Coordination tablewith <strong>Legrand</strong> DPX MCCBsSL, MS, SB, MR Switch-Busbar coordination table.Contingent short circuit kA eff. (50/60 Hz - 380/415 V)SL SL - MS MS MS MR MR MR MR MR MR MR MR40A 63A 100A 160A 250A 315A 400A 500A 630A 800A 1000ADPX LEGRANDDPX 125 I cw 16kA - 40A 16 16DPX 125 I cw 25kA - 40A 25 25DPX 125 I cw 36kA - 40A 36 36DPX 125 I cw 16kA - 63A 16 16DPX 125 I cw 25kA - 63A 25 25DPX 125 I cw 36kA - 63A 36 36DPX 125 I cw 16kA - 100A 16DPX 125 I cw 25kA - 100A 25DPX 125 I cw 36kA - 100A 36DPX 160 I cw 25kA - 160A 25 25DPX 160 I cw 36kA - 160A 36 36DPX 160 I cw 50kA - 160A 50 50DPX 250ER I cw 25kA - 250A 25 25DPX 250ER I cw 36kA - 250A 36 36DPX 250ER I cw 50kA - 250A 50 50DPX 250 I cw 36kA - 250A 36 36DPX 250-H I cw 70kA - 250A 70 70DPX 250-L I cw 100kA - 250A 100 100DPX 630 I cw 36kA - 400A 36 36DPX 630-H I cw 70kA - 400A 70 70DPX 630-L I cw 100kA - 400A 100 100DPX 630 I cw 36kA - 630A 36 36DPX 630-H I cw 70kA - 630A 70 70DPX 630-L I cw 100kA - 630A 100 100DPX 1250 I cw 50kA - 800A 50 50DPX 1250-H I cw 70kA - 800A 70 70DPX 1250-L I cw 100kA - 800A 100 100DPX 1250 I cw 50kA - 1000A 50 50DPX 1250-H I cw 70kA - 1000A 70 70DPX 1250-L I cw 100kA - 1000A 100 100Note for Lexic mini circuit breakersThe Zucchini Busbar Trunking Systems, specifiedherein, are protected by Lexic MCBs up to theirbreaking capacityTECHNICAL INFORMATION 2TECHNICALINFORMATIONLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE


LOW POWERLBLIGHTING BUSWAYHLHIGH LIGHTINGSLSERIE LUCE25 - 40A25 - 40A40 - 63Apage 1page 21page 43MEDIUM POWERMSMINI SBARRAMRMEDIUM RATINGTSTROLLEY SYSTEM63 - 100 - 160A160 - 1000A63 - 250Apage 57page 73page 109TECHNICALINFORMATIONpage 127


Integrated solutionsfor global projects<strong>Legrand</strong> is the world specialist in productsand systems for electrical installationsand information networks:- Distribution, automation panels andprotection equipment- Cable management(trunking, cable trays and wire mesh)- Busbars and lighting busbarsEvery product and system needed fordistributing energy and protecting peopleand property.Altis TM industrial cabinetsAtlantic and Marina boxesCablofil cable trays


EASY TO DESIGNThe electric design of the busbars is achieved byZucchini in compliance with the product Standards.The rated current of our busbars is guaranteed ata room temperature of 40 °C (n.d.r. the Standardrequires 35 °C). After choosing the busbar whichis able to meet the operating current regulations, itwill be very easy to verify the voltage drop as wellas the protection against overcurrents by using thetechnical tables available for all our production lines.In particular, these tables define: the short circuit andpeak currents that can be supported by the busbarwaiting for the protection device located upstreamto start operating, the specific voltage drop basedon the average cos phi of the loads, the losses andother data (R, X, Rpe, etc.) which allow the planningengineer to carry out calculations with electricvalues, which are not estimated but the result ofmeasurements made during heating and short circuittests (in certified LOVAG laboratories), which havecertified all our product lines.When using busbars, the load protection is locatedvery close to the device (decentralized protection);junction boxes can contain protection devices such asthermal magnetic circuit breakers, fuse carriers andmotorized switches which allow you to easily andefficaciously manage the system.Example of an electric characteristics tableINTRINSIC SAFETYA busbar does not use large amounts of insulatingplastic material and potentially dangerous materialsin case of fire. Furthermore, the plastic materials usedfor the insulating parts of the busbars are alwaysself-extinguishing (from V0 to V2) and the gasemission is generally very low (Halogen Free).Low electromagnetic emission is another advantageof the busbars compared to that of an equivalentcable system: as a result, the metal plate casing ofthe busbars serves as a screen for the electric field(shielded enclosure); the extreme vicinity betweenthe phase conductors also reduces the emission ofthe magnetic field considerably. The tests carried outon one of our 2500A SCP busbars at full operatingcurrent has shown that the emission of the magneticfield (magnetic induction) is lower than 10 μT of theDecree at a distance of 0.3m, and lower than 3 μTat a distance of only 0.7m from the busbar. Thesefeatures make our busbars the unavoidable choicefor hospital facilities, data processing centres andwherever it is necessary to supply a large amount ofpower in the vicinity of workplaces and/or sensitiveequipment..Zucchini busbar electromagnetic emission.LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE


Basic concepts forbusbarsFLEXIBILITYBy using the outlet windows locatedon the straight elements, the busbarsprovide high management flexibility,both when planning (electricalengineer) and when installing thesystem (installer); they are also usedfor the unavoidable changes requiredby the electric system to adapt to thevaried needs of the end user. Thejunction boxes can be inserted andremoved from their windows whenthe busbar is electrically poweredand inserted in another junctionwindow, thus avoiding downtime.The engineering department in chargeof designing the busbar does not haveto know the exact position of themachinery and of the electric loadsthat will be installed in the company;the project that will be carried out willbe open to changes and variationswhich will be defined by the end userwhen operationally using the system.No more point-point connections butonly one power distribution systemto which you will always be able toconnect to wherever there is a freewindow. Because of its flexibility anddurability features Zucchini’s busbar,installed inside a building, allows youto easily change the destination ofits intended use of the rooms, thusgiving also advantages to those whomanage and locate the various partsof the building premises.Busbar systemCable and tube lighting system


QUICK INSTALLATIONZucchini’s junction and fixing systemshave been designed and created to installbusbars easily. In a cable and tray system,the time required to install only the tray isthe same used to install a complete systemin busbars. Furthermore, given the samecapacity, a power busbar, which generallyhas aluminium conductors, is much lighterthan a system made with (copper) traysand cables: lighter weights require a lowernumber of supporting frames or, in any case,more simple and inexpensive supportingframes. That is why the installation time ofa busbar is obviously shorter than a similarsystem made with cables.REDUCED DIM<strong>EN</strong>SIONSThe overall dimensions of the busbars aregenerally smaller than an equivalent systemmade with cables, especially when the currentsto be carried exceed 1000A and when severalcables in parallel are necessary to ensure suchcapacity. Other advantages can be achievedwhen there are changes of direction where theradius of curvature of the cables is minimal andenough to not damage the insulating material;busbars allow you to change directions with 90°angles, thus optimizing the small spaces used inservice areas.LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE


LB - LIGHTING BUSWAY25 - 40A


LBLIGHTING BUSWAYSECTION CONT<strong>EN</strong>TS2 General features8 Trunking components: 2 and 4 conductors elements12 Trunking components: 6 conductors elements14 Plugs17 Fixing supports19 Cable channel and accessories128 Technical information135 Determination of the operating current of a busbar1LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


LBLighting BuswayG<strong>EN</strong>ERAL FEATURESZucchini’s LB product line is the ideal solution forsupplying power to light fixtures for commercial andindustrial applications. The main features of the LBrange are:• speed, simplicity and flexibility when planning andinstalling the lines;• capable of being installed both in false ceilings andbelow floating floors, because of the IP 55 degreeof protection;• compliance with Standard IEC 60439-1 and 2;• rated at average room temperature of 40 °C for ahigher performance level compared to the 35 °Crating required by the standard.Straight elementClamping bracketTap-off plugsEnd feed unitShopping centresOffices2 LB - LIGHTING BUSWAY


LBLIGHTING BUSWAYSTRAIGHT ELEM<strong>EN</strong>TSThe components and the features of the LB straightelements are:• a closed and rib-shaped section casing, made with hotgalvanized steel (Senzimir) (due to its cross-sectionand electrical continuity, it also serves as a protectiveconductor);• casing thickness 0.6 mm;• reduced dimensions 26x41 mm;• painted or with an anodized aluminium casingversions available on request;• number of conductors: 2, 4 or 6 rigid copperconductors with a 99.9% purity;• conductor section: 3.14 mm 2 for 25A and 6.15 mm 2for 40 A;• separation between the conductors by using a V0(according to UL94) self-extinguishing insulatingplastic sheathe and in compliance with the glow-wiretest according to IEC 60695-2-10;• tap-off outlets equidistant every 1m (3 outlets every3m) or 0.5m (6 outlets every 3m), receiving thecorresponding tap-off plugs (in the LB 6 conductorversion the outlets are arranged on both sides of thebusbar: 3+3 or 6+6 outlets);• a junction block automatically ensuring electricalcontinuity.The connection between two straight elements is quick;with one operation the mechanical and the electricalconnection is ensured between two joined elements;at the same time, an IP 55 degree of protection isguaranteed without using additional accessories.The continuity of the protective conductor (casing) isguaranteed by tightening the special connection screw.The whole busbar is fire retardant in compliance withthe IEC 60332-3 standard.Store houseHospitalsG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE3


LBLighting BuswayFEED UNITSAllows you to electrically power the LB line through acable line; the installation is carried out with a quickjunction connection as with the straight elements.The feed units have terminals for the connection offlexible copper cables for sections of up to 25 mm 2 .There is an anti-pullout cable clamp inside the feedunit. The entrance point for the incoming cable ispositioned on the end of the feed unit.Standard end feed unit<strong>EN</strong>D COVERThe end cover ensures the IP 55 protection degree atthe end of the line.End coverFIXING DEVICESSpecific accessories are available for attaching thebusbar to the structure of the building (directly orwith a steel chain or cable).The accessories for overhead fixing are:• snap clamp: the snap-on installation is extremelyfast. This bracket is suitable both for overhangingthe busbar to the ceiling and for hanging productssuch as fluorescent lamps, tap-off boxes, etc., tothe busbar itself;• snap clamp with ring or hook: the ring or the hookenables to hang lamps easily.• simple bracket: used with the ceiling bracketholder, it enables the installation the busbar directlyonto the ceiling at a distance of about 25cm;• wall bracket: enables the fixing of the busbardirectly onto the wall of a building, setting it at therequired distance enabling the installation of thenecessary components.Fixing accessories for fastening the busbar run to the structureand hanging the lamps onto the busbar4 LB - LIGHTING BUSWAY


LBLighting BuswayTRUNKING ELEM<strong>EN</strong>TS AND ADDITIONALELEM<strong>EN</strong>TSDepending on the different installation requirementsZucchini can provide various technical solutions:a) flexible joint: used to make changes of direction orto avoid possible interferences that may be found onthe natural path of the BUSBAR.The features are as follows:• same connection method as the straight elements;• electrical and mechanical connection with oneoperation;• standard degree of protection: IP 55;• continuity of the protective conductor, made from thecasing of the element itself, guaranteed by tighteningthe special connection screw;b) cable trunking with cover: this accessory, whichcan be positioned in the upper part of the busbar,can be used to distribute auxiliary circuits, it is anintegral part of the busbar run using special spacersand brackets which support the busbar trunkingsystem firmly. The trunking part is 3 m long and itsdimensions are 28x28 mm;c) intermediate feed unit: it can power the busbar froman intermediate point of the line, thus reducing thevoltage drop at the end of the line and/or makingthe installation easier when the electric energysupply point is near the middle of the line.Phase selectiontap-off plugsavailableWall suspensionbracketRing for suspending a lampor for suspending otheraccessories of the busbar.(boxes, loudspeakers, etc.)Snap-on bracket:can be used bothfor suspendingthe busbar itselfand other devices(lamps, etc)PARTS OF THE LINEPhase selection plugThree-phase plug with fuse carrierSingle-phase plugs with 1, 3, 5 m cable6 LB - LIGHTING BUSWAY


LBLIGHTING BUSWAYHook for suspending alamp or for suspendingother devices (boxes,loudspeakers, etc.)Single-phase 10 Atap-off plugs with apre-wired cable andphase identificationusing colours.Right end feed unitscomplete with cable clampand terminals for 25 mm 2flexible cables.Snap-on stainless steel hook, ring andbracketSimple suspension bracketBracket for coupling elements andfloor fixingG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE7


TrunkingcomponentsCloseClose OpenOpenCloseClose OpenOpenCloseClose OpenOpen41NLN (N3)L3L2L1 (N2)26150 675 100030<strong>001</strong>000 325STRAIGHT ELEM<strong>EN</strong>TSupplied with 3 pre-installed outlet covers(one cover every other outlet on the 6 outlet model)Model Item Length Rating Conductors No. of Weight(m) (A) outlets (kg)LB 252 70150101 3 25 2 3 2.900LB 252 70150102 3 25 2 6 2.900LB 252 70150111 1.5 25 2 2 1.500LB 402 70170101 3 40 2 3 3.200LB 402 70170102 3 40 2 6 3.200LB 402 70170111 1.5 40 2 2 1.650LB 254 70160101 3 25 4 3 3.100LB 254 70160102 3 25 4 6 3.100LB 254 70160111 1.5 25 4 2 1.550LB 404 70180101 3 40 4 3 3.400LB 404 70180102 3 40 4 6 3.400LB 404 70180111 1.5 40 4 2 1.750OUTLET COVER (spare part)CloseClose OpenOpenAlready mounted on each plug point, for IP 55 protection of outlets withoutplug.Model Item Weight (kg)All 70102054 0.00437 28 LB - LIGHTING BUSWAYVersions with painted and Aluminum casing on request


LBLIGHTING BUSWAYSTANDARD FEED UNITSupplied without an electric and mechanical bayonet connection. It must beinstalled on one side of the element, located near the linking bayonet.80 60d 1= MAX. Ø 383106.56.5Max. cablesection 25 mm 2Model Item Weight (kg)LB 252 70161<strong>001</strong> 0.400LB 402 70181<strong>001</strong> 0.430LB 254 70161<strong>001</strong> 0.400LB 404 70181<strong>001</strong> 0.430For cable glands see page 136STANDARD <strong>EN</strong>D COVERTo be used with standard feed units.Model Item Weight (kg)All 70101351 0.060663535Versions with painted and Aluminum casing on requestCATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE9


Trunkingelement<strong>EN</strong>D-LINE FEED UNITd 1= MAX. Ø 3880 606.56.5MAX. cablesection 25 mm 2Supplied with an electric and mechanical bayonet connection. It must beinstalled on the extremity of the element without the bayonet.Can be used when power feed is needed at both ends of a run (less voltagedrop) or cabled in association with a standard feed unit to create a flexibleelement to bypass large obstacles (beams, air ducts, etc)Model Item Weight (kg)LB 252 70161002 0.600LB 402 70181002 0.630LB 254 70161002 0.600LB 404 70181002 0.630For cable glands see page 136150310<strong>EN</strong>D COVERTo be used with end-line feed unit.Model Item Weight (kg)All 70161352 0.20066 35195FLEXIBLE JOINTUsed to make changes of direction.260Model Item Weight (kg)LB 252 70161261 1.350LB 402 70181261 1.400LB 254 70161261 1.350LB 404 70181261 1.40080 6015088010 LB - LIGHTING BUSWAYVersions with painted and Aluminum casing on request


LBLIGHTING BUSWAYC<strong>EN</strong>TRE FEED UNIT 25/40AUsed to power a busbar straight element from any intermediate point. Thecentre feed unit is also used for reducing the voltage drop of the line.Model Item Weight (kg)All 70181151 2.1<strong>001</strong>969250809660d1 = MAX. ø48150 8169Max. cable section 35 mm 2Versions with painted and Aluminum casing on requestCATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE11


Trunkingcomponents - LB6CloseClose OpenOpenCloseClose OpenOpenCloseClose OpenOpen150 675 100030<strong>001</strong>000 325STRAIGHT ELEM<strong>EN</strong>T41NL3L2L1N1LSupplied with 3+3 pre-installed outlet covers(one cover every other outlet on the 6+6 outlet model)The outlets are positioned on both sides in alternating pattern26Model Item Length Rating Conductors No. of Weight[m] A outlets (kg)LB 256 70250101 3 25 6 3 + 3 3.100LB 256 70250102 3 25 6 6 + 6 3.100LB 256 70250111 1.5 25 6 2 + 2 1.550LB 406 70260101 3 40 6 3 + 3 3.400LB 406 70260102 3 40 6 6 + 6 3.400LB 406 70260111 1.5 40 6 2 + 2 1.750OUTLET COVER (spare part)CloseClose OpenOpenAlready mounted on each plug point, for IP 55 protection of outlets without plug.Model Item Weight (kg)All 70102054 0.00437 2STANDARD FEED UNITSupplied without an electric and mechanical bayonet connection. It mustbe installed on one side of the element, located near the linking bayonet.Removable top and bottom cover to make cable connections easier.65 107no. 2 d 1= MAX. Ø 303336.56.5MAX. cablesection 25 mm 2Model Item Weight (kg)All 70261101 0.430For cable glands see page 13612 LB - LIGHTING BUSWAYVersions with painted and Aluminum casing on request


