The intensity is a maximum of 75 candela.The flash rate is a minimum of 1Hz and a maximum of 3Hz.There are no places in common corridors or hallways that are more than 50’ from required signaling appliances.When provided/required, audible emergency alarms meet applicable requirements.Areas not meeting new construction standards:The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.(86-1/2” (3).)Recommendation:Requires engineering/architectural evaluation.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-8-1 (originally 12-400)12


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue9. Hazards - North to South Corridor on 1st Floor of <strong>Life</strong> <strong>Science</strong>.Memo:One clock.Areas noted in compliance:None observed.Areas not meeting new construction standards:Any obstrution that overhangs a pedestrian way is a minimum 80” above the walking surface (measured from the bottomof the obstruction). (79-1/2” high.)Sidewalks are clear of hazards. (Overhead hazard.)If vertical clearance of an area adjoining an accessible route is reduced to less than 80”, a barrier to warn blind orvisually impaired persons is provided. (No barrier.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-9-1 (originally 13-400)13


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue10. Doors - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:One set of double doors.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate exterior doors. (11 lbs.)The international symbol of accessibility is posted at all primary entrances. (None.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Provide a sign/decal displaying the international symbol of accessibility.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-10-1 (originally 14-400)14


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-10-2 (originally 15-400)15


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue11. Clear Space at Doors - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:One set of double doors.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 24” exterior doors.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-11-1 (originally 16-400)16


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-11-2 (originally 17-400)17


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue12. Signage - West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-12-1 (originally 18-400)18


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-12-2 (originally 19-400)19


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue13. Floors and Levels - At West Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not attached.)Recommendation:Secure loose doormat.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-13-1 (originally 20-400)20


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue14. Elevators - 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #16 for additional recommendations.Areas noted in compliance:Located near major path of travel and are accessible at all times the building is occupied.80” min. width of the car platform with on-center door panels.54” min. depth of the car platform (rear wall to door)51” min. clearance from the rear wall to return panel.36” min. clear width of doorway when fully open.Handrail is provided (1 minimum) on one wall of the car (rear preferred).Operation of doors (opening and closing) is automatic.Elevator is self leveling within 1/2” of floor landings.Compartment doors (if provided) for emergency communication devices is lever type and do not require tight grasping,pinching or twisting of the wrist to operate.Emergency communication device does not require voice communication.The car inside allows for the turning of a wheelchair (enter the car, maneuver within reach of controls, and exit from the car).Handrail is smooth, no sharp edges.Doors are side-slide type (power-operated horizontally sliding).The clearance between the car platform sill and the edge of the hoistway landing is no greater than 1-1/4”.Elevator doors have an automatic reopening device. The device opens the doors when objects pass through the openingat heights of 5” and 29” from the floor without requiring contact. Doors remain open for 20 seconds minimum.Doors remain fully open a minimum of 5 seconds when initially activated.Emergency communication device is a maximum of 48” from the floor.The level of illumination at the platform, car threshold and landing sill is at least 5 foot-candles.Areas not meeting new construction standards:32” (+or- 1”) height of the handrail from the floor. (36-1/2”.)Minimum of 1-1/2” clearance of the handrail from the wall. (1/2”.)Door jambs at all landings identify the floor by both raised Arabic numerals (minimum of 2” in height) and Braillesymbols (immediately to left of numerals). (None.)Recommendation:Install/Replace handrail on rear wall of elevator cab.21


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-14-1 (originally 21-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-14-2 (originally 22-400)22


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-14-3 (originally 23-400)23


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue15. Elevator Control (Panel & Hall Call) - 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Elevator car controls are located on a front wall in cars that have center opening doors, and at the side wall or at the frontwall next to the door if the car has side opening doors.Elevator floor buttons comply with reach range requirements (48” front reach; 54” side reach to centerline of buttons).Control buttons are illuminated and are activated by a mechanical motion that is detectable.3/8” minimum distance between the rows of the control buttons.Emergency controls (stop and alarm) are a minimum of 35” from the floor.Areas not meeting new construction standards:Control buttons are square shouldered, and are a minimum of 3/4” and raised 1/8” plus of minus 1/32” above the sorroundingsurface. (Circular.)All buttons are designated by a 5/8” minimum Arabic Numeral, alphabet or other standard sans serif uppercase character,or standard raised symbol immediately to the left of the control button. (Right.)All raised characters are white on a black background. (Silver.)Grade 2 Braille symbols are located immediately below the raised characters. (Left.)The centerline of hall call buttons in elevator lobbies are located at 42” above the floor. (42-1/2”.)Hall call buttons are a minimum of 3/4” in size and raised 1/8” plus or minus 1/32” above the sorrounding surface.(Recessed.)Hall call button provides visual indication that shows each call registered and extinguishes when answered. (No light.)Hall call buttons are internally illuminated with a white light over the entire surface of the button. (No light.)Recommendation:Replace elevator control panel.Raise/Lower hall call buttons to 42” from floor.24


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-15-1 (originally 24-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-15-2 (originally 25-400)25


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue16. Visual and Audible Signals For Elevators - 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Centerline of the fixture is a minimum of 6’ (72”) in height above the lobby floor. NOTE: The use of in-car lanterns,located in or on the door jambs, visible from the proximity of the call buttons and conforming to items 1, 2, & 3 aboveshall or will be acceptable.Areas not meeting new construction standards:Elevator has visual and audible signals indicating the position of the car on or between floors. The indication is positionedabove the car control panel or over the door. (No audible.)The visual signal for each direction is a minimum of 2-1/2” x 2-1/2”, and visible from the proximity of the hall callbutton. NOTE: An automatic verbal announcement of the floor number at which a car stops or which a car passes maybe substituted for the audible signal. (1-1/2”.)Audible signal sounds are once for up and twice for down. (or equivalent) (No audible sounds.)Audible signal is no less than 20 decibels with a frequency no higher than 1500 Hz. (No audible sounds.)Recommendation:Replace/Install audible signals.Replace/Install new jamb signage.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-16-1 (originally 26-400)26


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue17. Water Fountains (Drinking) - North to South Corridor at 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:18” minimum depth of fountain.9” high x 17” deep toe clearance.Lever or push bar control is located 6” max. from front edge.Bubbler outlet is 6” maximum from front.Bubbler outlet is 36” maximum from floor.The force required to activate controls does not exceed 5lbf.Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficultybending or stooping. (Cup dispenser is provided.)Areas not meeting new construction standards:32” minimum wide and 18” minimum deep alcove provided. (None.)27” high x 8” deep clear knee space under fountain. (26” high.)Stream of bubbler is parallel to front edge. (Diagonal.)4” minimum height of stream. (2”.)Recommendation:Install new single drinking fountain.Install cane-detectable barrier around fountain.27


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-17-1 (originally 27-400)28


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue18. Protruding Objects - North to South Corridor at 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Two light fixtures.Areas noted in compliance:None observed.Areas not meeting new construction standards:Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passagewaysor aisles if lower edge of object is above 27” and below 80”. (9-1/4” projection at 57” high.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-18-1 (originally 28-400)29


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue19. Protruding Objects - Near the Souther Exterior Door at 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Lighting control box.Areas noted in compliance:None observed.Areas not meeting new construction standards:Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passagewaysor aisles if lower edge of object is above 27” and below 80”. (5” projection at 49-1/2” high.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-19-1 (originally 29-400)30


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue20. Doors - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong><strong>Science</strong> Psychology.Memo:One set of double doors.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Areas not meeting new construction standards:5 lb. maximum pressure to operate exterior doors. (15 - 17 lbs.)Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate). (6”.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Install kick-plate to bottom of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-20-1 (originally 30-400)31


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-20-2 (originally 31-400)32


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue21. Clear Space at Doors - Southwest Entrance to Middle Landing ofStairs at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 24” exterior doors.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-21-1 (originally 32-400)33


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-21-2 (originally 33-400)34


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue22. Signage - Southwest Entrance to Middle Landing of Stairs at <strong>Life</strong><strong>Science</strong> Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-22-1 (originally 30-400)35


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue23. Tactile Exit Signage - North to South Corridor on 1st Floor of <strong>Life</strong><strong>Science</strong> Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactileexit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, asappropriate. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-23-1 (originally 34-400)36


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue24. Floors and Levels - Southwest Entrance to Middle Landing of Stairs at<strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not attached.)Recommendation:Secure loose doormat.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-24-1 (originally 35-400)37


