SD-TestBus 2 v. 2.16<br />
7.6.1 Current time curve<br />
With some relays it is possible to have a graphical representation of the protection set (L, S, I and G protections).<br />
To open this window you have to push the button named “Curve current / time”.<br />
On the menu bar is made possible to print the current view, to change the current scale (Ampere or In) and to<br />
close the window.<br />
Note 1: the I1 current threshold is drawn at about 117% (IEC) or 105% (UL) of its nominal value. This is done according to<br />
the respective standards.<br />
Note 2: it is possible to change the protection set without close the window. At the end of the programming session, the window is<br />
automatically refreshed with the new parameters. If there is a communication problem or an incoherent parameter set a<br />
“?” icon is shown.<br />
7.7 Communication settings (only for PR222DS/PD and PR223EF)<br />
This page is visualized only if the device found on the bus belongs is a PR222DS/PD or PR223EF. Here is some<br />
information about the configuration of the communication unit.<br />