LBLIGHTING BUSWAYSTANDARD <strong>EN</strong>D COVERTo be used with standard feed units.Model Item Weight (kg)All 70101351 0.08035<strong>EN</strong>D-LINE FEED UNITNo. 2 d 1= MAX. Ø 30Supplied with an electric and mechanical bayonet connection. It must beinstalled on the extremity of the element without the bayonet.Can be used when power feed is needed at both ends of a run (less voltagedrop) or cabled in association with a standard feed unit to create a flexibleelement to bypass large obstacles (beams, air ducts, etc) Removable top andbottom cover to make cable connections easier.150333107656.56.5MAX. cablesection 25 mm 2Model Item Weight (kg)All 70261102 0.600For cable glands see page 136<strong>EN</strong>D COVERTo be used with end-line feed unit.Model Item Weight (kg)All 70263102 0.13026065 10766 356635195FLEXIBLE JOINTUsed to make changes of direction or avoid columns, obstructions oranything located along the path of the line.Model Item Weight (kg)All 70263201 1.350150926Versions with painted and Aluminum casing on requestCATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE13


Plugs forall versionsSINGLE-PHASE PLUGS WITH CABLELB Model Item Capacity Fuse Phase Cable length Cable end Colour252 254 256402 404 4064 conductors side• • 70105016 10 A - L1-N 1m stripped grey• • 70105116 10 A - L1-N 3m stripped grey• • 70105126 10 A - L1-N 5m stripped grey• • 447 40 10 A - L1-N 1m fast connection grey• • 70105017 10 A - L2-N 1m stripped orange• • 70105117 10 A - L2-N 3m stripped orange• • 70105127 10 A - L2-N 5m stripped orange• • 447 41 10 A - L2-N 1m fast connection orange• • • 70105018 10 A - L3-N 1m stripped blue• • • 70105118 10 A - L3-N 3m stripped blue• • • 70105128 10 A - L3-N 5m stripped blue• • • 447 42 10 A - L3-N 1m fast connection blue• • 70105063 10 A - L2-N2 1m stripped black• • 70105163 10 A - L2-N2 3m stripped black• • 70105173 10 A - L2-N2 5m stripped black• • 447 43 10 A - L2-N2 1m fast connection black2 conductors side• 70265<strong>001</strong> 10 A - L1-N 1m stripped orange• 70265101 10 A - L1-N 3m stripped orange• 70265111 10 A - L1-N 5m stripped orange• 447 45 10 A - L1-N 1m fast connection orangeThe availability of plugs having different colours allows you to immediately identify the circuit the device belongs to, hence giving you considerable installationadvantages for future modifications. The balance control of the loads on the various phases is immediate thanks to the different colours.Specifies the most frequently used plugs.LB 252LB 402SINGLE-PHAS<strong>EN</strong>L52LB 254LB 404N3L3L2N2DUAL SINGLE-PHAS<strong>EN</strong>3L3L2N238LB 254LB 404THREE-PHASE BALANCED LOAD77NL3L2L1NL3NL2NL1LB 256LB 40614 LB - LIGHTING BUSWAY


LBLIGHTING BUSWAYSAFETY PLUGSLB Model Item Capacity Fuse Phase Cable length Cable end Colour252 254 256402 404 4064 conductors side Phase selection single-phase plug• • • 70105030 16 A Ø5x20 6.3A selectable - - grey• • • 70105031 16 A - selectable - - grey• • • 447 47 16 A - selectable 1m fast connection grey• • • 70105130 16 A Ø5x20 6.3A selectable 3m stripped grey• • • 70105131 16 A Ø5x20 6.3A selectable 5m stripped greyThree-phase plugs• • 70105141 16 A - L1-L2-L3-N - - grey• • 70105142 16 A - L1-L2-L3-N 3m stripped grey• • 70105143 16 A - L1-L2-L3-N 5m stripped greySpecifies the most frequently used plugs.2 conductors side• 70265002 16 A Ø5x20 6.3A - - - orange• 70265003 16 A - - - - orange• 70265102 16 A - - 3m stripped orange• 70265103 16 A - - 5m stripped orange6753min. 6.5 mmMAX. 15 mmØ 3MAX. cablesection 2.5 mm 2104PLUGS WITH FUSE CARRIER CH8 - 16 A SINGLE-PHASELB Model Item Capacity Fuse Phase Cable length Cable end Colour252 254 256402 404 4064 conductors side• • • 70105071 16 A Ø8.5x31.5 selectable - - grey• • • 447 48 16 A Ø8.5x31.5 selectable 1m fast connection grey64min. 6.5 mmMAX 15 mm30Ø 3MAX. cablesection 2.5 mm 2135CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE15


Plugs forall versionsPLUGS WITH FUSE CARRIER - 16 A THREE-PHASELB Model Item Capacity A Fuse Phase Cable length Cable end Colour252 254 256402 404 4064 conductors side • • 70105035 16 A Ø 8.5x31.5* L1-L2-L3-N - - grey• • 70105045 16 A Ø 6.3x31.5* L1-L2-L3-N - - grey • • 447 49 16 A Ø 8.5x31.5 L1-L2-L3-N 1 m fast connection grey* Fuse not included857450min. 6.5 mmMax. 15 mmØ 3Max. cablesection 2.5 mm 2243MOBILE CONTACTCan be used to transform a single phase selection plug into a three-phase plug40Item Capacity A Fuse Weight (kg)71005028** 16 A 1 0.00871005029 16 A 0 0.008** 16 A contact with 6.3 A ceramic fuseFor fuse features, see page 13653816 LB - LIGHTING BUSWAY


FixingsupportsLBLIGHTING BUSWAYSNAP-ON BRACKET (MAX. 15 KG)Clamp to be clipped onto the element’s top or bottom edge.Ø 7Model Item Weight (kg)Burnished Steel 71003003 0.021STAINLESS STEEL 71203701 0.0213018SUSP<strong>EN</strong>SION HOOK (MAX. 15 kg)Clamp to be clipped onto the element’s top or bottom edge.Model Item Weight (kg)Burnished Steel 71005002 0.025STAINLESS STEEL 71203702 0.0254130Ø 18SUSP<strong>EN</strong>SION RING (MAX. 15 kg)Clamp to be clipped onto the element’s top or bottom edge.Model Item Weight (kg)Burnished Steel 71005015 0.025STAINLESS STEEL 71203703 0.0254130Ø 7SUSP<strong>EN</strong>SION BRACKET (MAX. 15 kg)Clamp to be clipped onto the element’s top or bottom edge.ItemWeight (kg)71003<strong>001</strong> 0.0331.5 Ø 66052030305630563025CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE17


Fixingelements6750BRACKET HOLDERMust be used with code 71003<strong>001</strong> suspension bracket.4955Ø 10ItemWeight (kg)73003312 0.136Ø 4.2625040slot 8 x 2549WALL SUSP<strong>EN</strong>SION BRACKETCannot be used with LB6 (no access to back side for plugs)ItemWeight (kg)71003008 0.03035532049slot 6.5 x 840Ø 6BRACKET FOR COUPLING ELEM<strong>EN</strong>TSBracket suitable for positioning two lines in parallel. The reduced dimensionsare also specified for floor installations.ItemWeight (kg)70105043 0.060Item 7100300830 1055Ø 8Ø 6suspension hole withchain/cable6627Hole forthreaded barfloor-fixing holeItem 7100300818 LB - LIGHTING BUSWAY


Cable channeland accessoriesLBLIGHTING BUSWAYCABLE CHANNEL WITH COVER (RIGID PVC)Item Length [m] Weight (kg)710<strong>001</strong>04 3 0.88428 30002828SPACER FOR CABLE CHANNELWhen ordering, consider using spacer every metre of conduit.ItemWeight (kg)71003007 0.006202 25Ø 5160281 m30362030SUSP<strong>EN</strong>SION BRACKET FOR CABLE CHANNELSuspension bracket to be used when the cable cable channel is used.ItemWeight (kg)71003006 0.10850CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE19


20HL - HIGH LIGHTING25 - 40A


HLHIGH LIGHTINGSECTION CONT<strong>EN</strong>TS22 General features28 HLs Trunking components: 2 and 4 conductors elements31 HLs plugs33 HLd Trunking components: 4, 6 and 8 conductors elements36 HLd plugs39 Fixing supports41 Cable channel and accessories129 Technical information135 Determination of the operating current of a busbarLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE21


HLHigh LightingG<strong>EN</strong>ERAL FEATURESThe HL busbar line is ideal for powering lightingfixtures wherever it is necessary to hang heavyaccessories onto the busbar. The main features of theHL range are:• speed, simplicity and flexibility when installing andplanning the lines;• high mechanical rigidity obtained by the particular“beam-type configuration” and by an increasedthickness of the metal casing;• capable of being installed in systems with adistance of up to 6m between suspension brackets;• compliance with Standard IEC 60439-1 and 2;• rated at average room temperature of 40 °C for ahigher performance level compared to the 35 °Crating required by the standard.HL is available in two dimensions:• HLs single version for 2 and 4 conductors• HLd dual version for 2+2; 4+2; 4+4 and 2x4conductors.Straight elementTap-off plugClamping bracketStandard end feed unitExhibition pavilionsCar parks22 HL - HIGH LIGHTING


STRAIGHT ELEM<strong>EN</strong>TSThe components and the features of the HL straightelements are:• a beam-shaped casing, made with hot galvanizedsteel (Senzimir) (due to its cross-section andelectrical continuity, it also serves as the protectiveearth)• HLs busbar dimensions: 26x62 mm; HLd: 40x70 mm;• upon request, the straight elements are alsoavailable in the Aisi 304 stainless steel version;• number of conductors: 2, 4, 6 or 8 rigid copperconductors with a 99.9% purity;• conductor section: 3.14 mm 2 for 25 A and6.15 mm 2 for 40 A;• separation between the conductors by using a V0(according to UL94) self-extinguishing insulatingplastic sheathe and in compliance with the glowwiretest according to IEC 60695-2-10;• tap-off outlets equidistant every 1m (3 outletsevery 3m) or 0.5m (6 outlets every 3m), receivingthe corresponding tap-off plugs (in the LB 6conductor version the outlets are arranged on bothsides of the busbar: 3+3 or 6+6 outlets);• a junction block automatically ensuring electricalcontinuityThe connection between two straight elements isquick; with one operation the mechanical and theelectrical connection is ensured between two joinedelements; at the same time, an IP 55 degree ofprotection is guaranteed without using additionalsealing accessories.The continuity of the protective conductor (casing)is guaranteed by tightening the special connectionscrew.The whole busbar is fire retardant in compliance withthe Standard IEC 60332-3.In the HLd (dual) version, the straight elementsare separated over their entire length by a metalplate divider (thickness 0.8 mm) which separatesthe straight elements in two parts making the twocircuits totally independent. Because of this divisionthe HLd busbar can be used for powering “normal”and “emergency” loads.The HLd line is designed so as to provide twoseparate rated circuits (25 A+25 A or 40 A+40 A) onwithout a derating factor, and not one one 25 or 40 Aincoming divided into two circuits.HLHIGH LIGHTINGSmall/medium industriesGymsG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE23


HLHigh LightingFEED UNITSAllows you to electrically power the HL line throughone (HLs) or two separate lines (HLd); the installationis carried out with a quick junction connection as withthe straight elements.The feed units have terminals for the connection offlexible cables for sections of up to 25 mm 2 . There isan anti-pullout cable clamp inside the feed unit. Theentrance point for the incoming cable is positionedon the end of the feed unit.Standard end feed unit<strong>EN</strong>D COVERThe end cover ensures the IP 55 protection degree atthe end of the line.Standard end coverFIXING DEVICESSpecific accessories are available for attaching thebusbar to the structure of the building (directly orwith a steel chain or cable). The accessories foroverhead fixing are:• snap clamp: the snap-on installation is extremelyfast. This bracket is suitable both for overhangingthe busbar to the ceiling and for hanging productssuch as fluorescent lamps, tap-off boxes, etc., tothe busbar itself;• snap clamp with ring or hook: the ring or the hookenables to hang lamps easily;• simple bracket: used with the ceiling bracketholder, it enables the installation the busbardirectly onto the ceiling at a distance of about25 cm;• wall bracket: enables the fixing of the busbardirectly onto the wall of a building, setting it at therequired distance enabling the installation of thenecessary components.Fixing accessories for fastening the busbar run to thestructure and hanging the lamps onto the busbar24 HL - HIGH LIGHTING


TAP-OFF PLUGSUsed for connecting and energizing light fixtures; theirfeatures include:• can be inserted and removed when the busbar isenergized and when the fixure is under load;• the PE contact (protective earth) is the first to make anelectrical connection when inserting the plug into theoutlet and it is the last to disconnect when pulling itout;• all insulating plastic components are in compliancewith the glow-wire test (IEC 60695-2-10) with V1 selfextinguishingdegree (UL94);• standard IP 55 degree of protection without usingadditional accessories according to Standard IEC 60529;• in the HLd line, the plugs are polarized, in otherwords the plug which is busbar on one side of theelement cannot be installed on the other side due to amechanical lock on the outlet;• the tap-off plugs are different for the HLs 2, 4 andHLd 2+2, 4+2, 4+4; 2x4 conductors offer. They include:a) 16 A phase selection tap-off plugs, pre-wired with1 m of 3x1.5 mm 2 FROR cable;b) 16 A phase selection tap-off plugs, with terminals forconnecting a cable;c) 16 A phase selection tap-off plugs, with Ø 5x20mmcylindrical ceramic fuse and with terminals forconnecting an L+N+PE cable;d) 16 A three-phase tap-off plugs, with a set of threecylindrical fuse carriers (8.5x31.5mm) with terminalsfor connecting a 3L+N+PE cable.HLHIGH LIGHTINGSingle-phase selection plugPlug with fuse carrierG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE25


Trunking components andadditional elementsDepending on the different installation requirementsZucchini can provide various technical solutions:a) flexible joint: used to make changes of direction orto avoid possible interferences that may be found onthe path of the busbar.Their main technical features are:• same connection method as the straight elements;• electrical and mechanical connection with oneoperation;• standard degree of protection: IP 55;• continuity of the protective conductor, made from thecasing of the element itself, guaranteed by tighteningthe special connection screw;b) cable trunking with cover: this accessory, whichcan be positioned in the upper part of the busbar,can be used to distribute auxiliary circuits, it is anintegral part of the busbar run using special spacersand brackets which support the busbar trunkingsystem firmly. The trunking part is 3 m long and itsdimensions are 28x28 mm;c) intermediate feed unit: it can power the busbar froman intermediate point of the line, thus reducing thevoltage drop at the end of the line and/or makingthe installation easier when the electric energysupply point is near the middle of the line.The end capcompletes theinstallation of thelines and guaranteesthe IP 55 degreeof protection of theline.Straight elements, withtap-off outlets every1000 mm on bothsides, with pre-installedblanking accessory.Phase selectiontap-off plugs, alsoavailable with fuses.Ring for suspending alamp or for suspendingother accessories ofthe busbar. (boxes,loudspeakers, etc.)Hook for suspending alamp or for suspendingbusbar itself and otherdevices (lamps, etc)Snap-on bracketthat can be used forsuspending the lineand devicesPARTS OF THE LINESingle-phase selection plugPlug with fuse carrierCeiling suspension bracket26 HL - HIGH LIGHTING


HLHIGH LIGHTINGSingle-phase 16 A tap-off plugswith a pre-wired cable and phaseidentification using colours:N - L1 = greyN - L2 = orangeN - L3 = bluefor L+N circuitandN3 - L3 = blueN2 - L2 = blackfor single-phase dual circuit.Wall suspensionbracketFeed units, complete with cableclamp and terminals for 25 mm 2cables.Wall mounting bracketSimple suspension bracketSnap-on stainless steel hook, ringand bracketOutlet cover (spare)G<strong>EN</strong>ERAL FEATURES27LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


HL Trunkingcomponents - single150325 100030<strong>001</strong>000 67512HL 252HL 402HL 254HL 404STRAIGHT ELEM<strong>EN</strong>TElements with pre-installed outlet covers.6238NL1NL3L2L1Model Item Length Rating Conductors No. of Weight(m) (A) outlets (kg)HL 252 71010151 3 25 2 3 4.5HL 252 71010161 1.5 25 2 2 2.251226HL 402 71030151 3 40 2 3 4.8HL 402 71030161 1.5 40 2 2 2.4HL 254 71020151 3 25 4 3 4.8HL 254 71020161 1.5 25 4 2 2.4HL 404 71040151 3 40 4 3 5.1HL 404 71040161 1.5 40 4 2 2.55OUTLET COVER (Spare)3525The straight elements are supplied with outlet cover pre-installed on theoutlets.Model Item Colour Weight (kg)All 71023601 grey 0.011STANDARD FEED UNIT95 60d 1= MAX Ø 386.56.5Max. cablesection 25 mm 2Supplied without an electric and mechanical bayonet connection. It must beinstalled on one side of the element, located near the linking bayonet.Model Item Weight (kg)All 71041<strong>001</strong> 0.800For cable glands see page 13634528 HL - HIGH LIGHTING