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue25. Doors - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:32” minimum clear width of doorway. (24” / 34”.)5 lb. maximum pressure to operate interior doors. (10 lbs.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2 seconds.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-25-1 (originally 36-400)38


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-25-2 (originally 37-400)39


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue26. Clear Space at Doors - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-26-1 (originally 38-400)40


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-26-2 (originally 39-400)41


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue27. Signage - Room #1447 on 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At doubleleaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably onthe right. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-27-1 (originally 40-400)42


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue28. Doors - Southwest of Corridor Leading to Rooms #1450 B - L at <strong>Life</strong><strong>Science</strong> Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (11 lbs.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate). (Door stop.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware.Remove door stop.43


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-28-1 (originally 41-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-28-2 (originally 42-400)44


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue29. Clear Space at Doors - Southwest of Corridor Leading to Rooms#1450 B - L at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Areas not meeting new construction standards:Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (4-1/2”.)Recommendation:Remove door latch and/or door closer.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-29-1 (originally 43-400)45


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-29-2 (originally 44-400)46


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue30. Signage - Doors Leading to Rooms #1450 B - L at <strong>Life</strong> <strong>Science</strong>Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-30-1 (originally 45-400)47


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue31. Doors - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Two single doors.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (11 lbs (1 door with closer).)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-31-1 (originally 46-400)48


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-31-2 (originally 47-400)49


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue32. Clear Space at Doors - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong>Psychology.Memo:Two single doors.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (One door - 6”.)Recommendation:Remove door latch and/or door closer.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-32-1 (originally 48-400)50


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-32-2 (originally 49-400)51


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue33. Signage - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At doubleleaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably onthe right. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-33-1 (originally 50-400)52


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue34. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #1427on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-34-1 (originally 51-400)53


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue35. Aisles - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:36” minimum width of aisles.Recommendation:Clear aisle width(s) to comply with minimum required aisle width(s) listed above.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-35-1 (originally 53-400)54


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-35-2 (originally 54-400)55


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue36. Sales and Service Counters - Room #1427 on 1st Floor at <strong>Life</strong><strong>Science</strong> Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (37-1/2”.)A minimum 30” x 48” clear floor space is provided at the counter and; (36” deep x 30” wide.)One full unobstructed side of the clear floor space adjoins or overlaps an accessible route. (Non-accessible aisle.)Recommendation:Lower 36” wide counter section or provide an auxiliary counter with a maximum height of 34”.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-36-1 (originally 55-400)56


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue37. Sinks - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:5 lb. maximum force required to activate controls.Areas not meeting new construction standards:Minimum 30” x 48” clear space is provided in front of sink that allows forward approach. (36” deep x 30” wide.)Required clear space adjoins or overlaps an accessible route. (Non-accessible aisle.)34” maximum height of rim or counter above floor surfaces. (37-1/2” high.)Sink is a maximum of 6-1/2” deep. (9” deep.)Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath thesink. (None.)Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow). (Knob.)Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist. (Grasping.)Recommendation:Replace/Install accessible sink.Insulate pipes under lavatory (or sink when applicable).Cut the paneling under the lavatory/sink counter to comply with knee clearance.57


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-37-1 (originally 56-400)58


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue38. Seating, Tables and Work Surfaces - Room #1427 on 1st Floor at<strong>Life</strong> <strong>Science</strong> Psychology.Memo:Areas noted in compliance:28” - 34” height of table or work surface that is 36” wide. (29-1/2” high.)Areas not meeting new construction standards:30” x 48” min. clear floor space is provided. (29” wide.)One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floorspace. (Non-accessible route.)27” high, 30” wide and 19” deep knee clearance provided. (26” high.)Recommendation:Provide accessible table.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-38-1 (originally 57-400)59


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue39. Hazards - Room #1427 on 1st Floor at <strong>Life</strong> <strong>Science</strong> Psychology.Memo:Ceiling suspended plugs.Areas noted in compliance:None observed.Areas not meeting new construction standards:Any obstrution that overhangs a pedestrian way is a minimum 80” above the walking surface (measured from the bottomof the obstruction). (59” - 80” high.)If vertical clearance of an area adjoining an accessible route is reduced to less than 80”, a barrier to warn blind orvisually impaired persons is provided. (No barrier.)Recommendation:Modify, relocate, replace or remove restricting objects.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-39-1 (originally 58-400)60


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue40. Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (12 lbs.)3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2 seconds.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-40-1 (originally 59-400)61


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-40-2 (originally 60-400)62


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue41. Clear Space at Doors - Room #1419 Survey Research Center at <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Areas not meeting new construction standards:Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer. (6”.)Recommendation:Remove door latch and/or door closer.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-41-1 (originally 61-400)63


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-41-2 (originally 62-400)64


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue42. Signage - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (Incorrectsign.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-42-1 (originally 63-400)65


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue43. Electrical Controls & Receptacles/Fire Alarm Boxes - Room #1419Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-43-2 (originally 65-400)66


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue44. Seating, Tables and Work Surfaces - Room #1419 Survey ResearchCenter at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Computer station.Areas noted in compliance:30” x 48” min. clear floor space is provided.One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.27” high, 30” wide and 19” deep knee clearance provided.28” - 34” height of table or work surface that is 36” wide.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-44-1 (originally 66-400)67


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue45. Controls, Operating Mechanisms & Vending Machines. - Room#1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:One fax machine.Areas noted in compliance:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate.Side Reach to Objects: Minimum 30” x 48” clear floor space for side approach is provided at the object.Side Reach to Objects: Clear floor space begins a maximum of 10” from the wall/surface the object is mounted on.Side Reach to Objects: Highest operable part of the object is a maximum of 54” above the floor surface.Side Reach to Objects: Lowest operable part of the object is a minimum of 9” above the floor surface.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-45-1 (originally 67-400)68


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue46. Doors - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Interior offices (one with closer).Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (11 lbs at one door.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knobs on both.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-46-1 (originally 68-400)69


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-46-2 (originally 69-400)70


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue47. Clear Space at Doors - Room #1419 Survey Research Center at <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Interior offices.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-47-1 (originally 70-400)71


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-47-2 (originally 71-400)72


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue48. Signage - Room #1419 Survey Research Center at <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Interior offices.Areas noted in compliance:None observed.Areas not meeting new construction standards:Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At doubleleaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably onthe right. (None at both.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-48-1 (originally 72-400)73


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue49. Corridors - East Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:44” minimum width for occupant loads of 10 or more.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-49-1 (originally 73-400)74


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-49-2 (originally 74-400)75


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue50. Electrical Controls & Receptacles/Fire Alarm Boxes - East Corridor onthe 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the floorlevel to the highest point of the activating handle or lever of the box. (61-1/2”.)Recommendation:Relocate fire alarm initiating device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-50-1 (originally 75-400)76


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-50-2 (originally 76-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-50-3 (originally 77-400)77


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue51. Visual/Audible Alarms - North / South Corridor on the 2nd Floor of<strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:The alarm is integrated into the building or facility alarm system.Lamp is a xenon strobe type or equivalent.The color is clear and nominal white (unfiltered) or clear filtered white light.The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.The intensity is a maximum of 75 candela.The flash rate is a minimum of 1Hz and a maximum of 3Hz.When provided/required, audible emergency alarms meet applicable requirements.Areas not meeting new construction standards:The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower. (86”high.)There are no places in common corridors or hallways that are more than 50’ from required signaling appliances. (Not every50’.)Recommendation:Requires engineering/architectural evaluation.78


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-51-1 (originally 78-400)79


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue52. Tactile Exit Signage - Near the South Stairway on the 2nd Floor of<strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactileexit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, asappropriate. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-52-1 (originally 79-400)80


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue53. Protruding Objects - South End of Corridor by Stairs on the 2nd Floorof <strong>Life</strong> <strong>Science</strong>s.Memo:One light sconce.Areas noted in compliance:None observed.Areas not meeting new construction standards:Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passagewaysor aisles if lower edge of object is above 27” and below 80”. (9-1/4” projection at 57” high.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-53-1 (originally 80-400)81


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue54. Doors - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:See Sequence #55 for additional recommendation.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Areas not meeting new construction standards:32” minimum clear width of doorway. (29”.)5 lb. maximum pressure to operate interior doors. (11 lbs.)Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate). (9” to grate.)Recommendation:Replace door and frame (concrete or block wall).Install kick-plate to bottom of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-54-1 (originally 81-400)82


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-54-2 (originally 82-400)83


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue55. Clear Space at Doors - South Men’s Restroom on the 2nd Floor of<strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:60” min. clear space in direction of door swing. (42-1/2”.)Recommendation:Install automatic door opening device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-55-1 (originally 83-400)84