STANDARD <strong>EN</strong>D COVERTo be used with standard feed unitsModel Item Weight (kg)All 71041301 0.05081HLHIGH LIGHTING3639<strong>EN</strong>D-LINE FEED UNITSupplied with an electric and mechanical bayonet connection. It must beinstalled on the extremity of the element without the bayonet.Can be used when power feed is needed at both ends of a run (less voltagedrop) or cabled in association with a standard feed unit to create a flexibleelement to bypass large obstacles (beams, air ducts, etc)150d 1= MAX. Ø 3834595 606.56.5Max. cablesection 25 mm 2Model Item Weight (kg)All 71041002 1.000<strong>EN</strong>D COVERTo be used with end-line feed unit.Model Item Weight (kg)All 71041302 0.36081226FLEXIBLE JOINTUsed to make changes of direction.Model Item Weight (kg)All 71041261 2.5002409560150930CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE29


HLs TrunkingcomponentsC<strong>EN</strong>TRE FEED UNIT 25/40AUsed to power a busbar from an intermediate point. The intermediate powerbox is also used for reducing the voltage drop of the line.Model Item Weight (kg)All 71041151 2.9<strong>001</strong>9695 60250 96d1 = MAX. ø48150 88699Max. cablesection 35 mm 230 HL - HIGH LIGHTING


HLs plugsPHASE SELECTION SAFETY PLUGSModel Item Rating Fuse Phase Cable length Cable end Colour252 254402 404• • 71005030 16 A Ø5x20 selectable - - grey• • 71005031 16 A - selectable - - greyHLHIGH LIGHTING• • 71005032 16 A - selectable 1m stripped grey• 71015030 16 A Ø5x20 L1-N - - blueHL 252HL 402blue outletHL 254HL 404grey outletBLUEGREY67GREY72104min. 6.5 mmMAX. 15 mmØ 3Max cablesection 2.5 mm 27100503071005031SINGLE-PHASE PLUGS WITH FUSE CARRIERModel Item Rating Fuse Phase Cable length Cable end Colour252 254402 404• • 71005068 16 A Ø8.5x31.5 selectable - - grey• • 71005070 16 A Ø8.5x31.5 L1-N 1m stripped grey• 71005071 16 A Ø8.5x31.5 L2-N 1m stripped orange• 71005072 16 A Ø8.5x31.5 L3-N 1m stripped blue3071015030 7100503071005031710050326075135min. 6.5 mmMAX. 15 mmØ 3Max cablesection 2.5 mm 2CATALOGUE31LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


HLs plugsTHREE-PHASE PLUGS WITH FUSE CARRIERØ 3Max cablesection 2.5 mm 2Model Item Rating Fuse Phase Colour252 254402 404• 71005035 16 A Ø8.5x31.5 * L1-L2-L3-N grey* Fuse not included81min. 6.5 mmMAX. 15 mm8550243MOVABLE CONTACTTo be added when creating three-phase versions of the safety tap-off plugs(2 for each plug).40Item Capacity Fuse Weight (kg)71005028 ** 16 A 1 0.01071005029 16 A 0 0.010** 16 A contact with 6.3 A fuse53832 HL - HIGH LIGHTING


HLd TrunkingcomponentsHLHIGH LIGHTINGHL 2522HL 4022HL 2542HL 4042STRAIGHT ELEM<strong>EN</strong>TElements with pre-installed outlet covers.701638NL2L1NL1L2L3NNL1Model Item Length Rating Conductors No. of Weight(m) (A) outlets (kg)HL 2522 71510151 3 25+25 2 + 2 6 8.4HL 2522 71510161 1.5 25+25 2 + 2 4 4.21626HL 4022 71540151 3 40+40 2 + 2 6 8.7HL 4022 71540161 1.5 40+40 2 + 2 4 4.35HL 2544HL 404440HL 2x4HL 2542 71520151 3 25+25 4 + 2 6 8.7HL 2542 71520161 1.5 25+25 4 + 2 4 4.35HL 4042 71550151 3 40+40 4 + 2 6 9.3HL 4042 71550161 1.5 40+40 4 + 2 4 4.65L1L2L3NNL3L2L1L1L3L4L2ZL6L5XHL 2544 71530151 3 25+25 4 + 4 6 8.7HL 2544 71530161 1.5 25+25 4 + 4 4 4.35HL 4044 71560151 3 40+40 4 + 4 6 9.6HL 4044 71560161 1.5 40+40 4 + 4 4 4.8HL 2x4 to create4 interlocked single-phase circuitsHL 2x4 71570151 3 25+25 2+2+2+2 6 8.7HL 2x4 71570161 1.5 25+25 2+2+2+2 4 4.35150 325 100030<strong>001</strong>000 675OUTLET COVER (spare)The elements are supplied with outlet covers pre-installed on the outletcovers.Model Item Colour Weight (kg)All 01150048 grey 0.0112535Versions with painted and stainless steel casing on requestCATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE33


HLd TrunkingcomponentsSTANDARD FEED UNIT 25/40A12055no. 2 d 1= MAX. Ø 386.5Supplied without an electric and mechanical bayonet connection. It mustbe installed on one side of the element, located near the linking bayonet.The feed unit has two separate cable inputs and the terminals are totallyseparated and independent.Model Item Weight (kg)All 71561<strong>001</strong> 1.100Cable gland selection page 136953456.5Max. cablesection 25 mm 2STANDARD <strong>EN</strong>D COVERTo be used with the standard feed unitModel Item Weight (kg)All 71561301 0.0903955<strong>EN</strong>D-LINE FEED UNIT 25/40ASupplied with an electric and mechanical bayonet connection. It must beinstalled on one side of the element, not located near the linking bayonet.The feed unit has two separate cable inputs and the terminals are totallyseparated and independent.no.2 d 1= MAX. Ø 3855120956.56.5Max. cablesection 25 mm 2Model Item Weight (kg)All 71561002 1.600Cable gland selection page 136150345<strong>EN</strong>D COVERTo be used with the end-line feed unit.Model Item Weight (kg)All 71561302 0.7869393935522634 HL - HIGH LIGHTINGVersions with painted and stainless steel casing on request


FLEXIBLE JOINT 25/40AUsed to make changes of direction.Model Item Weight (kg)All 71561261 3.000HLHIGH LIGHTING24095120150930C<strong>EN</strong>TRE FEED UNIT 25/40AUsed to power a busbar from an intermediate point. The intermediate powerbox is also used for reducing the voltage drop of the line.Model Item Weight (kg)All 71561151 3.8<strong>001</strong>9695 192*250max 2 holes ø 48mm15088699Max. cablesection 35 mm 2Versions with painted and stainless steel casing on requestCATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE35


HLd plugsHLd PLUGSModel Item Rating Fuse Phase Cable length Cable end Colour2522 2542 2544 2x44022 4042 4044• • • • 71505030 16 A Ø5x20 selectable - - grey• • • • 71505031 16 A - selectable - - grey• • • • 71505032 16 A - selectable 1m stripped grey• • 71515030 16 A Ø5x20 L1-N - - blue• 71515031 16 A Ø5x20 L2-L3 - - orange• 71575030 16 A Ø5x20 L1-L2 - - blue• 71575031 16 A Ø5x20 L3-L4 - - black• 71575032 16 A Ø5x20 L5-L6 - - orange• 71575033 16 A Ø5x20 X-Z - - brownSpecifies the most frequently used plugs.7781min. 6.5 mmMAX. 15 mmØ 3Max cablesection 2.5 mm 2104SINGLE-PHASE PLUGS WITH CH8 FUSE CARRIERModel Item Rating Fuse Phase Cable length Cable end Colour2522 2542 2544 2x44022 4042 4044• • • • 71505059 16 A Ø8.5x31.5 selectable - - grey• • 71505070 16 A Ø8.5x31.5 L1-N 1m stripped grey• • 71505071 16 A Ø8.5x31.5 L2-N 1m stripped orange• • 71505072 16 A Ø8.5x31.5 L3-N 1m stripped blue3080min. 6.5 mmMAX. 15 mm70Ø 3Max cablesection 2.5 mm 213536 HL - HIGH LIGHTING


THREE-PHASE PLUGS WITH FUSE CARRIERModel Item Rating A Fuse Phase Colour2522 2542 2544 2x44022 4042 4044• • 71505035 16 A Ø8.5x31.5 L1-L2-L3-N greyHLHIGH LIGHTING9550Ø 3Max cablesection 2.5 mm 286min. 6.5 mmMAX. 15 mm243MOVABLE CONTACTTo be added to create three-phase versions of the safety tap-off plugs(2 for each plug).40Item Rating A Fuse Weight (kg)71005028* 16 1 0.01071005029 16 0 0.010* 16 A contact with 6.3 A fuse538CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE37


HLd plugsHL 2522 - HL 4022blue outletorange outletGREYL1NBLUEL1NNL2ORANG<strong>EN</strong>L2GREYphase selection7150503071505031dedicated phasededicated phasephase selection71515030 71515031 7150503071505031HL 2542 - HL 4042blue outletgrey outletGREYNL1BLU<strong>EN</strong>L1L1L2L3NGREYphase selection7150503071505031dedicated phase71515030phase selection7150503071505031HL 2544 - HL 4044grey outletgrey outletGREYL1L2L3NNL3L2L1GREYphase selection7150503071505031phase selection7150503071505031HL 2 X 4blue outletorange outletBLACKL3L4BLUEL1L2L6L5ORANGEZXBROWN71575031 71575030 71575032 715750334 INDEP<strong>EN</strong>D<strong>EN</strong>T single-phase circuits38 HL - HIGH LIGHTING


FixingsupportsSNAP-ON BRACKET (MAX. 15 kg)Model Item Weight (kg)Burnished Steel 71003003 0.021STAINLESS STEEL 71203701 0.021HLHIGH LIGHTINGØ 73018SUSP<strong>EN</strong>SION HOOK (MAX. 15 kg)4130Ø 184130Ø 76052030Model Item Weight (kg)Burnished Steel 71005002 0.025STAINLESS STEEL 71203702 0.0253056SUSP<strong>EN</strong>SION RING (MAX. 15 kg)Model Item Weight (kg)Burnished Steel 71005015 0.025STAINLESS STEEL 71203703 0.0253056SUSP<strong>EN</strong>SION BRACKET (MAX. 15 kg)ItemWeight (kg)71003<strong>001</strong> 0.0331.5 Ø 63025CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE39


FixingelementsWALL SUSP<strong>EN</strong>SION BRACKET13 x 6.5For wall mounting of the HLd elements, it is possible to connect the plug on theinternal side only if the busbar is taken out of the wall bracket, then insert the plugand replace the element afterwards.557725ItemWeight (kg)71003009 0.090675055Ø 10Ø 4.262509613 x 6.596404055778025CEILING BRACKET HOLDERMust be used with the code 71003<strong>001</strong> suspension bracket.ItemWeight (kg)73003312 0.13640slot 8 x 2549FLOOR FIXING BRACKETOnly for the HLs single version. Suitable for horizontal HLs floor fastening.69ItemWeight (kg)71003018 0.090Compatible with:HL 252, HL 402, HL 254, HL 40446slot 5 x 1296 55JUNCTION STIFF<strong>EN</strong>ERTo be used for strengthening bracket links with suspension centre distancesthat are over 5m.500Model Item Weight (kg)for single-type 71042024 0.200for dual-type 71042025 0.20040 HL - HIGH LIGHTING


Cable channeland accessoriesCABLE CHANNEL WITH COVER (RIGID PVC)Model Length [m] Weight (kg)710<strong>001</strong>04 3 0.884HLHIGH LIGHTING28 300028302028SPACER FOR CABLE CHANNELItemWeight (kg)71003007 0.0061 m3620302 25Ø 5HLs - SUSP<strong>EN</strong>SION BRACKET FOR CABLE CHANNELOverhead bracket to be used when the cable trunking is used above thebusbar.160ItemWeight (kg)71003006 0.108Compatible with:HL 252, HL 402, HL 254, HL 40450225Ø 516028HLd - SUSP<strong>EN</strong>SION BRACKET FOR CABLE CHANNELSuspension bracket to be used when the cable trunking is used above thebusbar.ItemWeight (kg)71503006 0.108Compatible with:HL 2522, HL 4022, HL 2544, HL 4044, HL 2542, HL 4042, HL 2 x 450CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE41


42SL - SERIE LUCE40 - 63A


SLLIGHT SERIESSECTION CONT<strong>EN</strong>TS44 General features50 Trunking components52 Plugs and tap-off boxes53 Fixing supports55 Cable channel and accessories130 Technical information135 Determination of the operating current of a busbarLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE43


SLSerie LuceG<strong>EN</strong>ERAL FEATURESThe Zucchini SL line is suitable for powering smallone-phase and three-phase equipment, such as:industrial refrigerators, lathes, hand tools, etc.The main features of the SL range are:• speed, simplicity and flexibility when installing andplanning the lines;• reduced dimensions;• a rigid and robust structural design for severeinstallation conditions;• tap-off boxes with possibility of local protectionwith mcbs (<strong>Legrand</strong> Lexic series);• capable of being installed in systems with a bracketcentre distance of up to 6m;• compliance with Standard IEC 60439-1 and 2;• rated at average room temperature of 40°C for ahigher performance level compared to the 35°Crating required by the standard.Shopping centresSmall industriesStraight elementTap-off boxFeed unit44 SL - SERIE LUCE


STRAIGHT ELEM<strong>EN</strong>TSThe components and the features of the SL straightelements are:• a “beam-shaped” section, made with hotgalvanized steel (Senzimir) which, thanks to itssection and electrical continuity, can also serve asa protective conductor;• casing thickness: 0.8mm;• busbar dimensions: 26x62mm;• number of conductors: 4 copper conductors withpurity no less than 99.9%; section of conductors:9.5 mm 2 per In 40A and 12.3 mm 2 per In 63A;• separation between the conductors by using aV0 self-extinguishing insulating plastic sheathe(according to UL94) and in compliance with theglow-wire test according to IEC 60695-2-10;• tap-off outlets (IP40/IP 55) with a centre distanceof 0.75 m (4 outlets every 3m), set up for beingconnected with plugs and/or tap-off boxes;• an electrical joint block for automaticallyconnecting live parts.The connection between two straight elementsis quick; with one operation the electric and amechanical connection is easily made. The IP40performance of the SL line can be easily upgradedto IP 55 with joint covers and outlet covers. Thecontinuity of the protective earth is automaticallyensured when two components are joined. Thewhole busbar is fire retardant in compliance withthe IEC 60332-3 standard. There are also 3m straightelements with 6 or 10 tap-off outlets. Theseversions, which are characterized by high densityjunction points, are particularly valued in floatingunderfloor installations or when distributing energyon board the machine.Power linesLight linesSLLIGHT SERIESG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE45


SLSerie LuceFEED UNITSThe feed unit is assembled to the run in an identicalmanner as with the straight elements. The feed unitshave terminals for the connection of copper cablesfor sections of up to 25 mm².There is an anti-pullout cable clamp jumper insidethe power supply. The entrance point of the cables ispositioned on the end of the feed unit.Feed unit<strong>EN</strong>D COVERThe end cover ensures the IP 55 protection degree atthe end of the line.End coverFIXING SUPPORTSSpecific accessories are available for fixing the line tothe structure of the building (directly or with a steelchain or cable). The accessories for overhead fixingare:• snap clamp: the snap-on installation is extremelyfast. This bracket is suitable both for overhangingthe busbar to the ceiling and for hanging productssuch as fluorescent lamps, tap-off boxes, etc., tothe busbar itself;• snap clamp with ring or hook: the ring or the hookenables to hang lamps easily;• simple bracket: used with the ceiling bracketholder, it enables the installation the busbar directlyonto the ceiling at a distance of about 25cm;• wall bracket: enables the fixing of the busbardirectly onto the wall of a building, setting it at therequired distance enabling the installation of thenecessary components.Fixing accessories for fastening the busbar run to the structure and hangingthe lamps onto the busbar46 SL - SERIE LUCE


PLUGS AND TAP-OFF BOXESUsed for connecting and energizing small single andthree-phase loads; their features include:• manoeuvrability when energized;• the PE contact (protective earth) is the first to makean electrical connection when inserting the plug intothe outlet and it is the last to disconnect when pullingit out;• all insulating plastic components are in compliancewith the glow-wire test (IEC 60695-2-10) with V1 selfextinguishingdegree (UL94);• IP 55 according to Standard IEC 60529, with noadditional accessories.Tap-off plugs are three-phase, 32A plugs available intwo versions; without fuse or with 10.3 x 38mm fusecarriers.Tap-off boxes allow local protection of the derivationusing the <strong>Legrand</strong> Lexic DIN rail mounting mcbs.The following are available:a) 32A empty tap-off boxes with a disconnectionsystem integrated into the cover: when the coveris opened the power is automatically disconnectedfrom all the accessible metal parts;b) 32A tap-off box with a 4 module DIN window: Inthese boxes, the window allows the possibility ofoperating the Lexic DIN rail modules without openingthe cover.SLLIGHT SERIESTap-off boxG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE47


Trunking components andadditional elementsDepending on the different installation requirementsZucchini can provide various technical solutions:a) Flexible joint: used to make changes of direction orto avoid possible interferences that may be found onthe natural path of the busbar. The features are asfollows:• same connection method as the straight elements;• electrical and mechanical connection with oneoperation;• degree of basic protection IP40 (IP 55 with jointcovers and outlet covers);• continuity of the protective conductor, made from thecasing of the element itself, guaranteed by tighteningthe special connection screw;b) cable trunking with cover: this accessory, which canbe positioned on the upper or lower part of thebusbar, can be used to distribute auxiliary circuits. It isan integral part of the busbar by using special spacersand brackets which hold the busbar trunking systemfirmly.The end cover completesthe installation of the linesand guarantees the degreeof protection of the line.32A tap-off boxes withtransparent cover for modularcircuit breakers –4 DIN modules.Ring clamp forhanging lighting orsuspension of thebusbar with chainor wire cable.Snap-on bracket.PARTS OF THE LINETap-off boxFlexible joint48 SL - SERIE LUCE


SLLIGHT SERIESOverhead hook forlamps32A three-phasetap-off plugs,available with aset of three fusecarriersStraight elements with tap-offoutlets every 1000 mm on oneside, with pre-installed outletcovers.If required, straight elements areavailable with 6 junctions(every 500 mm).Standard or end-linefeed units, according tothe trend of the line,complete with cableclamp and terminals for25 mm 2 cables.Wall mounting bracketSimple suspension bracketSnap-on stainless steel bracketsOutlet coverG<strong>EN</strong>ERAL FEATURES49LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Trunkingcomponents475 750750 750 42515030<strong>001</strong>2STRAIGHT ELEM<strong>EN</strong>T623812L1NL2L3Model Item Length Rating No. of Weight(kg) (m) (A) outletsSL40 704<strong>001</strong>01 3 40 4 6.200SL40 704<strong>001</strong>11 3 40 6 6.800SL40 704<strong>001</strong>12 3 40 10 7.300SL40 706<strong>001</strong>02 1.5 63 2 3.85026SL63 706<strong>001</strong>01 3 63 4 6.500SL63 706<strong>001</strong>11 3 63 6 6.900SL63 706<strong>001</strong>12 3 63 10 7.400SL63 706<strong>001</strong>02 1.5 63 2 3.850IP 55 OUTLET COVERItemWeight (kg)71002062 0.474One cover needed per unused outlet956.56935 4260STANDARD FEED UNITModel Item Weight (kg)IP 55 70601061 0.750Cable gland selection page 136d 1= MAX Ø 38216 1506.5Max. cablesection 25 mm 250 SL - SERIE LUCE


<strong>EN</strong>D-LINE FEED UNITModel Item Weight (kg)IP 55 70601062 0.826Cable gland selection page 136150 216d 1= MAX. Ø 3895606.56.5Max. cablesection 25 mm 2SLLIGHT SERIESIP 55 <strong>EN</strong>D COVEREnsures the IP 55 at the end of the line. Used with standard and end-linefeed unit.ItemWeight (kg)71<strong>001</strong>351 0.5709756 240FLEXIBLE JOINTUsed to make changes of direction.ItemWeight (kg)70601261 1.90030060 9515097880IP 55 JOINT COVERWhen applied to each joint it increases the line from IP40 to IP 55.ItemWeight (kg)71002051 0.47456 240CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE51


Plugs and tap-off boxes32A TAP-OFF PLUGS 3P+N35Model Item Rating Fuse L= [mm] Weight (kg)(A) junctionsIP 55 70605051 32 - 80 0.070IP 55 70605052 32 Ø 10.3x38 * 105 0.100* Fuses not supplied5.5Max. cablesection 10 mm 2115105605.5Ld1= min 6mmMAX. 19mm32A EMPTY TAP-OFF BOXES 3P+NModel Item Feature Weight (kg)IP 55 70605054 Grey cover 0.700IP 55 70605055 Transparent cover 0.700Cable gland selection page 1365.55.5Max. cablesection 10 mm 2d 1= MAX. Ø 4826532A TAP-OFF BOX WITH TRANSPAR<strong>EN</strong>T COVER AND DOOR(set up for modular circuit breakers – max 4 DIN modules).Model Item Weight (kg)IP 55 70605053 0.800Cable gland selection page 136136105NICOTTO DI CONGIUNZIONE IP 555.5Max. cablesection 10 mm 21151365.5d 1= MAX Ø 4826552 SL - SERIE LUCE


FixingsupportsSNAP-ON BRACKET (MAX 15 KG)Suspension support to be fixed on the element edges.Ø 7Model Item Weight (kg)Burnished Steel 71003003 0.021Stainless steel 71203701 0.021SLLIGHT SERIES1841304130203030SUSP<strong>EN</strong>SION HOOK (MAX 15 KG)Suspension support to be fixed on the element edges.Model Item Weight (kg)Burnished Steel 71005002 0.025Stainless steel 71203702 0.0253056Ø 18SUSP<strong>EN</strong>SION RING (MAX 15 KG)Suspension support to be fixed on the element edges.Model Item Weight (kg)Burnished Steel 71005015 0.025Stainless steel 71203703 0.0253056Ø 71.5 Ø 6STANDARD SUSP<strong>EN</strong>SION BRACKET (MAX 15 KG)Suspension support to be fixed on the element edges.605ItemWeight (kg)71003<strong>001</strong> 0.0333025CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE53


FixingsupportsWALL SUSP<strong>EN</strong>SION BRACKETItemWeight (kg)71003009 0.0909613 x 6.540STAFFA DI SOSP<strong>EN</strong>SIONE A PARETE557725FLOOR FIXING BRACKETSuitable for horizontal floor fastening.ItemWeight (kg)71003018 0.0906946slot Ø 5 x 12STAFFA DI FISSAGGIO A PAVIM<strong>EN</strong>TO96 5554 SL - SERIE LUCE


Cable trunkingand accessories2 25Ø 5SUSP<strong>EN</strong>SION BRACKET FOR CABLE CHANNELOverhead bracket to be used when the cable trunking is used.ItemWeight (kg)71003006 0.10816050SLLIGHT SERIESCABLE CHANNEL WITH COVER (RIGID PVC)Item Length [m] Weight (kg)710<strong>001</strong>04 3 0.88428 30002830202828SPACER FOR CABLE CHANNELItemWeight (kg)71003007 0.006A spacer must be used for every metre of conduit1 m36 2030CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE55


56MS - MINI SBARRA63 - 100 - 160A


SECTION CONT<strong>EN</strong>TSMSMINI BUSBAR58 General features64 Trunking components66 Feed units67 Tap-off boxes70 Accessories131 Technical information135 Determination of the operating current of a busbarLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE57


MSTechnical descriptionG<strong>EN</strong>ERAL FEATURESMS is the smallest line of the Medium Power range.It is the ideal solution for energy distribution in smalland medium sized industries. The main features ofthe MS range are:• speed, simplicity and flexibility when planning andinstalling the lines;• strongly built, despite the reduced dimensions;• availability of tap-off boxes with housing capacityup to 16 DIN modules (i.e. <strong>Legrand</strong> Lexic mcbs);• compliance with the harmonised Standards IEC60439 - 1 and 2;• rated at average room temperature of 40°C for ahigher performance level compared to the 35°Crating required by the standard.Production lineSmall/medium industriesTap-off boxesStraight elementClamping bracketFeed unit58 MS - MINI SBARRA


STRAIGHT ELEM<strong>EN</strong>TSThe components and the features of the MS straightelements are:• a casing made of Senzimir quality galvanizedsteel, with a sheet-metal thickness that allows itsuse as the protective earth (PE) and ensures theelectrical continuity during mounting with no addedaccessories;• section bar dimensions: 39x97mm;• number of conductors: 4 with the same section3P+N available for capacities 63A, 100A and 160A;• separation between the conductors using plasticinsulating devices, reinforced with 20% ofglass fibres, which are able to ensure a V1 selfextinguishingdegree (according to UL94) and are incompliance with the glow-wire test according to IEC60695-2-10;• tap-off outlets with a constant centre distance of 1 mon both sides of the busbar (3+3 windows every3m), set up for being connected to tap-off boxes;• an electric joint block, with silver-plated coppercontacts for automatically connecting live parts andthe PE (protective conductor).The connection between two straight elementsis quick; with one operation it is possible to havean electric and a mechanical connection; hence,at the same time, an IP40 degree of protection isguaranteed. The upgrade to IP 55 is easily obtainedby adding joint covers and outlet covers. The wholeduct is fire retardant in compliance with the IEC60332-3 standard.MSMINI BUSBARInstallation in small industriesInstallation in workshopsG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE59


MSTechnical descriptionFIXING SUPPORTIn order to attach the line to the structure of thebuilding, directly or with wall supports, it is necessaryto use a bracket which serves as a collar around thebusbar. The bracket has holes to be easily pairedwith the available supports (see page 103).BracketTAP-OFF BOXESUsed to connect and energize one-phase and threephaseloads up to 63 A; their features include:• the PE contact (protective earth) is the first to makean electrical connection when inserting the boxinto the outlet and it is the last to disconnect whenpulling it out;• compliance with all insulating plastic componentsaccording to the glow-wire test (IEC 60695-2-10)with V1 self-extinguishing degree (UL94);• standard IP 55 degree of protection without usingadditional accessories;• can be inserted and removed when the busbar isenergized and when the fixure is under load, up to acapacity of 32 A.These boxes are available in a wide range of versions:• 63 A empty boxes (only with a terminal board forconnecting cables), with an internal DIN rail andtransparent door;• 16 A - available with a set of three cylindrical fusecarriers (10.3x38mm);• 16/32 A - available with a set of three cylindricalfuse carriers - DIAZED (D01: 16 A; D02: 32 A);• 50 A – available with cylindrical fuse carriers(14x51mm);• 63 A – available with 4-7-16 DIN mod;• 16 to 63 A – available with a disconnection deviceintegral with the cover.Example of a tap-off box with a transparentcover for modular circuit breakers60 MS - MINI SBARRA


FEED UNITAllows you to electrically power the MS line througha cable line; the installation is carried out with a quickjunction connection as with the straight elements.The feed units have terminals for the connection ofcopper cables for sections of up to 35 mm 2 for the63/100A feed unit and 70 mm 2 for the 160A feedunit.The entrance point of the cables is positioned on theback side of the feed unit. The MS line offers alsocentral feed units as well as power supply boxes witha switch-disconnector which allows you to select thewhole line for carrying out maintenance operationsor layout changes, if required.Standard feed unitMSMINI BUSBAREnd-line feed unit<strong>EN</strong>D COVERThe end cover ensures the IP 55 protection degree atthe end of the line.End coverG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE61


Trunking components andadditional elementsDepending on the different installation requirementsZucchini can provide various technical solutions:a) 90° angles: available for carrying out changes ofdirection both horizontally and vertically. There isa quick connection, as with the straight elements.standard IP40 degree of protection (IP 55 with preinstalledaccessories);b) T-type and X-type elements: available on request forspecial applications;c) flexible angle: available for 63A, 100A and 160Acapacities and allows changes of direction withangles different, horizontal and vertical, from 90°;d) straight elements with flame barrier (internal+ external). These elements - used when it isnecessary to move through fire-resistant walls - havebeen tested in laboratories (in compliance with DINStandards 4102-9 and <strong>EN</strong> 1366- 3) to confirm that, ifcorrectly installed, they can maintain the intrinsicfire-resistant properties of the wall;e) straight elements with bar lock: when the busbar isinstalled vertically (riser mains) these elements areequipped with a device that prevents the conductorsfrom sliding due to the weight of the portion ofcolumn over it. This type of element is required atabout every 10 m of column.End cap:completes theinstallation of the linesand guarantees the IP55 degree of protectionof the line.Straight elements, withtap-off outlets every1000 mm from bothsides.Wall suspensionbracket or bracketfor connecting asupport.PARTS OF THE LINECentre feed unitFlexible joint62 MS - MINI SBARRA


MSMINI BUSBARTap-off box complete with terminals forcables of up to 25 mm 2 . Made fromself-extinguishing plastic material, highmechanical resistance and resistance to staticcurrents. The Box can be connected anddisconnected when energized. Capacitiesfrom 16 A to 32A.Joint cover.It ensures the IP 55 degreeof protection of the link.Feed units.Tap-off boxesIP 55 gasket and joint coverEnd coverG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE63


Trunkingcomponents300086510<strong>001</strong>0<strong>001</strong>35 230230 135 10<strong>001</strong>000 865977039L1NL2L3STRAIGHT ELEM<strong>EN</strong>TModel Item Length (m) Rating (A) Weight (kg)MS63 51530101 3 63 7.890MS63 51530116 2 63 5.260MS63 51530115 1.5 63 3.945MS63 51530114 1 63 2.630MS63 51530112 < 1.5 63 -MS63 51530113 > 1.5 63 -MS100 51510101 3 100 7.890MS100 51510116 2 100 5.260MS100 51510115 1.5 100 3.945MS100 51510114 1 100 2.630MS100 51510112 < 1.5 100 -MS100 51510113 > 1.5 100 -MS160 51520101 3 160 9.290MS160 51520116 2 160 6.190MS160 51520115 1.5 160 4.645MS160 51520114 1 160 3.100MS160 51520112 < 1.5 160 -MS160 51520113 > 1.5 160 -64 MS - MINI SBARRA


FLEXIBLE JOINT8615216Enables you to make horizontal and vertical changes of directionModel ItemMS63 51511261MS100 51511261MS160 51521261246246MSMINI BUSBARRIGHT HORIZONTAL ELBOW9511269 216 693548648365365135NModel Item Weight (kg)MS63 51530351 1.600MS100 51500361 1.600MS160 51520351 2.600The R and L elbows are different due to the position of the linking block.88365135LEFT HORIZONTAL ELBOWModel Item Weight (kg)MS63 51530361 1.600MS100 51500362 1.600MS160 51520361 2.600N135NRIGHT VERTICAL ELBOWModel Item Weight (kg)MS63 51530451 1.600MS100 51500461 1.700MS160 51520451 2.700LEFT VERTICAL ELBOW365 8NModel Item Weight (kg)MS63 51530461 1.600MS100 51500462 1.700MS160 51520461 2.7<strong>001</strong>35CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE65


Feed unitsFEED UNIT IP 55 MS63 – MS 100Model Item MS 63 MS100 MS160 Weight (kg)DX 51511051 • • 1.732SX 51511052 • • 1.874Cable gland selection page 136DXSXFEED UNIT IP 55 MS160MAX. Ø 5585 125165 273 8SXDX1010Max. cablesection 35 mm 2Model Item MS 63 MS100 MS160 Weight (kg)DX 51521051 • 2.218SX 51521052 • 2.360Cable gland selection page 136Versions with switch-disconnector available on request.IP 55: the feed units are delivered with joint cover 515<strong>001</strong>61qty 2x =MAX. Ø 63200 273 8118 211SXDX1316Max. cablesection 70 mm 21010Max. cablesection 35 mm 2C<strong>EN</strong>TRE FEED UNIT MS63 - MS100Model Item MS 63 MS100 MS160 Weight (kg)IP 55 51511151 • • 3.500Cable gland selection page 1361808273270273 8qty 2x = MAX Ø 55qty 2x = MAX. Ø 551010Max. cablesection 35 mm 2C<strong>EN</strong>TRE FEED UNIT MS160Model Item MS 63 MS100 MS160 Weight (kg)IP 55 51521151 • 5.000Cable gland selection page 136400 2731310082738qty 2x = MAX. Ø 63120 200qty 2x = MAX. Ø 6316Max. cablesection 70 mm 21010Max. cablesection 35 mm 266 MS - MINI SBARRA