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-55-2 (originally 84-400)85


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue56. Identification Symbols, Restrooms - South Men’s Restroom on the2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Door mounted signage: Men’s - Equilateral triangle with 12” sides, 1/4” thick with the vertex pointing up. The trianglesymbol contrasts with the door, light on dark background or dark on light background. (Incorrect.)Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (No sign.)Recommendation:Install door-mounted sign on single door.Install wall-mounted sign at single entrance.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-56-1 (originally 85-400)86


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue57. Multiple Accommodation Toilets - South Men’s Restroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.Memo:Provide an accessible stall.Areas noted in compliance:60” min. diameter turning circle clear of objects from floor height to 27” in room.3 second min. automatic closing door.Flush valve is on wide side of the water closet.44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.Front of toilet paper dispenser is within 36” of back wall.The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toiletseat.19” minimum height to toilet paper dispenser.Toilet paper dispenser provides continuous flow.Areas not meeting new construction standards:44” min. clear path provided throughout facility. (35-1/2”.)Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.and twisting.)(Requires pinchingDoor has loop or U-shaped handle immediately below latch on both inside and outside of door. (None.)32” minimum opening at end. (22-1/4” wide.)The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.(30” deep.)The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.(5-1/2” wide x 30” deep.)The clear floor area on the push side of the door is a minimum 48” deep., measured perpendicular to the door in itsclosed position, and 54” wide, measured from the strike edge of the door frame past the hinge side of the door. (35-1/2”to the wall.)If the compartment has an end opening door (facing the water closet), a minimum 60” wide x 48”deep clear floorspace is provided in front of the water closet. (36-1/2” wide x 30” deep.)60” minimum width of stall. (36-1/2” wide.)18” betwen centerline of water closet and side wall or partition. (19-1/2”.)32” minimum from side of water closet to opposite wall or partition.87


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue42” minimum from centerline of water closet to opposite wall or partition. (17”.)The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toiletseat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high). (16” high.)Recommendation:Requires engineering/architectural evaluation.Provide major renovation (including moving plumbing locations and walls).Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-57-1 (originally 86-400)88


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-57-2 (originally 87-400)89


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue58. Toilet Grab Bars - South Men’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:1-1/4” to 1-1/2” diameter of bars. (None.)Side bar has 42” min. length. (None.)Back bar has 36” min. length. (None.)Recommendation:Replace/Install grab bar.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-58-1 (originally 87-400)90


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue59. Lavatories - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into thisspace).Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.18” minimum from center of fixture to side wall or partition.29” min. clearance from bottom of apron to floor surface.27” high x 8” deep knee clearance under front lip.30” wide x 9” high x 17” deep clearance from front of lavatory.There are no sharp or abrasive elements under lavatory.Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.5 lb. max. force required to operate controls.Areas not meeting new construction standards:34” max. height to rim or counter above floor surface. (35”.)Drain and piping is insulated or configured to prevent contact. (No insulation.)Recommendation:Raise/Lower existing lavatory.Insulate pipes under lavatory (or sink when applicable).91


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-59-1 (originally 88-400)92


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue60. Urinals - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:14” minimum projection and 17” maximum projection from the wall.5 lb max. pressure to operate valve.Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adverselyaffected by moisture.Areas not meeting new construction standards:A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.(28” x 48”.)17” maximum urinal rim height above the finished floor. (19”.)44” maximum height to flush valve above finished floor. (46”.)Recommendation:Replace/Install urinal.Widen partitions around urinal.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-60-1 (originally 89-400)93


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue61. Alcoves - South Men’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:See Sequence #60 for recommendations.Areas noted in compliance:One full unobstructed side of clear floor space adjoins accessible route.Areas not meeting new construction standards:36” x 48” clear floor space for front access alcoves greater than 24” depth. (28” wide.)Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-61-1 (originally 89-400)94


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue62. Accessories - South Men’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:Accessories do not require tight grasping, pinching or twisting of the wrist to operate.A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.A maximum of 5 lbs. force is required to operate mechanisms.Areas not meeting new construction standards:40” maximum height to bottom of reflective surface of mirror. (51”.)40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins,waste recepatacles, etc.). (Paper towel dispenser - 56” / soap dispenser - 42”.)Recommendation:Install new accessible mirror.Relocate the paper towel dispenser / hand dryer.Relocate the soap dispenser.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-62-1 (originally 90-400)95


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-62-2 (originally 91-400)96


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue63. Electrical Controls & Receptacles/Fire Alarm Boxes - South Men’sRestroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the flooror working platform.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-63-1 (originally 92-400)97


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-63-2 (originally 93-400)98


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue64. Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).48” minimum clearance provided between doors in series.Areas not meeting new construction standards:32” minimum clear width of doorway. (30-1/2”.)5 lb. maximum pressure to operate interior doors. (20 lbs.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door and frame (concrete or block wall).Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-64-1 (originally 94-400)99


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-64-2 (originally 95-400)100


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue65. Clear Space at Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (7” to the wall.)Recommendation:Reverse door swing.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-65-1 (originally 96-400)101


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-65-2 (originally 97-400)102


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue66. Identification Symbols, Restrooms - Women’s Restroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Women’s - 12” diameter circle 1/4” thick. The circle symbol contrasts with the door, light on dark background or darkon light background. (Non-compliant.)Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (No sign.)Recommendation:Install door-mounted sign on single door.Install wall-mounted sign at single entrance.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-66-1 (originally 98-400)103


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue67. Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.48” minimum clearance provided between doors in series.Areas not meeting new construction standards:32” minimum clear width of doorway. (30”.)5 lb. maximum pressure to operate interior doors. (13 lbs.)Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate). (8-3/4” to grate.)Recommendation:Remove door and frame.Widen existing doorway.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-67-1 (originally 99-400)104


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-67-2 (originally 100-400)105


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue68. Clear Space at Doors - Women’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:See Sequence #67 for recommendations.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:44” min. clear space opposite direction of door swing (48” with latch and closer). (16” to the mirror counter.)Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (7” to the wall.)Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-68-1 (originally 101-400)106


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-68-2 (originally 102-400)107


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue69. Signage - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:See Sequence #67 for recommendations.Areas noted in compliance:None observed.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-69-1 (originally 103-400)108


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue70. Multiple Accommodation Toilets - Women’s Restroom on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.Memo:No accessible stall. Provide an accessible stall.Areas noted in compliance:60” min. diameter turning circle clear of objects from floor height to 27” in room.3 second min. automatic closing door.Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.Front of toilet paper dispenser is within 36” of back wall.The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toiletseat.19” minimum height to toilet paper dispenser.Toilet paper dispenser provides continuous flow.Areas not meeting new construction standards:44” min. clear path provided throughout facility. (33-1/2”.)Door has loop or U-shaped handle immediately below latch on both inside and outside of door. (None.)32” minimum opening at end. (22-1/4”.)The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.(32” deep.)The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.(3-1/2” wide x 32” deep.)The clear floor area on the push side of the door is a minimum 48” deep., measured perpendicular to the door in itsclosed position, and 54” wide, measured from the strike edge of the door frame past the hinge side of the door. (33-1/2”deep to wall.)If the compartment has an end opening door (facing the water closet), a minimum 60” wide x 48”deep clear floorspace is provided in front of the water closet. (36-1/2” wide x 32” deep.)60” minimum width of stall. (36-1/2”.)18” betwen centerline of water closet and side wall or partition. (12”.)32” minimum from side of water closet to opposite wall or partition.42” minimum from centerline of water closet to opposite wall or partition.The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet109


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenueseat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high). (16-3/4”.)Flush valve is on wide side of the water closet. (Wrong side.)Recommendation:Requires engineering/architectural evaluation.Provide major renovation (including moving plumbing locations and walls).Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-70-1 (originally 104-400)110


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-70-2 (originally 105-400)111


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue71. Toilet Grab Bars - Women’s Restroom on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:1-1/4” to 1-1/2” diameter of bars. (No grab bars.)Side bar has 42” min. length. (No grab bars.)Back bar has 36” min. length. (No grab bars.)Recommendation:Replace/Install grab bar.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-71-1 (originally 105-400)112


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue72. Lavatories - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into thisspace).18” minimum from center of fixture to side wall or partition.34” max. height to rim or counter above floor surface.30” wide x 9” high x 17” deep clearance from front of lavatory.There are no sharp or abrasive elements under lavatory.Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.5 lb. max. force required to operate controls.Areas not meeting new construction standards:Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route. (Nonaccessibleroute.)29” min. clearance from bottom of apron to floor surface. (28”.)27” high x 8” deep knee clearance under front lip. (24”.)Drain and piping is insulated or configured to prevent contact. (No insulation.)Recommendation:Replace/Install accessible lavatory.Insulate pipes under lavatory (or sink when applicable).113


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-72-1 (originally 106-400)114


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue73. Accessories - Women’s Restroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Accessories do not require tight grasping, pinching or twisting of the wrist to operate.A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.A maximum of 5 lbs. force is required to operate mechanisms.Areas not meeting new construction standards:40” maximum height to bottom of reflective surface of mirror. (48”.)40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins,waste recepatacles, etc.). (Paper towel dispenser - 49”.)Recommendation:Relocate mirror.Relocate the paper towel dispenser / hand dryer.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-73-1 (originally 107-400)115


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-73-2 (originally 108-400)116


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue74. Electrical Controls & Receptacles/Fire Alarm Boxes - Women’sRestroom on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-74-1 (originally 109-400)117


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue75. Water Fountains (Drinking) - At 2nd Floor of <strong>Life</strong> <strong>Science</strong>sPsychology Corridor.Memo:Areas noted in compliance:18” minimum depth of fountain.9” high x 17” deep toe clearance.Lever or push bar control is located 6” max. from front edge.Bubbler outlet is 6” maximum from front.Bubbler outlet is 36” maximum from floor.The force required to activate controls does not exceed 5lbf.Areas not meeting new construction standards:32” minimum wide and 18” minimum deep alcove provided. (None.)27” high x 8” deep clear knee space under fountain. (16” high.)Stream of bubbler is parallel to front edge. (Diagonal.)4” minimum height of stream.Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficultybending or stooping. (Single fountain.)Recommendation:Install new single drinking fountain.Install cane-detectable barrier around fountain.Install paper cup dispenser at existing fountain.118


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-75-1 (originally 110-400)119


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue76. Signage - At 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology Corridor.Memo:Directional signage is at elevator.Areas noted in compliance:Directional and Informational Signage: Letters and numbers on signs have a 3:5 to 1:1 width to height ratio.Letters and numbers on signs have a stroke width-to-height ratio between 1:5 and 1:10.Signage that is suspended or projected overhead have characters and/or numbers that are a minimum of 3” in height.Characters and background of sign(s) is eggshell, matte or other non-glare finish.Characters contrast with their background (light characters on a dark background, or dark characters on a light background).Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-76-1 (originally 111-400)120


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue77. Protruding Objects - 2nd Floor <strong>Life</strong> <strong>Science</strong>s Next to the Elevator.Memo:One emergency phone.Areas noted in compliance:None observed.Areas not meeting new construction standards:Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passagewaysor aisles if lower edge of object is above 27” and below 80”. (6” projection at 37” high.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-77-1 (originally 112-400)121


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue78. Doors - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate exterior doors. (13 - 14 lbs.)3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2 seconds.)The international symbol of accessibility is posted at all primary entrances. (No sign.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Provide a sign/decal displaying the international symbol of accessibility.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-78-1 (originally 113-400)122


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-78-2 (originally 114-400)123


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue79. Clear Space at Doors - Southeast Entrance on the 2nd Floor of <strong>Life</strong><strong>Science</strong>.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 24” exterior doors.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-79-1 (originally 115-400)124


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-79-2 (originally 116-400)125


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue80. Signage - Southeast Entrance on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (Nosign.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-80-1 (originally 117-400)126


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-80-2 (originally 118-400)127


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue81. Hazards - Clock at the East Corridor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Any obstrution that overhangs a pedestrian way is a minimum 80” above the walking surface (measured from the bottomof the obstruction). (79”.)If vertical clearance of an area adjoining an accessible route is reduced to less than 80”, a barrier to warn blind orvisually impaired persons is provided. (No barrier.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-81-1 (originally 119-400)128


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue82. Corridors - West Corridor Running North to South on the 2nd Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:44” minimum width for occupant loads of 10 or more.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-82-1 (originally 120-400)129


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue83. Hazards - West Corridor Running North to South on the 2nd Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Any obstrution that overhangs a pedestrian way is a minimum 80” above the walking surface (measured from the bottomof the obstruction). (79” high.)If vertical clearance of an area adjoining an accessible route is reduced to less than 80”, a barrier to warn blind orvisually impaired persons is provided. (No barrier.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-83-1 (originally 121-400)130


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue84. Doors - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and#2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.5 lb. maximum pressure to operate interior doors.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob (7).)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-84-1 (originally 122-400)131


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-84-2 (originally 123-400)132


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue85. Clear Space at Doors - Rooms #2400, #2405, #2410, #2415,#2420, #2425 and #2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (Furniture.)Recommendation:Relocate furniture to provide clear space.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-85-1 (originally 124-400)133


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-85-2 (originally 125-400)134


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue86. Signage - Rooms #2400, #2405, #2410, #2415, #2420, #2425 and#2430 at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (Nosigns.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-86-1 (originally 126-400)135


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue87. Doors - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (11 lbs.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-87-1 (originally 127-400)136


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-87-2 (originally 128-400)137


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue88. Clear Space at Doors - Room #2418 on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:44” min. clear space opposite direction of door swing (48” with latch and closer). (30” to table.)Recommendation:Relocate furniture to provide clear space.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-88-1 (originally 129-400)138


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-88-2 (originally 130-400)139


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue89. Signage - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (Nosign.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-89-1 (originally 131-400)140


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue90. Seating, Tables and Work Surfaces - Room #2418 on the 2nd Floorof <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:22 total seats.Areas noted in compliance:One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.28” - 34” height of table or work surface that is 36” wide.Areas not meeting new construction standards:30” x 48” min. clear floor space is provided. (30” x 40”.)27” high, 30” wide and 19” deep knee clearance provided. (23-1/4” high - 25” high.)Recommendation:Provide accessible table.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-90-1 (originally 132-400)141


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue91. Aisles - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Relocate the fixed tables to provide clear space.Areas noted in compliance:None observed.Areas not meeting new construction standards:36” minimum width of aisles. (18” - 41”.)Recommendation:Relocate furniture to provide clear space.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-91-1 (originally 133-400)142


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-91-2 (originally 134-400)143


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue92. Controls, Operating Mechanisms & Vending Machines. - Room#2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Projector controls.Areas noted in compliance:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate.Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface.Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.Forward reach over obstruction: Depth of obstruction is not more than 25”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-92-1 (originally 135-400)144


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue93. Controls, Operating Mechanisms & Vending Machines. - Room#2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:One phone. Relocate the telephone. Relocate the fixed table to provide clear space.Areas noted in compliance:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate.Side Reach to Objects: Highest operable part of the object is a maximum of 54” above the floor surface.Side Reach to Objects: Lowest operable part of the object is a minimum of 9” above the floor surface.Side Reach Over Obstructions: Maximum depth of obstruction is 24”.Side Reach Over Obstructions: Lowest operable part of object is a minimum of 9” above the floor surface.Areas not meeting new construction standards:Side Reach to Objects: Minimum 30” x 48” clear floor space for side approach is provided at the object.Side Reach to Objects: Clear floor space begins a maximum of 10” from the wall/surface the object is mounted on.Side Reach Over Obstructions: The maximum height of the obstruction is 34” from the floor surface. (44”.)Recommendation:Install accessible counter.Relocate furniture to provide clear space.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-93-1 (originally 136-400)145


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue94. Sinks - Room #2418 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Required clear space adjoins or overlaps an accessible route.Sink is a maximum of 6-1/2” deep.Areas not meeting new construction standards:Minimum 30” x 48” clear space is provided in front of sink that allows forward approach. (30” x 38” to the table.)34” maximum height of rim or counter above floor surfaces. (37-1/2”.)Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath thesink. (None.)Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow). (Knob.)Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist. (Tight graspingand twisting.)5 lb. maximum force required to activate controls.Recommendation:Replace/Install accessible sink.Cut the paneling under the lavatory/sink counter to comply with knee clearance.Insulate pipes under lavatory (or sink when applicable).146


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-94-1 (originally 137-400)147


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue95. Doors - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.5 lb. maximum pressure to operate interior doors.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-95-1 (originally 138-400)148


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue96. Clear Space at Doors - Room #2445 on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (6” to the wall.)Recommendation:Reverse door swing.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-96-1 (originally 139-400)149