Tap-off boxesTAP-OFF BOXES97Energy withstand 400.000 A 2 sMAX power loss 10W (16W for long version)Totally insulated boxModel Item Weight (kg)EMPTY TAP-OFF BOX with 4 module DIN rail32A 51515071 0.680d1 MAX. = 38160TAP-OFF BOX with fuse carrier (10.3x38mm)32A 51515076 0.680150TAP-OFF BOX with D01 fuse carrier16 A 51515077 0.9506.56.5TAP-OFF BOX with D02 fuse carrier32A 51515078 0.950MSMINI BUSBARMax. cablesection 25 mm 2Tap-off box for 4 DIN rail modules cover junction32A 51515072 0.73097Model Item Weight (kg)Empty tap-off box with 8 module DIN rail (long version)32A 51515073 0.930d1 MAX. = 38160Tap-off box with 4 module DIN rail (long version)32A 51515074 0.960250Tap-off box with 8 module DIN rail (long version)32A 51515075 0.9906.56.5Max. cablesection 25 mm 2CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE67


Tap-off boxes with disconnectingdevice on coverWITH FUSE CARRIER (10.3X38mm)55160d 1= MAX. Ø 295.55.5Model Item Fuses Weight (kg)16 A 51515051 Ø 10.3x38* 0.908* Fuses not supplied145Max. cablesection 10 mm 2d 1= MAX. Ø 29WITH FUSE CARRIER (14X51mm)77221.51010Max. cablesection 35 mm 2Model Item Fuses Weight (kg)50A 51515052 Ø 14x51* 0.908* Fuses not supplied117d 1= MAX. Ø 3863A TAP-OFF BOXES109Energy withstand 400.000 A 2 SMAX power loss 20Wd 1= MAX. Ø 55283Model Item Weight (kg)Tap-off box with transparent cover63A 51515057 1.1<strong>001</strong>32d 1= MAX. Ø 55Tap-off box with transparent cover and hinged window (4 modules)63A 51515056 1.2<strong>001</strong>010Max. cablesection 35 mm 2Tap-off box with hinged window (7 modules)63A 51515067 1.10068 MS - MINI SBARRA


WITH DOOR FOR 16 DIN MODULESModel Item Weight (kg)63A 51515058 2,500Energy withstand 400.000 A 2 SMAX power loss 20WCable gland selection page 136d 1= MAX Ø 5528515578MSMINI BUSBAR1048751110Max. cablesection 35 mm 2CATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE69


AccessoriesIP 55 <strong>EN</strong>D COVERModel Item Weight (kg)All 51501351 0.5703104242SET OF IP 55 JOINT GASKETSModel Item Weight (kg)All 515<strong>001</strong>51 0.050One set for each linkIP 55 JOINT COVERModel Item Weight (kg)All 515<strong>001</strong>61 0.788One set for each link31082IP 55 OUTLET COVERModel Item Weight (kg)All 515<strong>001</strong>60 0.0616 every 3m straight element70 MS - MINI SBARRA


SUSP<strong>EN</strong>SION BRACKETModel Item Weight (kg)All 51002002 0.1<strong>001</strong> bracket every 2 metres80Slot 7x11Slot 7x11Slot 7x1113164Slot 7x116820Ø 7MSMINI BUSBARCATALOGUELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE71


72MR - MEDIUM RATING160 - 1000A


SECTION CONT<strong>EN</strong>TS74 General features80 Advantages84 Illustrated contentsMRMEDIUM RATING86 Trunking components94 Feed units and end covers97 Tap-off boxes102 Tap-off box installation diagram103 Fixing supports105 Determination of the measurements for special elements106 Riser mains installation107 SB/MR Adapter132 Technical information135 Determination of the operating current of a busbarLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE73


MRTechnical descriptionG<strong>EN</strong>ERAL FEATURESThe Zucchini MR (Medium Rating) line is the idealsolution for the distribution of power in medium –large industries, and for riser mains in commercialand service buildings (banks, insurance companies,trade and business centres, etc.).The main features of the MR range are:• speed, simplicity and flexibility when planning andinstalling and installing the lines;• availability in sizes ranging from 160A up to800A with aluminum alloy conductors and from250A up to 1000A with 99.9% electrolytic copperconductors;• availability of a wide selection of tap-off boxesfrom 16 A up to 1000A with the possibility ofhousing protective devices such as fuses, MCBs(Lexic range) and MCCB (DPX range);• compliance with standard IEC 60439-1 and 2;• rated at average room temperature of 40°C for ahigher performance level compared to the 35°Crating required by the standard;• Each trunking component (straight element,angle,...) is pre-equipped with a monobloc atone end and with an IP 55 joint cover placed atthe other end, thus permitting an easy and rapidinstallation.High-rise buildingsIndustriesStraight elementTap-off boxFeed unit74 MR - MEDIUM RATING


STRAIGHT ELEM<strong>EN</strong>TSThe components and the features of the MR straightelements are:• a casing made of Senzimir quality galvanized steelused as protective earth (PE);• overall dimensions: 75 to 135x196 mm;• painted casing available on request;• number of conductors: 4 with the same section(3P+N) with PE made from the casing or 5 whenusing MRfull (3P+N+PE), available in the aluminumor electrolytic copper version with 99.9% purity;• conductors insulators are made by fiberglassreinforced plastic material, ensuring a V1 selfextinguishingdegree (according to UL94), incompliance with the glow-wire test according toIEC 60695-2-10;• tap-off outlets with a constant centre distance of 1 mon both sides of the busbar (3+3 windows every 3m),set up for being connected to plug-in type tap-offboxes; These outlets open and close automaticallywhen inserting or pulling out a tap-off box;• “monobloc” electric junction system made witha silver coated copper plate system to connectconductors and PE in a fast and reliable way. The“monobloc” has shear-head bolts with a presettorque setting which ensure good, long-lastingelectrical continuity.• All components and accessories of the MR line areIP 55 when the plug outlet covers are installed onthe straight elements. Without plug outlet coversthere is an IP52 for “edgewise” installations, or IP40with a“flatwise” installation (outlets facing up).• The whole busbar is fire retardant in compliancewith the IEC 60332-3 standard.MRMEDIUM RATINGInstallation in medium-sized industriesRiser main installationsG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE75


MRTechnical descriptionFEED UNITSAllows you to electrically power the MR line througha cable line or directly connected to an electricdistribution board. The 160 and 250A feed unitshave terminals for cables up to 150mm 2 ; for higherratings, the cable connection to the feed unit requirescable lugs to be fastened to the provided spreaders.The MR line can be provided with centre feed unitsor end feed units with a switch-disconnector whichallows you to isolate the whole line for carryingout maintenance operations or layout changes, ifrequired.Feed unit<strong>EN</strong>D COVERThe end cover ensures the IP 55 protection degree atthe end of the line.End coverFIXING SUPPORTSIn order to fix the line to the structure of the building,directly or with wall / ceiling / beam supports, it isnecessary to use the bracket supports or verticalsuspension supports.Suspension bracket for verticalelements76 MR - MEDIUM RATING


TAP-OFF BOXESUsed for energizing three-phase loads from 16 A up to1000A; they can be divided into two big categories:1) Plug-in type tap-off boxes (from 16 A up to 630A)with the following features:• Intervention under load possible up to 32A;• disconnection device integrated into the cover ofthe boxes with a rating from 63A to 630A, ensuringautomatic absence of electric current when the coveris opened;• possibility of padlocking box cover in the opendisconnectedposition so that all maintenanceoperations of the loads connected to it can be carriedout safely;• the supplied PE contact (protective conductor) is thefirst to make an electrical connection when insertingthe box into the outlet and it is the last to disconnectwhen pulling it out;• all insulating plastic components are in compliancewith the IEC 60695-2-1 glow-wire test and rated V2self-extinguishing according to the UL94;• standard IP 55 degree of protection without usingadditional accessories;• availability of boxes in the following versions:- with a set of three fuse carriers- with Lexic MCBs- with EEC sockets and Schuko sockets- with AC23 switch disconnector and fuse carrier- for MCCBs.2) Boxes bolted onto the connection (from 630A to1000A) which include the following features:• very easy, fast and reliable installation;• high rated current;• rigid connection to the busbar through the use of amonobloc junction similar to the straight elementsystem;• possibility of removing the boxes only when thebusbar is not energized (isolated busbar);• availability of boxes in the following versions:- with AC23 switch disconnector and fuse carrier- with MCCBsMRMEDIUM RATINGTap-off box with the possibility of installingmodular circuit breakersTap-off box with integrateddisconnecting deviceG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE77


Trunking components andadditional elementsDepending on the different installation requirementsZucchini can provide various technical solutions:a) 90° elbows: available for carrying out changes ofdirection both horizontally and vertically. There is aquick connection, as for the straight elements.The standard degree of protection is IP 55;b) T-type and X-type elements, Z-type double elbowsavailable. The standard degree of protection is IP 55;c) straight elements with fire barrier (internal +external) S120 (certified for 120min).Tested in laboratories (in compliance with DINStandards 4102-9 and <strong>EN</strong> 1366-3) to confirm that,correctly installed, they maintain the intrinsic fireresistantproperties of the wall;d) straight elements with 5 outlets on one side; theyare ideal for riser mains or segments with a largenumber of derivations;e) straight elements with no outlets, used for energytransport only.The MR line is even more advantageous in verticalapplications (riser mains) as no thrust unit or thermalexpansion element is necessary. The MR monobloc isdesigned to compensate the thermal expansions of theconductors.IP 55 joint cover.Straight elements, with tapoffoutlets every 1000 mm.on both sides.Suspensionbracket.Tap-off box.PARTS OF THE LINEMetal end feed unitSwitchboard - transformer feed unitHorizontal angleVertical angle78 MR - MEDIUM RATING


MRMEDIUM RATINGTap-off box complete with terminals forcables of up to 25 mm 2 . Made from selfextinguishingplastic material, ensures highmechanical resistance and resistance tostatic currents. Plug-in type boxes can beinserted and removed when the busbar isenergized.Joint coverpre-installed on theelements.Feed units.End cover IP 55 outlet cover (accessory) Tap-off box Tap-off box with cover disconnectorG<strong>EN</strong>ERAL FEATURESLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE79


AdvantagesPRE-ASSEMBLED MONOBLOCAll trunking components (straight elements, angles, etc.) are provided witha pre-assembled monobloc which considerably speeds up the installation ofthe system and makes transportation and storage operations easier.EXTREMELY FAST INSTALLATIONThe monobloc and the “dynamometric” bolt allow a very fast installation ofthe whole line.DYNAMOMETRIC MONOBLOCTighten the “dynamometric” bolt on the monobloc until the head breaks toelectrically connect the elements. The breakage of the bolt head guaranteeslong-lasting reliability and safety.The connection is maintenance free.In case of a future intervention on the line, the monobloc must beretightened using the second bolt head with a torque wrench at the correctsettings: 34 Nm (up to 315 A Al / 400 A Cu) or 55 Nm(up to 800 A Al / 1000 A Cu)80 MR - MEDIUM RATING


CONNECTION FLANGESIf the monobloc has been tightened improperly, the head of thedynamometric bolt will prevent the mechanical coupling from closing. Theconnection fl anges and the seals serve as a protection for the elementduring transportation and ensure their degree of protection as well as theirmechanical rigidity when being installed.IP OF PROTECTIONThe MR line on “edgewise” position has a standard IP52 protection degree;by simply adding the plug-outlet covers to the tap-off outlets, the line canreach an IP55 degree of protection.MRMEDIUM RATINGEXCELL<strong>EN</strong>T FIRE RESISTANCEThe MR line has elements provided with a fl ame barrier (S120 accordingto DIN 4102-9 ISO 834) and structures which guarantee that the bus-linecontinues to function in case of fi re (E120 according to DIN 4102-12).The fi re load of the MR line is extremely low compared to the quantity ofplastic materials needed to insulate cables with the same capacity.G<strong>EN</strong>ERAL FEATURES 81LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


AdvantagesGLOW-WIRE TESTAll plastic materials are resistant and in compliance with the “glow-wire”test (IEC <strong>EN</strong>60439-2).VERSIONSThe MR symbol indicates a busbar with 4 conductors with an equal crosssection (3L+N), and the casing acts as the protective earth conductor (PE);the MRf (full) line has 5 conductors with an equal cross section (3L+N+PE).The MR and MRf lines are also available on request in a painted version (RALto be defi ned by the customer).SIMPLE AND RELIABLEThe “monobloc” connection of the MR line is able to compensate for anyheat expansion affecting the conductors, thus avoiding the need to insertspecial expansion elements even in considerably long systems.If the MR line is installed vertically (riser main) there is no need to installbusbar thrust units because the monobloc prevents the conductors fromsliding.82 MR - MEDIUM RATING


COMPATIBLE WITH THE SB RANGEThe tap-off boxes of the SB range can be installed without any modifi cationson the MR range. This allows existing systems to be extended.MAXIMUM STR<strong>EN</strong>GTHThe MR range has been designed and manufactured for heavy industrialenvironments. The degree of impact-resistance of the casing which housesthis line is the maximum stated in IEC <strong>EN</strong>60068-2-62: IK10.MRMEDIUM RATINGALUMINIUM AND COPPER RATINGAluminium 160 250 315 400 500 630 800 -Copper - 250 315 400 - 630 800 1000G<strong>EN</strong>ERAL FEATURES 83LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Line routePage ...11510210510610611011763-160A tap-off box119103109115121114 102117110105 119104106S120 element with internal flame barrierRight horizontal elbowRight vertical elbowSpecial element > 1500 mmWall fixing bracketStraight element 3000 mm32A tap-off box with EEC socketSuspension bracketOutlet cover IP55Left end feed unit84 MR - MEDIUM RATING


Element with 5 outletson one side630-1000A bolton type boxesMRMEDIUM RATINGEnd cover250-400A tap-off boxSuspension bracket forvertical elementsSwitch disconnector“Cross” elementSpecial element < 1500 mmRight vertical elbowG<strong>EN</strong>ERAL FEATURES 85LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


TrunkingcomponentsIP551000 1000 37562575 1353 METRE STRAIGHT ELEM<strong>EN</strong>TS WITH 3+3 OUTLETS196162160-315A Al250-400A Cu* only on MRfL(PE)*L2NL3pe196162400-800A Al630-1000A CuStraight element with tap-off outlets in fixed position.Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 3000 3 + 3 5040 01 01 19.9 - -250 3000 3 + 3 5040 01 02 20.9 5540 01 02 25.7315 3000 3 + 3 5040 01 03 22.8 5540 01 03 28.1400 3000 3 + 3 5040 01 04 33.8 5540 01 04 36.9500 3000 3 + 3 5040 01 08 37.5630 3000 3 + 3 5040 01 05 41.7 5540 01 05 56.0800 3000 3 + 3 5040 01 06 44.3 5540 01 06 72.11000 3000 3 + 3 5540 01 07 83.7625500 500 500 500 3753 METRE STRAIGHT ELEM<strong>EN</strong>TS WITH 5 OUTLETS ON ONE SIDEElement with outlets on one side which can be used for riser mains(see page 122).Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 3000 5 + 0 5040 02 51 19.9250 3000 5 + 0 5040 02 52 20.9 5540 02 52 25.7315 3000 5 + 0 5040 02 53 22.8 5540 02 53 28.1400 3000 5 + 0 5040 02 54 33.8 5540 02 54 36.9500 3000 5 + 0 5040 02 58 37.5630 3000 5 + 0 5040 02 55 41.7 5540 02 55 56.0800 3000 5 + 0 5040 02 56 44.3 5540 02 56 72.11000 3000 5 + 0 5540 02 57 83.786 MR - MEDIUM RATING


TableConversionCodeConductors Casing CodeMR 4 Galvanized - - - 0 ---MRf 5 Galvanized - - -1---MR-P 4 Painted - - -2 ---MRf-P 5 Painted - - -3 ---3 METRE STRAIGHT ELEM<strong>EN</strong>TS WITHOUT OUTLETS150 9020530003135160-315A Al • 250-400A Cu3135400-800A Al • 630-1000A Cu110135 75196Element used for transport/feeder purposes with the possibility of aderivation between two elements (see bolt-on tap-off boxes).Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 3000 0 5040 02 41 19.9250 3000 0 5040 02 42 20.9 5540 02 42 25.7315 3000 0 5040 02 43 22.8 5540 02 43 28.1400 3000 0 5040 02 44 33.8 5540 02 44 36.9500 3000 0 5040 02 48 37.5630 3000 0 5040 02 45 41.7 5540 02 45 56.0800 3000 0 5040 02 46 44.3 5540 02 46 72.11000 3000 0 5540 02 47 83.7MRMEDIUM RATINGSTRAIGHT ELEM<strong>EN</strong>TS FROM 1501 TO 2999 mm WITH 2+2 OUTLETSStraight element with tap-off outlets in fixed position.625375Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 1501-2999 2 + 2 5040 01 51 13.6250 1501-2999 2 + 2 5040 01 52 14.1 5540 01 52 16.5315 1501-2999 2 + 2 5040 01 53 14.9 5540 01 53 17.7400 1501-2999 2 + 2 5040 01 54 23.3 5540 01 54 22.0500 1501-2999 2 + 2 5040 01 58 25.2630 1501-2999 2 + 2 5040 01 55 26.9 5540 01 55 34.3800 1501-2999 2 + 2 5040 01 56 28.0 5540 01 56 42.21000 1501-2999 2 + 2 5540 01 57 47.8In your Purchase Order please specify the required length(see page 105: How to take measurements).CATALOGUE 87LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


TrunkingcomponentsSTRAIGHT ELEM<strong>EN</strong>TS FROM 1501 TO 2999 mm WITHOUT OUTLETSElement used for transport/feeder purposes. Tap-off point possible on thejunction (see bolt-on tap-off boxes).205901501501 A 2999 110160-315A Al • 250-400A Cu135 75 196Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 1501-2999 0 5040 01 21 13.6250 1501-2999 0 5040 01 22 14.1 5540 01 22 16.5315 1501-2999 0 5040 01 23 14.9 5540 01 23 17.7400 1501-2999 0 5040 01 24 23.3 5540 01 24 22.0500 1501-2999 0 5040 01 28 25.2630 1501-2999 0 5040 01 25 26.9 5540 01 25 34.3800 1501-2999 0 5040 01 26 28.0 5540 01 26 42.21000 1501-2999 0 5540 01 27 47.8In your Purchase Order please specify the required length (see page 105: How to takemeasurements).400-800A Al • 630-1000A CuSTRAIGHT ELEM<strong>EN</strong>TS FROM 1000 TO 1500 mm WITH 1+1 OUTLETSStraight element with tap-off outlets in fixed position.375Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 1000-1500 1 + 1 5040 01 41 13.6250 1000-1500 1 + 1 5040 01 42 14.1 5540 01 42 16.5315 1000-1500 1 + 1 5040 01 43 14.9 5540 01 43 17.7400 1000-1500 1 + 1 5040 01 44 23.3 5540 01 44 22.0500 1000-1500 1 + 1 5040 01 48 25.2630 1000-1500 1 + 1 5040 01 45 26.9 5540 01 45 34.3800 1000-1500 1 + 1 5040 01 46 28.0 5540 01 46 42.21000 1000-1500 1 + 1 5540 01 47 47.8In your Purchase Order please specify the required length (see page 105: How totake measurements).STRAIGHT ELEM<strong>EN</strong>TS FROM 600 TO 1500 mm WITHOUT OUTLETSElement used for transport/feeder purposes. Tap-off point possible on thejunction (see bolt-on tap-off boxes).20590from 600 to 15<strong>001</strong>60-315A Al • 250-400A Cu11019675Rating Length No. Item Weight Item Weight(A) (m) outlets (kg) (kg)AluminiumCopper160 600-1500 0 5040 01 11 13.6250 600-1500 0 5040 01 12 14.1 5540 01 12 16.5315 600-1500 0 5040 01 13 14.9 5540 01 13 17.7400 600-1500 0 5040 01 14 23.3 5540 01 14 22.0500 600-1500 0 5040 01 18 25.2630 600-1500 0 5040 01 15 26.9 5540 01 15 34.3800 600-1500 0 5040 01 16 28.0 5540 01 16 42.21000 600-1500 0 5540 01 17 47.8150400-800A Al • 630-1000A Cu135In your Purchase Order please specify the required length (see page 105: How to takemeasurements).88 MR - MEDIUM RATING


A 200 630FIRE BARRIER EI120When ordering, specify the dimension A = ….. mm of the element that will beequipped with the fire barrier.158244554EFB01160 - 315A Al250 - 400A Cu218554EFB01400 - 800A Al630 - 1000A Cu244AlluminiumCopperexternal internal external internal160 554EFB01 554IFB01250 554EFB01 554IFB02 554EFB01 554IFB01315 554EFB01 554IFB03 554EFB01 554IFB02400 554EFB02 554IFB04 554EFB01 554IFB05500 554EFB02 554IFB06630 554EFB02 554IFB07 554EFB02 554IFB04800 554EFB02 554IFB08 554EFB02 554IFB061000 554EFB02 554IFB07Conductors CodeMR 4 ------0 -MRf 5 ------1-MRMEDIUM RATINGIn your Purchase Order please specify the required position of the internal firebarrier. Take the measurement as shown in the Figure. The internal fire barrier is630mm long.IP55 OUTLET COVERSuitable for all MR versions.ItemWeight (kg)50403601 0.10CATALOGUE 89LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Elbow trunkingcomponents300300HORIZONTAL ELBOW (300 + 300 mm) - RIGHTRating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 03 01 8.1250 5040 03 02 8.2 5540 03 02 16.5315 5040 03 03 8.4 5540 03 03 17.7400 5040 03 04 14.5 5540 03 04 22.0500 5040 03 08 14.9630 5040 03 05 15.4 5540 03 05 34.3800 5040 03 06 15.7 5540 03 06 42.21000 5540 03 07 47.8HORIZONTAL ELBOW (300 + 300 mm) - LEFTRating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 03 11 8.1250 5040 03 12 8.2 5540 03 12 9.2315 5040 03 13 8.4 5540 03 13 9.6400 5040 03 14 14.5 5540 03 14 11.0500 5040 03 18 14.9630 5040 03 15 15.4 5540 03 15 18.7800 5040 03 16 15.7 5540 03 16 21.41000 5540 03 17 23.3300300VERTICAL ELBOW (300 + 300 mm) - RIGHTRating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 04 01 8.1250 5040 04 02 8.2 5540 04 02 9.2315 5040 04 03 8.4 5540 04 03 9.6400 5040 04 04 14.5 5540 04 04 11.0500 5040 04 08 14.9630 5040 04 05 15.4 5540 04 05 18.7800 5040 04 06 15.7 5540 04 06 21.41000 5540 04 07 23.3VERTICAL ELBOW (300 + 300 mm) – LEFTRating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 04 11 8.1250 5040 04 12 8.2 5540 04 12 9.2315 5040 04 13 8.4 5540 04 13 9.6400 5040 04 14 14.5 5540 04 14 11.0160 5040 04 18 14.9630 5040 04 15 15.4 5540 04 15 18.7800 5040 04 16 15.7 5540 04 16 21.41000 5540 04 17 23.390 MR - MEDIUM RATING


TableConversionCodeConductors Casing ItemMR 4 Galvanized - - - 0 ---MRf 5 Galvanized - - -1---MR-P 4 Painted - - -2 ---MRf-P 5 Painted - - -3 ---ABSPECIAL HORIZONTAL ELBOW - RIGHTRating (A) Item ItemAluminiumCopper160 5040 03 21250 5040 03 22 5540 03 22315 5040 03 23 5540 03 23400 5040 03 24 5540 03 24500 5040 03 28630 5040 03 25 5540 03 25800 5040 03 26 5540 03 261000 5540 03 27SPECIAL HORIZONTAL ELBOW - LEFTRating (A) Item ItemAluminiumCopper160 5040 03 31250 5040 03 32 5540 03 32315 5040 03 33 5540 03 33400 5040 03 34 5540 03 34500 5040 03 38630 5040 03 35 5540 03 35800 5040 03 36 5540 03 361000 5540 03 37Dimensions [ mm]min MAX250 ≤ A ≤ 900250 ≤ B ≤ 900In your Purchase Order please specify therequired length (see page 105: How to takemeasurements).MRMEDIUM RATINGABSPECIAL VERTICAL ELBOW - RIGHTRating (A) Item ItemAluminiumCopper160 5040 04 21250 5040 04 22 5540 04 22315 5040 04 23 5540 04 23400 5040 04 24 5540 04 24500 5040 04 28630 5040 04 25 5540 04 25800 5040 04 26 5540 04 261000 5540 04 27SPECIAL VERTICAL ELBOW - LEFTRating (A) Item ItemAluminiumCopper160 5040 04 31250 5040 04 32 5540 04 32315 5040 04 33 5540 04 33400 5040 04 34 5540 04 34500 5040 04 38630 5040 04 35 5540 04 35800 5040 04 36 5540 04 361000 5540 04 37Dimensions [ mm]min MAX300 ≤ A ≤ 900300 ≤ B ≤ 900In your Purchase Order please specify therequired length (see page 105: How to takemeasurements).CATALOGUE 91LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Trunking componentsDouble elbowsDOUBLE HORIZONTAL ELBOWRight + LeftDOUBLE VERTICAL ELBOWRight + LeftRating (A) Weight (kg) Weight (kg)160 10.29250 10.55 12.23315 11.06 12.97400 18.37 15.72500 19.50630 20.55 25.77800 21.20 30.881000 34.55Rating (A) Weight (kg) Weight (kg)160 10.29250 10.55 12.23315 11.06 12.97400 18.37 15.72500 19.50630 20.55 25.77800 21.20 30.881000 34.55Left + RightLeft + Right(A)(C)Rating (A) Weight (kg) Weight (kg)160 10.29250 10.55 12.23315 11.06 12.97400 18.37 15.72500 19.50630 20.55 25.77800 21.20 30.881000 34.55(A)(C)Rating (A) Weight (kg) Weight (kg)160 10.29250 10.55 12.23315 11.06 12.97400 18.37 15.72500 19.50630 20.55 25.77800 21.20 30.881000 34.55(B)Dimensions [mm]min. MAX.250 A, B,C 900(B)Dimensions [ mm]min. MAX.300 A, B,C 900DOUBLE VERTICAL ELBOW + HORIZONTAL ELBOWDOUBLE HORIZONTAL ELBOW + VERTICAL ELBOWDX + DXDX + SXAluminiumRating (A) Weight (kg)160 10.29250 10.55315 11.06400 18.37500 19.50630 20.55800 21.201000 34.55DX + DXDX + SXAluminiumRating (A) Weight (kg)160 10.29250 10.55315 11.06400 18.37500 19.50630 20.55800 21.201000 34.55SX + DX(A)SX + SX(C)CopperRating (A) Weight (kg)250 12.23315 12.97400 15.72630 25.77800 30.881000 34.55SX + DX(A)SX + SX(C)CopperRating (A) Weight (kg)250 12.23315 12.97400 15.72630 25.77800 30.881000 34.55(B)Dimensions [ mm]min. MAX.300 A, B,C 900(B)Dimensions [ mm]min. MAX.300 A, B,C 90092 MR - MEDIUM RATING


TableConversionCodeConductors Casing ItemMR 4 Galvanized - - - 0 ---MRf 5 Galvanized - - -1---MR-P 4 Painted - - -2 ---MRf-P 5 Painted - - -3 ---HORIZONTAL “TEE” ELEM<strong>EN</strong>T (300 + 300 + 300 mm)DX Rating (A) DX 1 DX 2 SX 1 SX 2 Weight (kg)Aluminium160 5040 07 01 5040 07 11 5040 07 21 5040 07 31 11.2250 5040 07 02 5040 07 12 5040 07 22 5040 07 32 11.4315 5040 07 03 5040 07 13 5040 07 23 5040 07 33 11.8400 5040 07 04 5040 07 14 5040 07 24 5040 07 34 18.4500 5040 07 08 5040 07 18 5040 07 28 5040 07 38 19.5630 5040 07 05 5040 07 15 5040 07 25 5040 07 35 20.0800 5040 07 06 5040 07 16 5040 07 26 5040 07 36 20.5SX 300 300DX SX 300Rating (A) DX 1 DX 2 SX 1 SX 2 Weight (kg)Copper250 5540 07 02 5540 07 12 5540 07 22 5540 07 32 12.8315 5540 07 03 5540 07 13 5540 07 23 5540 07 33 13.4400 5540 07 04 5540 07 14 5540 07 24 5540 07 34 15.7630 5540 07 05 5540 07 15 5540 07 25 5540 07 35 24.4800 5540 07 06 5540 07 16 5540 07 26 5540 07 36 28.51000 5540 07 07 5540 07 17 5540 07 27 5540 07 37 31.3The various versions allow any type of path and are different from the monoblocsposition and branch point.Special dimensions are available on request.MRMEDIUM RATINGCROSS ELEM<strong>EN</strong>T (300 + 300 + 300 + 300 mm)300300Rating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 30 01 15.5250 5040 30 02 15.7 5540 30 02 17.6315 5040 30 03 16.1 5540 30 03 18.4400 5040 30 04 27.5 5540 30 04 21.1500 5040 30 08 29.3630 5040 30 05 29.1 5540 30 05 35.2800 5040 30 06 29.5 5540 30 06 40.21000 5540 30 07 43.7300300CATALOGUE 93LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Feed unitsand end coversRIGHT FEED UNIT550cablesinputCable connection: max. sect. (3x120mm 2 + 1x70mm 2 ) or (3x150mm 2 ) max PG 48200350550350 2<strong>001</strong>75240240 100240 100Rating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 11 01 5.70250 5040 11 02 5.85 5540 11 02 6.10LEFT FEED UNITRating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 11 11 6.80250 5040 11 12 6.85 5540 11 12 7.20<strong>EN</strong>D COVERRating (A) Capacity (A) Item Weight (kg)AluminiumCopper160 - 250 - 315 Al 250 - 315 - 400 Cu 5040 31 01400 - 630 - 800 Al 630 - 800 - 1000 Cu 5040 31 02Suitable for all MR versions.Ensures the closure and the IP55 degree of protection (<strong>EN</strong> 60529).94 MR - MEDIUM RATING


TableConversionCodeConductors Casing ItemMR 4 Galvanized - - - 0 ---MRf 5 Galvanized - - -1---MR-P 4 Painted - - -2 ---MRf-P 5 Painted - - -3 ---METAL FEED UNITS - RIGHTUpon request, the feed units are available with AC23 switch disconnector installed.40250 600850290 400Rating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 11 21 16.64250 5040 11 22 16.76 5540 11 22 17.37315 5040 11 23 17.03 5540 11 23 17.70400 5040 11 24 18.32 5540 11 24 18.88500 5040 11 28 20.00630 5040 11 25 19.43 5540 11 25 21.17800 5040 11 26 19.80 5540 11 26 23.301000 5540 11 27 24.83The box is shipped with its body part positioned on the inside to reduce its overalldimensions. Take it out and screw it into the position shown here.Back side cable entry hole: 180x290 mm. The dimensions of the bars and holesare described in the corresponding rating of the Board/Transf on page 96.METAL FEED UNITS - LEFT290 40060085025040The box is shipped with its body part positioned on the inside to reduce its overalldimensions. Take it out and screw it into the position shown here.Rating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 11 31 17.74250 5040 11 32 17.76 5540 11 32 18.47315 5040 11 33 17.83 5540 11 33 18.70400 5040 11 34 23.22 5540 11 34 19.58500 5040 11 38 23.20630 5040 11 35 23.63 5540 11 35 26.07800 5040 11 36 23.70 5540 11 36 27.801000 5540 11 37 29.03Back side cable entry hole: 180x290 mm. The dimensions of the bars and holesare described in the corresponding rating of the Board/Transf on page 96.MRMEDIUM RATINGCATALOGUE 95LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Feed unitsTableConversionCodeConductors Casing ItemMR 4 Galvanized - - - 0 ---MRf 5 Galvanized - - -1---MR-P 4 Painted - - -2 ---MRf-P 5 Painted - - -3 ---INTERMEDIATE FEED UNITUsed to power a busbar from any intermediate point on the connection betweentwo elements. The intermediate end feed unit is also used for reducing thevoltage drop of the line. (see page 135).290400600Rating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 12 01 17.27250 5040 12 02 17.13 5540 12 02315 5040 12 03 16.88 5540 12 03400 5040 12 04 22.06 5540 12 04500 5040 12 08 22.65630 5040 12 05 23.24 5540 12 05800 5040 12 06 23.02 5540 12 061000 5540 12 07NOTE: Back side cable entry hole: 180 x 290 mmBOARD/TRANSFORMER FEED UNIT - RIGHTFeed unit for direct connection of the busbar to an electric board or to the LVterminals of a distribution transformer.25014025065Rating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 10 01 4.9250 5040 10 02 5.1 5540 10 02 5.7315 5040 10 03 5.3 5540 10 03 6.0400 5040 10 04 6.4 5540 10 04 9.2500 5040 10 08 6.9630 5040 10 05 7.5 5540 10 05 9.3800 5040 10 06 7.9 5540 10 06 11.41000 5540 10 07 12.914065BOARD/TRANSFORMER FEED UNIT - LEFTFeed unit for direct connection of the busbar to an electric board or to the LVterminals of a distribution transformer.280340 Ø975 75 75 75125 12520 Ø11Ø1120305090Al CuMR 160A 250A 250A 315A315A 400AMR 400A 630A 500A 800A630A 1000A800ARating (A) Item Weight (kg) Item Weight (kg)AluminiumCopper160 5040 10 11 6.0250 5040 10 12 6.1 5540 10 12 6.7315 5040 10 13 6.2 5540 10 13 7.0400 5040 10 14 11.3 5540 10 14 7.8500 5040 10 18 11.4630 5040 10 15 11.7 5540 10 15 14.2800 5040 10 16 11.8 5540 10 16 15.91000 5540 10 17 17.196 MR - MEDIUM RATING