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue97. Signage - Room #2445 on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (Nosign.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-97-1 (originally 140-400)150


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue98. Doors - Rooms #2505, #2510, #2515, #2520, #2525, #2530 and#2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.5 lb. maximum pressure to operate interior doors.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob (7).)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-98-1 (originally 141-400)151


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-98-2 (originally 142-400)152


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue99. Clear Space at Doors - Rooms #2505, #2510, #2515, #2520,#2525, #2530 and #2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-99-1 (originally 143-400)153


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-99-2 (originally 144-400)154


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue100. Signage - Rooms #2505, #2510, #2515, #2520, #2525, #2530and #2535 at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (Nosigns.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-100-1 (originally 145-400)155


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue101. Doors - Rooms #2600, #2605, #2610, #2615, #2620, #2625,#2630, #2635 and #2640 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.5 lb. maximum pressure to operate interior doors.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knobs.)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-101-1 (originally 146-400)156


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-101-2 (originally 147-400)157


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue102. Clear Space at Doors - Rooms #2600, #2605, #2610, #2615,#2620, #2625, #2630, #2635 and #2640 on the 2nd Floor at <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-102-1 (originally 148-400)158


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-102-2 (originally 149-400)159


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue103. Signage - Rooms #2600, #2605, #2610, #2615, #2620, #2625,#2630, #2635 and #2640 on the 2nd Floor at <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-103-1 (originally 150-400)160


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue104. Doors - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong><strong>Science</strong>s.Memo:Two sets of double doors swinging in both directions.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (15 - 20 lbs.)3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2 seconds.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-104-1 (originally 151-400)161


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-104-2 (originally 152-400)162


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue105. Clear Space at Doors - BNN Administrative Offices on the 2nd Floorat <strong>Life</strong> <strong>Science</strong>s.Memo:Two sets of double doors swinging in both directions.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-105-1 (originally 153-400)163


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-105-2 (originally 154-400)164


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue106. Signage - BNN Administrative Offices on the 2nd Floor at <strong>Life</strong><strong>Science</strong>s.Memo:Two sets of double doors.Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-106-1 (originally 155-400)165


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-106-2 (originally 156-400)166


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue107. Tactile Exit Signage - BNN Administrative Offices on the 2nd Floorat <strong>Life</strong> <strong>Science</strong>s.Memo:Two sets of double doors.Areas noted in compliance:None observed.Areas not meeting new construction standards:Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-107-1 (originally 157-400)167


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue108. Protruding Objects - Time Sheet Box West of Room #2705 on the2nd Floor at <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passagewaysor aisles if lower edge of object is above 27” and below 80”. (7” projection at 30” high.)Recommendation:Install cane detectable barrier below object.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-108-1 (originally 158-400)168


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue109. Doors - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.5 lb. maximum pressure to operate interior doors.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-109-1 (originally 159-400)169


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-109-2 (originally 160-400)170


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue110. Clear Space at Doors - Room #2705 at the West Wing on the 2ndFloor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-110-1 (originally 161-400)171


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-110-2 (originally 162-400)172


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue111. Signage - Room #2705 at the West Wing on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-111-1 (originally 163-400)173


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue112. Corridors - West Wing Corridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:44” minimum width for occupant loads of 10 or more.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-112-1 (originally 164-400)174


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue113. Electrical Controls & Receptacles/Fire Alarm Boxes - West WingCorridor on the 2nd Floor of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the floorlevel to the highest point of the activating handle or lever of the box. (62”.)Recommendation:Relocate fire alarm initiating device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-113-1 (originally 165-400)175


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue114. Visual/Audible Alarms - West Wing Corridor on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:The alarm is integrated into the building or facility alarm system.Lamp is a xenon strobe type or equivalent.The color is clear and nominal white (unfiltered) or clear filtered white light.The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.The intensity is a maximum of 75 candela.The flash rate is a minimum of 1Hz and a maximum of 3Hz.There are no places in common corridors or hallways that are more than 50’ from required signaling appliances.When provided/required, audible emergency alarms meet applicable requirements.Areas not meeting new construction standards:The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.(86”.)Recommendation:Requires engineering/architectural evaluation.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-114-1 (originally 166-400)176


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue115. Water Fountains (Drinking) - West Wing on the 2nd Floor of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:9” high x 17” deep toe clearance.Lever or push bar control is located 6” max. from front edge.Bubbler outlet is 6” maximum from front.4” minimum height of stream.The force required to activate controls does not exceed 5lbf.Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficultybending or stooping. (Cup dispenser.)Areas not meeting new construction standards:32” minimum wide and 18” minimum deep alcove provided. (None.)18” minimum depth of fountain. (13”.)27” high x 8” deep clear knee space under fountain.Bubbler outlet is 36” maximum from floor. (40”.)Stream of bubbler is parallel to front edge. (Angled.)Recommendation:Install new single drinking fountain.Install cane-detectable barrier around fountain.177


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-115-1 (originally 167-400)178


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue116. Doors - Rooms #2710, #2715, #2720, #2725, #2730, #2735,#2740, #2745, #2805 and #2840 on the 2nd Floor West Wing of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.5 lb. maximum pressure to operate interior doors.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knobs.)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-116-1 (originally 168-400)179


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-116-2 (originally 169-400)180


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue117. Clear Space at Doors - Rooms #2710, #2715, #2720, #2725,#2730, #2735, #2740, #2745, #2805 and #2840 on the 2nd Floor WestWing of <strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-117-1 (originally 170-400)181


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-117-2 (originally 171-400)182


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue118. Signage - Rooms #2710, #2715, #2720, #2725, #2730, #2735,#2740, #2745, #2805 and #2840 on the 2nd Floor West Wing of <strong>Life</strong><strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-118-1 (originally 172-400)183


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue119. Tactile Exit Signage - Stairs at the West Wing on the 2nd Floor of<strong>Life</strong> <strong>Science</strong>s.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactileexit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, asappropriate. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-119-1 (originally 173-400)184


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue120. Doors - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the 1stFloor.Memo:One set of double doors.Areas noted in compliance:Opens a min. of 90 degrees.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:1/4” maximum vertical threshold or 1/2” beveled at 1:2. (1-1/2”.)5 lb. maximum pressure to operate exterior doors. (14 - 15 lbs.)3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2.5 seconds.)The international symbol of accessibility is posted at all primary entrances. (None.)Recommendation:Replace or modify the threshold.Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Post a sign/decal displaying the ”International Symbol of Accessibility” at the primary entrance.185


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-120-1 (originally 174-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-120-2 (originally 175-400)186


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-120-3 (originally 176-400)187


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue121. Clear Space at Doors - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>sPsychology on the 1st Floor.Memo:Areas noted in compliance:60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 24” exterior doors.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:Floor or landing is level and clear (2% max. slope). (3.1%.)Recommendation:Install level exterior door landing.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-121-1 (originally 177-400)188


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-121-2 (originally 178-400)189


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue122. Signage - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychology on the1st Floor.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-122-1 (originally 179-400)190


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-122-2 (originally 180-400)191


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue123. Tactile Exit Signage - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>sPsychology on the 1st Floor.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Each grade-level exterior exit door shall be identified by a tactile sign with the word ”EXIT”. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-123-1 (originally 181-400)192


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue124. Floors and Levels - West Wing Entrance to <strong>Life</strong> <strong>Science</strong>s Psychologyon the 1st Floor.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Carpets or carpet tiles are securely attached and do not exceed 1/2” in height. (Not secured.)Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length. (Not fastened.)Recommendation:Secure loose doormat.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-124-1 (originally 182-400)193


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue125. Corridors - West Wing Main Corridor at <strong>Life</strong> <strong>Science</strong>s Psychology onthe 1st Floor.Memo:Areas noted in compliance:44” minimum width for occupant loads of 10 or more.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-125-1 (originally 183-400)194


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue126. Electrical Controls & Receptacles/Fire Alarm Boxes - West WingMain Corridor at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:The height of the manual fire alarm box is a minimum of 42” and a maximum of 48”, measured vertically, from the floorlevel to the highest point of the activating handle or lever of the box. (62”.)Recommendation:Relocate fire alarm initiating device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-126-1 (originally 184-400)195


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue128. Controls, Operating Mechanisms & Vending Machines. - West WingCorridor at <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Memo:One telephone. Lower the telephone.Areas noted in compliance:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate.Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.Areas not meeting new construction standards:Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (68”.)Recommendation:Lower the house phone.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-128-1 (originally 186-400)197