Tap-off boxes withoutdisconnecting deviceSTANDARD VERSIONS11100Rating Protective component and setup Item Weight (kg)32A DIN Rail (8 modules) 5041 40 61 1.60121632A 3x10.3 x 38mm - Fuse carrier 5041 40 62 1.751226010032A Transparent door and DIN Rail (4 modules) 5041 40 63 1.70132A Transparent door and DIN Rail (8 modules) 5041 40 64 1.70216135016A 3xD01 - Fuse carrier and DIN Rail (8 modules) 5041 40 68 2.07Fuses not suppliedCable gland included1Fuses not suppliedCable gland included232A 3xD02 - Fuse carrier and DIN Rail (8 modules) 5041 40 69 2.1532A DIN Rail (12 modules) 5041 40 71 1.90MRMEDIUM RATING232A Transparent door and DIN Rail (12 modules) 5041 40 75 2.05WITH INTERNAL WIRING1Fuses not supplied2Fuses not supplied2Fuses not supplied2Fuses not suppliedRating Protective component and setup Item Weight (kg)16A 3xD01 - Fuse carrier, 5041 41 11 2.29transparent door,3 16A standard Schuko sockets16A 3xD01 - Fuse carrier, 5041 41 62 2.60transparent door,1 CEE 3P+N+T 16A socket32A 3xD02 - Fuse carrier, 5041 41 71 2.79transparent door,1 CEE 3P+N+T 32A socket16A 3xD01 - Fuse carrier, 5041 41 61 2.96transparent door, and DIN Rail.2 CEE 3P+N+T 16A socketsBearable energy400 . 10 3 A 2 sMax. power lossesVersion 1216W20WModules 17.5 mm.CATALOGUE 97LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Tap-off boxes withoutdisconnecting deviceWITH INTERNAL WIRING11<strong>001</strong>Rating Protective component and setup Item Weight (kg)16A 4P 16A MCB curve B, 5041 41 30 2.29transparent door and DIN Rail (4 modules)121616A 4P 16A MCB curve C, 5041 41 28 2.29transparent door and DIN Rail (4 modules)260132A 4P 32A MCB curve C, 5041 41 44 2.36transparent door and DIN Rail (4 modules)116A (1P 16A MCB curve B) 5041 41 22 2.13transparent door and DIN Rail (4 modules)3 16A Schuko sockets116A (1P+N 16A MCB curve B) 5041 41 21 2.10transparent door and DIN Rail (4 modules)3 16A Schuko sockets2Fuses not supplied100216A (4P 16A MCB curve C) 5041 41 85 3.23transp. door (8 modules),2 EEC 3P+N+T 16A sockets2221635016A 3x (1P+N 16A MCB curve C) 5041 41 81 3.05transp. door (8 modules),3 EEC 2P+T 16A sockets32A (4P 32A MCB curve C) 5041 41 92 3.06transp. door (8 modules),1 EEC 3P+N+T 32A sockets116A Transparent door (4 modules), 5041 42 21 1.833 16A Schuko sockets116A Set up for MCB (8 modules) 5041 42 51 1.943 16A Schuko sockets216A Set up for MCB (8 modules) 5041 42 81 2.553 EEC 2P+T 16A sockets216A Set up for MCB (8 modules) 5041 42 82 2.492 EEC 3P+N+T 16A sockets232A Set up for MCB (8 modules) 5041 42 91 2.592 EEC 3P+N+T 32A socketsBearable energy400 . 10 3 A 2 sMax. power lossesVersion 1 16W2 20WModules 17.5 mm98 MR - MEDIUM RATING


A3B44513020032A3115 40025063-160A 4WITH FUSE CARRIERThese tap-off boxes are made from thermoplastic material strengthened withfibreglass. They fit all MR versions and are provided with a set of three fusecarriers.Rating (A) Fuse carrier Figure 5 conductors code Weight (kg)MR - MRf32 ø10.3x38 A 5565 50 51 0.8563 ø22x58 B 5505 50 52 3.20125 NH 0 B 5505 50 53 3.35125 NH 00 B 5505 50 57 3.35160 NH 0 B 5040 40 04 3.60250 NH 1 F 5565 50 57 14.90400 NH 2 F 5565 50 58* 15.80* Neutral section 50%.FOR MCBS WITH TRANSPAR<strong>EN</strong>T DOORC4D4All tap-off boxes with a transparent door are equipped with a DIN 50022 rail formodular devices. The transparent door of the box lets you access the equipmentwithout opening the cover, thus isolating the load connected.Rating (A) DIN modules Figure 5 conductors item Weight (kg)MR - MRf63 8 D 5505 50 86 3.2063 11 E 5505 50 88 3.60125 8 D 5505 50 56 3.20125 11 E 5505 50 68 3.60125 4 C 5505 50 66 3.<strong>001</strong>60 4 C 5040 40 24 3.60400 7 G 5505 50 70* 13.40400 11+11 H 5505 50 71* 15.30* Neutral section 50%.MRMEDIUM RATINGE4200 560EMPTY READY FOR MCBSThese boxes can be installed on the tap-off outlets of the MR. They canbe plugged in and unplugged from the busbar only when the cover of thebox is open i.e. when the tap-off is isolated. Boxes can be installed anddisconnected from the energized busbar. The same box can be installed bothon Aluminium and Copper conductors.F5250-400A3005Rating (A) Info Figure 5 conductors item Weight (kg)MR - MRf125 empty B 5505 50 55 2.90400 empty F 5565 50 59* 14.30* Neutral section 50%.G5H5CATALOGUE 99LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Tap-off boxes with disconnectingdevice on the coverWITH FUSE CARRIERTap-off box with galvanized and painted steel sheet structure. Metal boxesare suitable for heavy loads and are used to shield electric fields caused byflows of current.P6185Side cables input70 x 105400QR78Side cablesinput150 x 220Rating (A) Fuse Figure 5 conductors item Weight (kg)PE + FE **63 CH 22 (ø22x58) P 5041 40 21 8.75125 NH 00 P 5041 40 22 8.90160 NH 00 P 5041 40 23 9.10250 NH 2 Q 5041 40 24400 NH 2 Q 5041 40 26630 NH 3 R 5041 40 252406 PWITH SWITCH DISCONNECTOR (AC23)250600Tap-off box with galvanized and painted steel sheet structure. Metal boxesare suitable for heavy loads and are used to shield electric fields caused byflows of current.360284 7504107QRating (A) Fuse Figure 5 conductors itemPE + FE **63 NH00 P 5041 16 01125 NH00 P 5041 16 22160 NH0 P 5041 16 23250 NH1 Q 5041 16 24400 NH2 R 5041 16 25630 NH3 R 5041 16 46These tap-off boxes are equipped with a switch disconnector (AC23) and a fusecarrier. The disconnector switch is operated through a rotary handle on the cover.Note: It is not possible to open, close, install or pull out the tap-off box if theswitch is in “ON” position.8REMPTY VERSIONThese boxes can be installed on the tap-off outlets of the MR. They canbe plugged in and unplugged from the busbar only when the cover of thebox is open i.e. when the tap-off is isolated. Boxes can be installed anddisconnected from the energized busbar. The same box can be installed bothon Aluminium and Copper conductors.Rating (A) Figure 5 conductors itemPE + FE **63 P 5041 40 01125 P 5041 40 02160 P 5041 40 03250 Q 5041 40 04630 R 5041 40 05“PE+FE” tap-off boxes have separate terminals for the two earths whereas the“PE” boxes have parallel earths (casing and conductor). They can be customizedwith MCBs by various manufacturers. Boxes available with factory installed circuitbreakers.* PE Protective earthing** FE Functional earthing100 MR - MEDIUM RATING


Tap-off boxesbolt-on typeWITH SWITCH DISCONNECTOR AND FUSE CARRIER“Bolt-on” tap-off boxes. They make use of the joint between straight elementsas a connection for the junction. As this connection affects live conductors, itcan NOT be carried out when the line is energized - the line has to be isolated.9 10Rating (A) Dimension Circ. breaker Fuse Item ItemAluminium 630 800630 9 AC23 NH3 5040 18 01 5040 18 02800 10 AC23 NH4 - 5040 18 041000 10 AC23 - -280 750Rating (A) Dimension Circ. breaker Fuse Item Item ItemCopper 630 800 1000630 9 AC23 NH3 5540 18 01 5540 18 02 5540 18 03800 10 AC23 NH4 - 5540 18 04 5540 18 051000 10 AC23 NH4 - - 5540 18 064009630A300 1050Cable entry plate (mm)Type 910180 x 290210 x 380450MRMEDIUM RATING10800-1000ACATALOGUE 101LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Tap-off boxinstallationSTRAIGHT ELEM<strong>EN</strong>T WITH 3 OUTLETSEdgewiseThe numbers in the circles refer to the dimensions of the tap-offboxes. (see previous pages)Riser mains9 101 23 45 67 81 23 45 61 23 45 67 81 23 45 67 81 23 45 61 23 45 67 81 2 3 45 6 7 81 2 34 5 61 2 34 5 61 2 34 5 61 2 3 45 6 7 81 2 34 5 69910STRAIGHT ELEM<strong>EN</strong>T WITH 5 OUTLETSOn one sideThe numbers in the circles refer to the dimensions of the tap-offboxes. (see previous pages)Riser mains1 2 34 5 61 2 34 5 69 101 23 45 61 23 45 61 23 45 61 23 45 61 23 45 61 2 34 5 61 2 34 5 6NOTUSABL<strong>EN</strong>OTUSABLE1 2 34 5 61 2 34 5 6In elements with 5 outlets, tap-off boxes with dimension5 do not allow the possibility of installing other boxes onthe next outlet1 2 34 5 691 2 34 5 6910102 MR - MEDIUM RATING


FixingelementsSUSP<strong>EN</strong>SION BRACKETSA - Bslot 9 x 30C40slot 9 x 30slot 11 x 33Rating Installation Figure Item Weight (kg)Al Cu160 250250 315 1 bracket every 2 metres of line A 5063 20 01 0.55315 400400 630500630 800 1 bracket every 2 metres of line B 5063 20 03 0.60800 10<strong>001</strong>48 20811217283Wall spacer. Required when the bracket needs to be fixed directly to the wall.40 mm wall spacer C 5063 22 05 0.05260146260146206143slot 9 x 15ABCSUSP<strong>EN</strong>SION BRACKETS FOR VERTICAL ELEM<strong>EN</strong>TSSuspension bracket for vertical elements. Suitable for riser mains up to 4 mand for weights up to 300 kg. It is to be used together with 50632<strong>001</strong>/3.Installation Usage Figure Item Weight (kg)1 bracket at the base of the riser mains max 4 m. D 5040 37 11 1.05MRMEDIUM RATINGDSUSP<strong>EN</strong>SION BRACKETS WITH SPRINGS FOR VERTICAL ELEM<strong>EN</strong>TSSuspension bracket with tie-rods for riser mains. This bracket is used invertical applications. Use one bracket every 300 Kg (see weight table).Installation Usage Figure Item Weight (kg)1 bracket every 300 kg. Section longer E 5040 37 12 1.20than 4 m.EL11x25450 / 550 / 750WALL BRACKET HOLDERAdjustable arm both in height and in depth. The bracket holder can be combinedwith the MR - MS - TS brackets.P5<strong>001</strong>705025x74060Arm length Load on end Item Weight (kg)L= 0.45 m p max= 80 kg 5063 22 12 2.80L= 0.55 m p max= 68 kg 5063 22 13 3.00L= 0.75 m p max= 50 kg 5063 22 14 3.50CATALOGUE 103LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


FixingelementsCEILING BRACKET HOLDERLA98240slots 11 x 259813010057Ceiling bracket holder with a base to be fixed to the ceiling and a drilledU-shaped section bar available in various lengths. The section bar holes aresuitable for being installed with the MR brackets.Components Length Figure Item Weight (kg)Ceiling flange A 5063 22 01 2.80U-shaped bar L= 0.50 B 5063 22 02 3.00U-shaped bar L= 1 C 5063 22 03 3.50U-shaped bar L= 2 D 5063 22 04 3.50BCD5030500 / 1000 / 2000ø 11100ø 8.2BEAM BRACKET HOLDERBracket holder for beam fixing. This bracket holder has a bracket and twoclamps that are hooked to the wings of the beam.45Components Figure Item Weight (kg)Beam bracket base p max= 65 kg A 5063 22 10 0.90Beam clamp B 5063 22 11 0.9040BAP540147ø7 8.5x136517550104 MR - MEDIUM RATING


Determination of the measurementsfor special elementsAlways takemeasurements on thelong side on the metalcasing as shown in thefigure. For simplicity’ssake, it will bereferred to as “longcasing”STRAIGHT ELEM<strong>EN</strong>TSThe length of thestraight elementscan range from 600mm to 3000 mm.LELBOWSAABBWhen usingelbows, thedimension shouldbe measured fromthe long casingto the axis of theelement.BBMRMEDIUM RATINGAAMINIMUM FIXING DISTANCESMinimum fixing distancesWall fixingCeiling fixingmin.110 mmOKWallSpacer5063 22 05min.80 mmDo not fix the bracket directlyon the wall. Use the specialspacer 5063 22 05.CATALOGUE 105LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


RisingmainsL1 PE L2 N L3–How to design the systemUse a LH end feed unit.This allows the neutral bar to be positionedon the right side of the busbar, hence thecable exit of the tap-off boxes is locateddownwards.Use one or more suspension brackets forthe vertical elements, according to theweight of the whole rising mains.For risers that are shorter than 4 metres,fix to the base with code 50403711; whenlonger, use a suspension bracket code50403712 every 300 kg of rising main.Use a standard suspension bracket witha 40mm spacer every 2 metres of risingmains.Use straight elements with 5 outlets onone side.Use a straight element with fire barrier foreach compartment floor.It is necessary to specify the position of theinternal fire barrier before placing an order(see page 59).The tap-off boxes can be installed in thetap-off outlets and near the connectionbetween the elements.At the end of the riser mains, position theIP55 end cover.Before installing the end cover remove themonobloc located on the last element.Put the outlet covers into the tap-offoutlets in order to guarantee the IP55degree of protection.106 MR - MEDIUM RATING


SB/MR ADAPTER ELEM<strong>EN</strong>TSB MRThe old SB line has now been replaced by the MR range, hence itis no longer possible to find elements and accessories for it. If it isnecessary to replace or add some trunking components to the SBline, there is an adapter that can make it compatible with the MRline. Tap-off boxes and fixing accessories are compatible betweenthe two lines.How to arrange the itemMRConductors0 Aluminium5 CopperCasing / No. of conductor0 Galvanized1 Full Galvanized2 Painted3 Full Painted L1PEL2NL3SBSXType2 Right3 LeftRatingL1PEL2NL3SBDX1 160A2 250A3 315A4 400A5 630A6 800A7 1000A8 500AItem example50400226 meansAluminiumGalvanizedR type800A55420235 meansCopperFull GalvanizedL type630AMRMEDIUM RATING3501200600 25040290400CATALOGUE 107LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


108TS - TROLLEY SYSTEM63 - 250A


SECTION CONT<strong>EN</strong>TS110 General features116 TS5 Trunking components118 TS5 Accessories120 TS250 Trunking components121 TS250 Accessories123 MTS63 Trunking components124 MTS63 Trunking accessoriesTSTROLLEY SYSTEM125 Fixing supports134 Technical information135 Determination of the operating current of a busbar109LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


TSTechnical descriptionG<strong>EN</strong>ERAL FEATURESThe TS (Trolley System) is part of the Zucchini rangeused for supplying power to moving devices such as:overhead cranes, traversing motors, assembly lines,etc.The main features of the TS range are:• quick installation thanks to the electric terminaljunction;• wide range of fixing accessories;• suitable for straight and curved sections (only forhorizontal changes of direction);• compliance with Standard IEC 60439-1 and 2;• rated at average room temperature of 40°C for ahigher performance level compared to the 35°Crating required by the standard.• available in the following versions: 3L+N+PE (5conductors) for ratings from 63-70-110-150A and3L+PE (4 conductors), for 250A rating in which theloads connected are normally three-phase motors.Automated warehousesCranesSuspension bracketStraight elementTrolleyFeed unit110 MR TS -- TROLLEY MEDIUM SYSTEM RATING


STRAIGHT ELEM<strong>EN</strong>TSThe components and the features of the TS straightelements are:• casing made with a hot galvanized steel (Senzimir);• sheet metal thickness: 1.2 mm (1.5 mm for 250A);As for the 63A (MTS63) rating, the casing is madeof extruded aluminium with a minimum thicknessof 1.4 mm; it has good mechanical rigidity andpreserves its linearity over time.• number of conductors: 5 conductors with the samesection 3L+N+PE (4 for the TS 250A), shaped toguarantee excellent mechanical strength. Theconductors are made of 99.9% pure electrolyticcopper;• separation between the conductors using fibreglassreinforced plastic material ensuring a V1 selfextinguishingdegree (according to UL94) and incompliance with the glow-wire test according toIEC 60695-2-10;• the slot along the underside of the busbar allowsa current trolley to slide in it. The size of the slotensures an IP20 degree of protection;• an independent electrical junction terminal system(made of bronze plates) for fast and reliableconnection of the live conductors and the PE. Theterminals make an electric connection between theconductors, with a smooth flat lower part in orderto make the trolleys slide more easily. The wholebusbar is “fire retardant” in compliance with thestandard IEC 60332-3.Work station installationInstallation for mobile machineryMRMEDIUM RATINGTSTROLLEY SYSTEMCrane installationG<strong>EN</strong>ERAL FEATURES111LOW-MEDIUM POWER G<strong>EN</strong>ERALCATALOGO CONDOTTI CATALOGUESBARRE