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue129. Protruding Objects - West Wing at <strong>Life</strong> <strong>Science</strong>s Psychology on the1st Floor.Memo:Eye wash.Areas noted in compliance:Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passagewaysor aisles if lower edge of object is above 27” and below 80”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-129-1 (originally 187)198


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue130. Controls, Operating Mechanisms & Vending Machines. - West Wingat <strong>Life</strong> <strong>Science</strong>s Psychology on the 1st Floor.Memo:Safety shower. Lower the lever.Areas noted in compliance:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate.Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.Areas not meeting new construction standards:Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (68”.)Recommendation:Contact the provider to install a compliant machine.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-130-1 (originally 188-400)199


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue131. Water Fountains (Drinking) - West Wing at <strong>Life</strong> <strong>Science</strong>sPsychology on the 1st Floor.Memo:Areas noted in compliance:Lever or push bar control is located 6” max. from front edge.Bubbler outlet is 6” maximum from front.Stream of bubbler is parallel to front edge.4” minimum height of stream.The force required to activate controls does not exceed 5lbf.Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficultybending or stooping. (Cup dispenser.)Areas not meeting new construction standards:32” minimum wide and 18” minimum deep alcove provided. (None.)18” minimum depth of fountain. (15”.)27” high x 8” deep clear knee space under fountain. (0”.)9” high x 17” deep toe clearance. (0”.)Bubbler outlet is 36” maximum from floor. (38”.)Recommendation:Install new single drinking fountain.Install cane-detectable barrier around fountain.200


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-131-1 (originally 189-400)201


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue132. Doors - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Door hardware is operable with a single effort (lever type, panic bar or push pull type).Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (15 lbs.)3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch. (2 seconds.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-132-1 (originally 190-400)202


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-132-2 (originally 191-400)203


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue133. Clear Space at Doors - West Wing Exit Door to Stairwell on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-133-1 (originally 192-400)204


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-133-2 (originally 193-400)205


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue134. Signage - West Wing Exit Door to Stairwell on the 1st Floor of <strong>Life</strong><strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-134-1 (originally 194-400)206


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue135. Tactile Exit Signage - West Wing Exit Doors to Stairwell on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp is identified by a tactileexit sign that states ”EXIT STAIR DOWN”, ”EXIT RAMP DOWN”, ”EXIT STAIR UP”, or ”EXIT RAMP UP”, asappropriate. (None.)Recommendation:Provide compliant sign.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-135-1 (originally 195-400)207


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue136. Doors - Women’s Restroom #1517 at the West Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #137 for additional recommendation.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:32” minimum clear width of doorway. (24”.)5 lb. maximum pressure to operate interior doors. (21 lbs.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Replace door hardware with compliant hardware.Replace door and frame (concrete or block wall).Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-136-1 (originally 196-400)208


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-136-2 (originally 197-400)209


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue137. Clear Space at Doors - Women’s Restroom #1517 at the West Wingon the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (2-1/2” to the wall.)Recommendation:Install automatic door opening device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-137-1 (originally 198-400)210


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-137-2 (originally 199-400)211


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue138. Identification Symbols, Restrooms - Women’s Restroom #1517 atthe West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Women’s - 12” diameter circle 1/4” thick. The circle symbol contrasts with the door, light on dark background or darkon light background. (Non-compliant.)Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (None.)Recommendation:Install door-mounted sign on single door.Install wall-mounted sign at single entrance.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-138-1 (originally 200-400)212


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue139. Multiple Accommodation Toilets - Women’s Restroom #1517 at theWest Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:No accessible stall. Provide an accessible stall.Areas noted in compliance:44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.Front of toilet paper dispenser is within 36” of back wall.19” minimum height to toilet paper dispenser.Toilet paper dispenser provides continuous flow.Areas not meeting new construction standards:60” min. diameter turning circle clear of objects from floor height to 27” in room. (37-1/2”.)44” min. clear path provided throughout facility. (34” - 37-1/2”.)3 second min. automatic closing door.Door has loop or U-shaped handle immediately below latch on both inside and outside of door.34” minimum opening at side.The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicularto the door in its closed position.If the compartment has an inward swinging, side opening door and contains a floor mounted water closet, the clearancearound the water closet is a minimum of 60” wide and and a minimum 59” deep that is clear of the stall door swing.60” minimum width of stall.18” betwen centerline of water closet and side wall or partition.32” minimum from side of water closet to opposite wall or partition.42” minimum from centerline of water closet to opposite wall or partition.The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toiletseat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toiletseat. (Above proposed bar.)Recommendation:Requires engineering/architectural evaluation.213


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenueProvide major renovation (including moving plumbing locations and walls).Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-139-1 (originally 201-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-139-2 (originally 202-400)214


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-139-3 (originally 203-400)215


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue140. Toilet Grab Bars - Women’s Restroom #1517 at the West Wing onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:1-1/4” to 1-1/2” diameter of bars. (No grab bar.)Side bar has 42” min. length. (No grab bar.)Back bar has 36” min. length. (No grab bar.)Recommendation:Replace/Install grab bar.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-140-1 (originally 203-400)216


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue141. Lavatories - Women’s Restroom #1517 at the West Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into thisspace).18” minimum from center of fixture to side wall or partition.34” max. height to rim or counter above floor surface.30” wide x 9” high x 17” deep clearance from front of lavatory.There are no sharp or abrasive elements under lavatory.Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.5 lb. max. force required to operate controls.Areas not meeting new construction standards:Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route. (Nonaccessibleroute.)29” min. clearance from bottom of apron to floor surface. (27-1/2”.)27” high x 8” deep knee clearance under front lip. (23”.)Drain and piping is insulated or configured to prevent contact. (None.)Recommendation:Replace/Install accessible lavatory.Insulate pipes under lavatory (or sink when applicable).217


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-141-1 (originally 204-400)218


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue142. Accessories - Women’s Restroom #1517 at the West Wing on the1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #139 for additional recommendations.Areas noted in compliance:Accessories do not require tight grasping, pinching or twisting of the wrist to operate.A maximum of 5 lbs. force is required to operate mechanisms.Areas not meeting new construction standards:40” maximum height to bottom of reflective surface of mirror. (48”.)40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins,waste recepatacles, etc.). (Paper towel dispenser - 49”.)A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.(Not enough clear space.)Recommendation:Relocate mirror.Relocate the paper towel dispenser / hand dryer.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-142-1 (originally 205-400)219


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue143. Electrical Controls & Receptacles/Fire Alarm Boxes - Women’sRestroom #1517 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the flooror working platform.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-143-1 (originally 206-400)220


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-143-2 (originally 207-400)221


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue144. Doors - Men’s Restroom #1522 at the West Wing on the 1st Floorof <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:32” minimum clear width of doorway. (29”.)5 lb. maximum pressure to operate interior doors. (19.5 lbs.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware.Replace door and frame (concrete or block wall).222


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-144-1 (originally 208-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-144-2 (originally 209-400)223


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue145. Clear Space at Doors - Men’s Restroom #1522 at the West Wingon the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #147 for additional recommendations.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:60” min. clear space in direction of door swing. (36”.)Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Recommendation:Requires engineering/architectural evaluation.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-145-1 (originally 210-400)224


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-145-2 (originally 211-400)225


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue146. Identification Symbols, Restrooms - Men’s Restroom #1522 at theWest Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Door mounted signage: Men’s - Equilateral triangle with 12” sides, 1/4” thick with the vertex pointing up. The trianglesymbol contrasts with the door, light on dark background or dark on light background. (Non-compliant.)Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (None.)Recommendation:Install door-mounted sign on single door.Install wall-mounted sign at single entrance.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-146-1 (originally 212-400)226


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue147. Multiple Accommodation Toilets - Men’s Restroom #1522 at theWest Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Provide a compliant restroom.Areas noted in compliance:Front of toilet paper dispenser is within 36” of back wall.19” minimum height to toilet paper dispenser.Toilet paper dispenser provides continuous flow.Areas not meeting new construction standards:60” min. diameter turning circle clear of objects from floor height to 27” in room. (35-3/4”.)44” min. clear path provided throughout facility. (30” - 35-3/4”.)3 second min. automatic closing door.Door has loop or U-shaped handle immediately below latch on both inside and outside of door.34” minimum opening at side.60” minimum width of stall.18” betwen centerline of water closet and side wall or partition.32” minimum from side of water closet to opposite wall or partition.42” minimum from centerline of water closet to opposite wall or partition.The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toiletseat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toiletseat. (Over proposed bar.)Recommendation:Requires engineering/architectural evaluation.Provide major renovation (including moving plumbing locations and walls).227


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-147-1 (originally 213-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-147-2 (originally 214-400)228


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-147-3 (originally 215-400)229


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue148. Toilet Grab Bars - Men’s Restroom #1522 at the West Wing on the1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:1-1/4” to 1-1/2” diameter of bars. (None.)Side bar has 42” min. length. (None.)Back bar has 36” min. length. (None.)Recommendation:Replace/Install grab bar.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-148-1 (originally 215-400)230


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue149. Lavatories - Men’s Restroom #1522 at the West Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #147 for additional recommendations.Areas noted in compliance:30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into thisspace).34” max. height to rim or counter above floor surface.30” wide x 9” high x 17” deep clearance from front of lavatory.There are no sharp or abrasive elements under lavatory.Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.5 lb. max. force required to operate controls.Areas not meeting new construction standards:Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route. (Nonaccessibleroute.)18” minimum from center of fixture to side wall or partition. (13-1/2”.)29” min. clearance from bottom of apron to floor surface. (27-1/2”.)27” high x 8” deep knee clearance under front lip. (23”.)Drain and piping is insulated or configured to prevent contact. (None.)Recommendation:Replace/Install accessible lavatory.Insulate pipes under lavatory (or sink when applicable).231


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-149-1 (originally 216-400)232


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue150. Urinals - Men’s Restroom #1522 at the West Wing on the 1st Floorof <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:44” maximum height to flush valve above finished floor.5 lb max. pressure to operate valve.Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adverselyaffected by moisture.Areas not meeting new construction standards:A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.(25-3/4” wide.)17” maximum urinal rim height above the finished floor. (22” high.)14” minimum projection and 17” maximum projection from the wall. (22” deep.)Recommendation:Replace/Install urinal.Widen partitions around urinal.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-150-1 (originally 217-400)233


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue151. Alcoves - Men’s Restroom #1522 at the West Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #150 for recommendations.Areas noted in compliance:None observed.Areas not meeting new construction standards:36” x 48” clear floor space for front access alcoves greater than 24” depth. (25-3/4” wide.)One full unobstructed side of clear floor space adjoins accessible route. (Non-accessible route.)Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-151-1 (originally 217-400)234


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue152. Accessories - Men’s Restroom #1522 at the West Wing on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #147 for additional recommendations.Areas noted in compliance:Accessories do not require tight grasping, pinching or twisting of the wrist to operate.A maximum of 5 lbs. force is required to operate mechanisms.Areas not meeting new construction standards:40” maximum height to bottom of reflective surface of mirror. (48-1/2”.)40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins,waste recepatacles, etc.). (Paper towel dispenser - 48”.)A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.(No minimum clearance.)Recommendation:Relocate mirror.Relocate the paper towel dispenser / hand dryer.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-152-1 (originally 218-400)235


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue153. Electrical Controls & Receptacles/Fire Alarm Boxes - Men’sRestroom #1522 at the West Wing on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:The center of electrical receptacles or controls, and switches to control lighting, heating, cooling & appliances are 48”max. above the floor or working platform.The center of electrical outlets intended to be used by the room occupant are located a min. of 15” above the flooror working platform.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-153-1 (originally 219-400)236


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-153-2 (originally 220-400)237


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue154. Doors - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:See Sequence #155 for additional recommendation.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (12 lbs.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-154-1 (originally 221-400)238


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-154-2 (originally 222-400)239


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue155. Clear Space at Doors - West Wing Room #1521 on the 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:See Sequence #157 for additional recommendations.Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:44” min. clear space opposite direction of door swing (48” with latch and closer). (37” to the fixed table.)Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (4” to the wall.)Recommendation:Install automatic door opening device.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-155-1 (originally 223-400)240


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-155-2 (originally 224-400)241


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue156. Signage - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-156-1 (originally 225-400)242


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue157. Seating, Tables and Work Surfaces - West Wing Room #1521 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.27” high, 30” wide and 19” deep knee clearance provided.Areas not meeting new construction standards:30” x 48” min. clear floor space is provided. (37”.)28” - 34” height of table or work surface that is 36” wide. (37” high.)Recommendation:Install accessible counter.Move built-in counter to provide adequate clear space.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-157-1 (originally 226-400)243


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue158. Sales and Service Counters - West Wing Room #1521 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:A minimum 30” x 48” clear floor space is provided at the counter and;One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.Areas not meeting new construction standards:A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (37”.)Recommendation:Install accessible counter.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-158-1 (originally 227-400)244


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-158-2 (originally 228-400)245


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue159. Sinks - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Required clear space adjoins or overlaps an accessible route.5 lb. maximum force required to activate controls.Areas not meeting new construction standards:Minimum 30” x 48” clear space is provided in front of sink that allows forward approach. (Space is not provided.)34” maximum height of rim or counter above floor surfaces. (37”.)Sink is a maximum of 6-1/2” deep. (10”.)Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath thesink. (0”.)Drain and hot water piping is insulated or configured to prevent contact. (None.)Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist. (Tight graspingand twisting.)Recommendation:Replace/Install accessible sink.Cut the paneling under the lavatory/sink counter to comply with knee clearance.Insulate pipes under lavatory (or sink when applicable).246


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-159-1 (originally 229-400)247


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue160. Aisles - West Wing Room #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:36” minimum width of aisles.Recommendation:Clear aisle width(s) to comply with minimum required aisle width(s) listed above.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-160-1 (originally 230-400)248


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-160-2 (originally 231-400)249


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue161. Seating, Tables and Work Surfaces - West Wing Room #1521 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:One fume hood. Highest control is at 63” high.Areas noted in compliance:30” x 48” min. clear floor space is provided.One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floorspace.Areas not meeting new construction standards:27” high, 30” wide and 19” deep knee clearance provided. (0” deep.)28” - 34” height of table or work surface that is 36” wide. (37” high.)Recommendation:Replace the fume hood with an accessible fume hood workstation.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-161-1 (originally 232-400)250


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue162. Controls, Operating Mechanisms & Vending Machines. - West WingRoom #1521 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Various controls. Lower the glass.Areas noted in compliance:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate.Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.Forward reach over obstruction: Depth of obstruction is not more than 25”.Side Reach to Objects: Minimum 30” x 48” clear floor space for side approach is provided at the object.Side Reach to Objects: Clear floor space begins a maximum of 10” from the wall/surface the object is mounted on.Side Reach to Objects: Lowest operable part of the object is a minimum of 9” above the floor surface.Areas not meeting new construction standards:Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (54”.)Side Reach to Objects: Highest operable part of the object is a maximum of 54” above the floor surface. (58”.)Recommendation:Contact the provider to install a compliant machine.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-162-1 (originally 233-400)251


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-162-2 (originally 234-400)252


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue163. Doors - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:No closer on door.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-163-1 (originally 235-400)253


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-163-2 (originally 236-400)254


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue164. Clear Space at Doors - West Wing Room #1523 on the 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-164-1 (originally 237-400)255


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-164-2 (originally 238-400)256


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue165. Signage - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At doubleleaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably onthe right. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-165-1 (originally 239-400)257


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue166. Sales and Service Counters - West Wing Room #1523 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:A minimum 30” x 48” clear floor space is provided at the counter and;One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and;Areas not meeting new construction standards:A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (37-1/4” high.)Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and; (37-1/4” high.)Recommendation:Lower 36” wide counter section or provide an auxiliary counter with a maximum height of 34”.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-166-1 (originally 240-400)258


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue167. Sinks - West Wing Room #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Required clear space adjoins or overlaps an accessible route.5 lb. maximum force required to activate controls.Areas not meeting new construction standards:Minimum 30” x 48” clear space is provided in front of sink that allows forward approach. (Space of provided.)34” maximum height of rim or counter above floor surfaces. (37-1/4” high.)Sink is a maximum of 6-1/2” deep. (9-1/2” deep.)Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath thesink. (None.)Drain and hot water piping is insulated or configured to prevent contact.Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow). (Knob.)Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.grasping and twisting.)(RequiresRecommendation:Replace/Install accessible sink.Cut the paneling under the lavatory/sink counter to comply with knee clearance.Insulate pipes under lavatory (or sink when applicable).259


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-167-1 (originally 241-400)260


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue168. Seating, Tables and Work Surfaces - West Wing Room #1523 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Work table.Areas noted in compliance:One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.28” - 34” height of table or work surface that is 36” wide.Areas not meeting new construction standards:30” x 48” min. clear floor space is provided.27” high, 30” wide and 19” deep knee clearance provided. (25” high.)Recommendation:Provide accessible table.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-168-1 (originally 242-400)261


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue169. Controls, Operating Mechanisms & Vending Machines. - West WingRoom #1523 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Various controls throughout the lab. Lower the shower lever. Provide accessible outlets and spigots.Areas noted in compliance:Side Reach to Objects: Minimum 30” x 48” clear floor space for side approach is provided at the object.Side Reach to Objects: Clear floor space begins a maximum of 10” from the wall/surface the object is mounted on.Side Reach to Objects: Lowest operable part of the object is a minimum of 9” above the floor surface.Side Reach Over Obstructions: Lowest operable part of object is a minimum of 9” above the floor surface.Areas not meeting new construction standards:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate. (Two machines with knobs.)Side Reach to Objects: Highest operable part of the object is a maximum of 54” above the floor surface. (72” high.)Side Reach Over Obstructions: The maximum height of the obstruction is 34” from the floor surface. (37-1/4”.)Side Reach Over Obstructions: Maximum depth of obstruction is 24”. (29-3/4”.)Recommendation:Contact the provider to install a compliant machine.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-169-1 (originally 243-400)262


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-169-2 (originally 244-400)263


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue170. Doors - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.32” minimum clear width of doorway.Hardware is 30” to 44” above floor.3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:5 lb. maximum pressure to operate interior doors. (15 lbs.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Adjust door for opening pressure/closing times unless accepted by DSA / Fire <strong>Life</strong> Safety.Replace door hardware with compliant hardware.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-170-1 (originally 245-400)264


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-170-2 (originally 246-400)265


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue171. Clear Space at Doors - West Wing Room #1529 on the 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-171-1 (originally 247-400)266


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-171-2 (originally 248-400)267


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue172. Signage - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Signage for Permanent Rooms and Spaces: Letters are 1/32” raised, uppercase or sans serif w/ Grade II Braille. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-172-1 (originally 249-400)268


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue173. Sales and Service Counters - West Wing Room #1529 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:A minimum 30” x 48” clear floor space is provided at the counter and;One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.Areas not meeting new construction standards:A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (37”.)Recommendation:Lower 36” wide counter section or provide an auxiliary counter with a maximum height of 34”.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-173-1 (originally 250-400)269


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue174. Sinks - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.Required clear space adjoins or overlaps an accessible route.5 lb. maximum force required to activate controls.Areas not meeting new construction standards:34” maximum height of rim or counter above floor surfaces. (37”.)Sink is a maximum of 6-1/2” deep. (9”.)Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath thesink. (0”.)Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.tight grasping and twisting.)(RequiresRecommendation:Replace/Install accessible sink.Cut the paneling under the lavatory/sink counter to comply with knee clearance.Insulate pipes under lavatory (or sink when applicable).270


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-174-1 (originally 251-400)271


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue175. Seating, Tables and Work Surfaces - West Wing Room #1529 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Work stations.Areas noted in compliance:One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.28” - 34” height of table or work surface that is 36” wide.Areas not meeting new construction standards:30” x 48” min. clear floor space is provided.27” high, 30” wide and 19” deep knee clearance provided. (24-1/2” - 25” high x 26” wide.)Recommendation:Provide accessible table.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-175-1 (originally 252-400)272


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue176. Seating, Tables and Work Surfaces - West Wing Room #1529 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Table at entrance.Areas noted in compliance:30” x 48” min. clear floor space is provided.One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.28” - 34” height of table or work surface that is 36” wide.Areas not meeting new construction standards:27” high, 30” wide and 19” deep knee clearance provided. (26-3/4” high x 29-1/2” wide.)Recommendation:Provide accessible table.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-176-1 (originally 253-400)273


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue177. Aisles - West Wing Room #1529 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:36” minimum width of aisles. (37”.)Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-177-1 (originally 254-400)274


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue178. Doors - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Door has no closer.Areas noted in compliance:Opens a min. of 90 degrees.1/4” maximum vertical threshold or 1/2” beveled at 1:2.Hardware is 30” to 44” above floor.Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to beopened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).Areas not meeting new construction standards:32” minimum clear width of doorway. (28”.)Door hardware is operable with a single effort (lever type, panic bar or push pull type). (Knob.)Recommendation:Replace door hardware with compliant hardware.Replace door and frame (concrete or block wall).Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-178-1 (originally 255-400)275


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-178-2 (originally 256-400)276


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue179. Clear Space at Doors - West Wing Room #1535 on the 1st Floor of<strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:Floor or landing is level and clear (2% max. slope).60” min. clear space in direction of door swing.44” min. clear space opposite direction of door swing (48” with latch and closer).Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.Minimum strike side clearance on PUSH side of door: 0”.Areas not meeting new construction standards:None observed.Recommendation:None.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-179-1 (originally 257-400)277


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-179-2 (originally 258-400)278


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue180. Signage - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:None observed.Areas not meeting new construction standards:Permanent I.D. signs, when provided, are installed on the wall adjacent to the latch side of the door NOTE: At doubleleaf doors, and when there is no room on the latch side, signs shall be placed on the nearest adjacent wall, preferably onthe right. (None.)Recommendation:Install permanent ID sign to latch side of door.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-180-1 (originally 259-400)279


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue181. Sales and Service Counters - West Wing Room #1535 on the 1stFloor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Areas noted in compliance:A minimum 30” x 48” clear floor space is provided at the counter and;One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and;Areas not meeting new construction standards:A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (36-3/4”.)Knee space at table(s) is at least 27” high, 30” wide and extends 19” under the table(s) and; (22” wide x 36-3/4”high.)Recommendation:Install accessible counter.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-181-1 (originally 260-400)280


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue182. Sinks - West Wing Room #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>sPsychology.Memo:Areas noted in compliance:Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.Required clear space adjoins or overlaps an accessible route.5 lb. maximum force required to activate controls.Areas not meeting new construction standards:34” maximum height of rim or counter above floor surfaces. (37-1/2”.)Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath thesink. (None.)Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow). (Knob.)Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.grasping and twisting.)(RequiresRecommendation:Replace/Install accessible sink.Cut the paneling under the lavatory/sink counter to comply with knee clearance.Insulate pipes under lavatory (or sink when applicable).281


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-182-1 (originally 261-400)282


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue183. Seating, Tables and Work Surfaces - West Wing Room #1535 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:One fume hood.Areas noted in compliance:30” x 48” min. clear floor space is provided.One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floorspace.Areas not meeting new construction standards:27” high, 30” wide and 19” deep knee clearance provided. (None.)28” - 34” height of table or work surface that is 36” wide. (38-1/2” high.)Recommendation:Replace the fume hood with an accessible fume hood workstation.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-183-1 (originally 262-400)283


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue184. Seating, Tables and Work Surfaces - West Wing Room #1535 onthe 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Computer desks.Areas noted in compliance:One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.28” - 34” height of table or work surface that is 36” wide.Areas not meeting new construction standards:30” x 48” min. clear floor space is provided.27” high, 30” wide and 19” deep knee clearance provided. (26-1/2” high.)Recommendation:Provide accessible table.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-184-1 (originally 263-400)284


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University Avenue185. Controls, Operating Mechanisms & Vending Machines. - West WingRoom #1535 on the 1st Floor of <strong>Life</strong> <strong>Science</strong>s Psychology.Memo:Various controls throughout the lab: outlets, spigots, paper towel dispenser, VWR machine, Millipore machine andcentrifuge. Relocate the paper towel dispenser. Relocate the Millipore machine. Relocate the outlets and spigots.Areas noted in compliance:Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.Side Reach Over Obstructions: Lowest operable part of object is a minimum of 9” above the floor surface.Areas not meeting new construction standards:Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do notrequire tight grasping, pinching or twisting of the wrist to operate. (Two knobs (centrifuge machine and VMR machine).)Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (71” high.)Side Reach Over Obstructions: The maximum height of the obstruction is 34” from the floor surface. (36-3/4”.)Side Reach Over Obstructions: Maximum depth of obstruction is 24”. (23-1/2” - 29-1/2”.)Recommendation:Contact the provider to install a compliant machine.Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-185-1 (originally 264-400)285


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-185-2 (originally 265-400)Photo #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-185-3 (originally 266-400)286


University of California at RiversideSite Evaluation SurveyReport: UCR P5316 <strong>Life</strong> <strong>Science</strong> Building in Riverside, CA900 University AvenuePhoto #UCR P5316 <strong>Life</strong> <strong>Science</strong> Building-185-4 (originally 267-400)287