TSTechnical descriptionFEED UNITSAllows you to electrically power the TS busbarthrough a cable line. The entrance point of the cablesis generally positioned on the back side of the feedunit. The TS range has centre feed units which can beinstalled wherever there is a junction between thestraight elements.Feed unitIntermediate feed unit<strong>EN</strong>D COVERThe end cover ensures the IP55 protection degree atthe end of the line.End coverFIXING SUPPORTSIn order to fix the line to the structure of the building,directly or with wall / ceiling / beam supports, it isnecessary to use a bracket which serves as a collararound the busbar. An electrical junction, which canalso serve for suspending the busbar, is available onthe TS line. The bracket has holes so it can be easilypaired with the supports available in this catalogue.Coupling clamp with suspension bracket112 MR TS -- TROLLEY MEDIUM SYSTEM RATING


TROLLEYSThese are used for connecting and supplying powerfor 25A – 40A – 80A or 160A three-phase loads (in thecoupled version); their features include:• The trolleys are equipped with 5 graphite brushes(3L+N+PE) which, due to the spring action, keep thecorrect pressure on the conductors enabling themto pick up current from the line while the trolley ismoving (travelling) inside the TS busbar.• The trolleys can be coupled with a mechanical joint soas to pickup twice the rated current of a single trolley.• The trolley is coupled to the motor with a “drive arm”which receives the movement from the same electricmotor supplying power to it.• The drive arms are connected to the trolleys withspecial springs which reduce the acceleration(so-called “sudden pulls”) when starting up and whenbraking;• Maximum travelling speed of the trolleys is 90 m/min(150 m/min for the MTS 63A).• Availability, on request, of a box with a set of threefuse carriers, used as an accessory, to protect the cablefrom overcurrents.• compliance with all insulating plastic componentsaccording to the glow-wire test (IEC 60695-2-10) withV1 self-extinguishing degree (UL94).• Standard IP20 degree of protection without usingadditional accessories.40A trolleyMRMEDIUM RATINGTSTROLLEY SYSTEMG<strong>EN</strong>ERAL FEATURES113LOW-MEDIUM POWER G<strong>EN</strong>ERALCATALOGO CONDOTTI CATALOGUESBARRE


Trunking components andadditional elementsDepending on the different installation requirementsZucchini can provide various technical solutions:a) curved elements: available for making changes ofdirection (only horizontally) up to a minimum radiusof curvature of 1.5m. There is a quick connection,as with the straight elements. Standard trolleys slideefficiently even within the curved sections of the line.The standard degree of protection is IP20;b) straight elements with trolley introduction device:these elements are provided with an access dooron the underside. With this door open, it is possibleto insert or remove a trolley from the line. Trolleyscan generally be put into the line near the endcovers. However, when there are lines with severaloperating trolleys or when using very long lines, it isrecommended to use an inserting centre element tomake maintenance operations on the trolleys easier.The standard degree of protection is IP20;c) straight lengths with thermal expansion device.These elements are necessary in lines exceeding35-40 m in length. Expansion elements absorb andcompensate the thermal expansion of the conductorspreventing them from losing their linearity, avoidingthe reduction of the air insulation distances andobstructing the sliding action of the trolleys.The end covercompletes theinstallation of thelines and guaranteesthe IP20 degree ofprotection of the line.The suspension bracket canbe positioned anywherealong the busbar.Straight elements.PARTS OF THE LINEEnd feed unitEnd coverElectrical and mechanical jointSuspension and joint bracket114 MR TS -- TROLLEY MEDIUM SYSTEM RATING


TSTROLLEY SYSTEMMRMEDIUM RATINGTrolley. It slides on theelement, ensuring contact withthe conductors.Suspension and jointbracket.End feedunits.Suspension bracket40A trolleyG<strong>EN</strong>ERAL FEATURES115LOW-MEDIUM POWER G<strong>EN</strong>ERALCATALOGO CONDOTTI CATALOGUESBARRE


Trunking componentsTS5 - IP20Three-pole + Neutral + copper earthing conductor:Rating 70-110-150ASTRAIGHT ELEM<strong>EN</strong>TRating (A) Item L=3000 Item L=1500 Weight (kg)70 80520101 12110 80530101 12.5150 80540101 1365.5L3 L2 L1 NL = 3000L = 150070 80530102 6110 80530102 6150 80540102 6.5The element includes the following:• a galvanized metal plate shaped to provide good mechanical strength and rigidPVC section bars.• Polyamide resin busbar holder supports reinforced with fibreglass with a highdegree of insulation.• Electrolytic copper busbars ETP 99.9 which allow the trolley to slide easily.983 m STRAIGHT ELEM<strong>EN</strong>TWith trolley introduction deviceL = 3000Rating (A) Item L=3000 Weight (kg)70 80530201 13110 80530201 13150 80540201 13.5The trolley can be easily inserted with this device, and a perfect runningplane is ensured after the closure.L = 30003 m STRAIGHT ELEM<strong>EN</strong>T WITH EXPANSION JOINTRating (A) Item L=3000 Weight (kg)70 80530301 14110 80530301 14150 80540301 14.5It compensates the expansion effects of the busbar conductors resulting fromthe temperature variations of the conductors. It is recommended to use it every35-40m of line.Rmin = 1500CURVED ELEM<strong>EN</strong>TRating (A) Item L=300070 80530401110 80530401150 80540401Curved elements can be ordered with any radius of curvature, to a minimum of1500 mm. Lines with curved elements can be used with our standard trolleys.116 TS - TROLLEY SYSTEM


AccessoriesTS5 - IP20FUSE CARRIER BOX FOR LINES RANGING FROM 70A TO 250ARating (A) Item L=3000max 160 80045504Set of three NH 00 fuse carriers.500320 180Fuses not included130240<strong>EN</strong>D FEED UNIT115150115Rating (A) Item70 80541<strong>001</strong>110 80541<strong>001</strong>150 80541<strong>001</strong>The end feed unit can be installed at either end of a busbar.INTERMEDIATE FEED UNIT110240130Rating (A) Item70 80541101110 80541101150 80541101Used to power a busbar from any intermediate point. The intermediate feed unitis also used for reducing the voltage drop of the line.TSTROLLEY SYSTEMCATALOGUE 117LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


AccessoriesTS5 - IP20COUPLING CLAMP1207295Rating (A) Item70 80542<strong>001</strong>110 80542<strong>001</strong>150 80542<strong>001</strong>Use one piece for each element.Provides the mechanical and electrical connection between two elements.SUSP<strong>EN</strong>SION COUPLING CLAMP6062Ø 6.5slot 6.5 x 157295Rating (A) Item70 80542002110 80542002150 80542002Provides the mechanical and electrical connection between two elements as wellas a fixing support point120INTERMEDIATE SUSP<strong>EN</strong>SION BRACKET6062Ø 6.5slot 6.5 x 1595Rating (A) Item70 80042101110 80042101150 80042101It allows the possibility to hang the busbar anywhere along the line. Use oneevery 2 metres501209892<strong>EN</strong>D COVERRating (A) Item70 80531301110 80531301150 80541301The end cover can be installed at either end of the busbar.118 TS - TROLLEY SYSTEM


40A 3P + N + PE TROLLEY97160(A)Item80545002The 40A trolley has graphite contacts which ensure electrical continuity. An 80Arating can be achieved by connecting two trolleys in parallel using the couplingbracket (code 80045203). It works properly up to a sliding speed of 90m/minand withstands weights up to 30 kg.182(A)Always pull the trolley by means of its springs.DRIVE ARMSItem Model80045201 standard80045202 dualIn order to have a perfect alignment and an excellent sliding action, a driving armis essential. It adjusts the trolley both horizontally and vertically.400644TSTROLLEY SYSTEMBRACKET FOR COUPLING TROLLEYS150Item80045203The coupling bracket can connect two trolleys together, thus allowing you toobtain 80A.CATALOGUE 119LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Trunking componentsTS250 - IP20Trolley System - Three-pole + copper earthing conductor:Rating 250AL = 3000L = 1500STRAIGHT ELEM<strong>EN</strong>TRating (A) Item L=3000 Item L=1500 Weight (kg)250 822<strong>001</strong>01 29.2250 822<strong>001</strong>02 15The element includes the following:• A galvanized metal plate shaped to provide good mechanical features.• Polyamide resin busbar holder supports reinforced with fibreglass with a highdegree of insulation.• Electrolytic copper phase conductors - ETP 99.9%• Two rigid PVC edges ensure an IP20 protection degree against direct contacts.89L3 L2 L1141443 m STRAIGHT ELEM<strong>EN</strong>TWith trolley introduction deviceL = 3000Rating (A) Item L=3000 Weight (kg)250 82200201 29.2The trolley can be easily inserted with this device, thus making it possible to lineit up so as to achieve a perfect running action after the closure. The element withthe trolley introduction shall be used for very long lines (> 20m).3 m STRAIGHT ELEM<strong>EN</strong>TWith expansion jointL = 3000Rating (A) Item L=3000 Weight (kg)250 82200301 32It compensates the expansion effects of the busbar conductor thermal expansionwhen the temperature changes.It is recommended to use them every 35-40m of line.120 TS - TROLLEY SYSTEM


AccessoriesTS250 - IP20<strong>EN</strong>D FEED UNIT125Rating (A) Item250 82<strong>001</strong><strong>001</strong>The end feed unit can be installed at either end of a busbar.140330140350INTERMEDIATE FEED UNITRating (A) Item250 82<strong>001</strong>101Used to power a busbar from any intermediate point. The intermediate feed unitis also used for reducing the voltage drop of the line.225COUPLING CLAMP137Rating (A) Item250 82002<strong>001</strong>Use one piece for each element.Provides the mechanical and electrical connection between two elements.20060108Ø 6.5slot 6.5 x 15SUSP<strong>EN</strong>SION COUPLING CLAMPRating (A) Item250 82002101TSTROLLEY SYSTEM137Provides the mechanical and electrical connection between two elements as wellas a suspension point.20060108Ø 6.5slot 6.5 x 15120INTERMEDIATE SUSP<strong>EN</strong>SION BRACKETRating (A) Item250 82002101It allows the possibility to hang the busbar anywhere along the line.Use one every 2 metres70143<strong>EN</strong>D COVER137Rating (A) Item250 82<strong>001</strong>301The end cover can be installed at either end of a busbar.200CATALOGUE 121LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


AccessoriesTS250 - IP20186144Item82205<strong>001</strong>80A 3P + T TROLLEYThe driving action of the trolleys shall always be carried out with its springs.210The trolley used for the 250A (3PH+T) Trolley line is available for an 80A rating.The contacts are of the sliding type, two for each phase. The earth contacts arelocated beside the trolley and ensure a constant and efficient contact. It worksproperly up to a sliding speed of 90m/min and withstands weights up to 30 kg.DRIVE ARMSItemModel80045201 standard80045202 dualIn order to have a perfect alignment and an excellent sliding action, adriving arm is essential. It adjusts the trolley both horizontally and vertically.400644150BRACKET FOR COUPLING TROLLEYSItemDescription80045203 The coupling bracket can connect two trolleys together,thus allowing you to obtain 160A.122 TS - TROLLEY SYSTEM


Trunking componentsMTS63-IP23Three-pole + Neutral + copper earthing conductor:Rating 63ASuitable for manual driveSTRAIGHT ELEM<strong>EN</strong>TRating (A) Item L=3000 Item L=1500 Weight (kg)63 845<strong>001</strong>01 563 845<strong>001</strong>11 2.5The element includes the following:• An extruded anodised aluminium casing shaped to provide a section with strongmechanical features.• Internal conductor holder sheath made of rigid PVC• Electrolytic copper phase conductors - ETP 99.9%L2L1TSTROLLEY SYSTEM57NL344.8CATALOGUE 123LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


Trunking componentsMTS63-IP23R <strong>EN</strong>D FEED UNIT + R COVERRating (A) Item Weight (kg)63 84501<strong>001</strong> 1L <strong>EN</strong>D FEED UNIT + L COVERRating (A) Item Weight (kg)63 84501002 1.525A TROLLEYItemWeight (kg)84505<strong>001</strong> 0.32The 25A trolley has graphite contacts which ensure electrical continuity. It worksproperly up to a sliding speed of 150 m/min and withstands weights up to 30 kg.ABBRACKETSType Item Description Weight (kg)A 71003<strong>001</strong> Standard suspension bracket -B 84502101 Ceiling suspension bracket -FUSE CARRIER BOX (FROM 10.3 TO 38)ItemWeight (kg)84505004 -Used for local protection.124 TS - TROLLEY SYSTEM


Bracket holderWALL FIXING BRACKET cm 45 - cm 55 - cm 75Rating (A) Item Weight (kg)450 50632212 2.800550 50632213 3.000750 50632214 3.5007015511x259x20450 - 550 - 750415 - 515 - 715130130355<strong>001</strong>706050slot 25x71CEILING BRACKET:Ref. Item Description Weight (kg)1 50632201 Ceiling flange 0.9002 50632202 U-shaped bar L = 500 mm 0.9003 50632203 U-shaped bar L = 1000 mm 1.8004 50632204 U-shaped bar L = 2000 mm 3.60043250 30204100L100Ø 8.2TSTROLLEY SYSTEM5711x25Ø 1112 3 4BEAM BRACKET:Ref. Item Description Weight (kg)1 50632210 Beam bracket base 1.0002 50632211 Beam clamp 0.1002(2 for each bracket holder)154045146.5Ø 7 8.5 x 1240651757 x 421 2CATALOGUE 125LOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE


126TECHNICALINFORMATION


SECTION CONT<strong>EN</strong>TS128 LB129 HL130 SL131 MS132 MR134 TS135 DETERMINATION OF THE OPERATING CURR<strong>EN</strong>T OF A BUSBAR136 CABLE GLAND TABLE137 COORDINATION TABLELOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUECATALOGO CONDOTTI SBARRE127TECHNICALINFORMATION


LBtechnical informationModel 252 254 256 402 404 406Number of live conductorsNo.Casing overall dimensionsA x B [mm]Rated currentI n [A]Cross-section of conductors (3P+N) S [mm 2 ]Cross-section ofprotective conductor eq. CuS PE[mm 2 ]Operating voltageU e [V]Insulation voltageU i [V]Rated frequencyf [Hz]Rated short-time current (0.1 s)I CW [kA]rmsAllowable peak currentI pk [kA]Thermal limit I 2 t [A 2 s x 10 6 ]Phase resistanceR20 [m/m]Phase reactance (50Hz)X [m/m]Phase impedanceZ [m/m]Resistance of the protective conductor RPE [m/m]Reactance of the protective conductor (50Hz) XPE [m/m]Resistance of the fault loopRo [m/m]Reactance of the fault loop (50Hz)Xo [m/m]Impedance of the fault loopZo [m/m]V [V/m/A]10 -3 cos = 0.70V1F = 1(2 V [V/m/A]10 -3 cos = 0.75R20 cos + 2 X sen )2V [V/m/A]10 -3 cos = 0.80Voltage drop with distributed load (k) V [V/m/A]10 -3 cos = 0.85V3F =32(R20 cos + X sen )Straight element weightFire loadDegree of protectionJoule effect losses at rated currentAmbient temperature min./MAX.V [V/m/A]10 -3 cos = 0.90V [V/m/A]10 -3 cos = 0.95V [V/m/A]10 -3 cos = 1.00p [kg/m][kWh/m]IPP [W/m]t [°C]side side side side2 4 4 • 2 2 4 4 • 226 x 41 26 x 41 26 x 41 26 x 41 26 x 41 26 x 4125 25 25 40 40 403.14 3.14 3.14 6.15 6.15 6.158.72 8.72 8.72 8.72 8.72 8.72400 400 400 400 400 400500 500 500 500 500 50050/60 50/60 50/60 50/60 50/60 50/602.2 2.2 2.2 2.7 2.7 2.710 10 10 10 10 100.48 0.48 0.48 0.73 0.73 0.735.803 5.803 5.803 2.963 2.963 2.9631.144 1.279 1.279 • 1.144 0.792 0.770 0.770 • 0.7925.914 5.942 5.942 • 5.914 3.067 3.061 3.061 • 3.0671.45 1.45 1.45 1.45 1.45 1.451.10 1.10 1.10 1.10 1.10 1.107.25 7.25 7.25 4.41 4.41 4.412.24 2.38 2.38 • 2.24 1.89 1.87 1.87 • 1.897.59 7.63 7.639 • 7.59 4.80 4.79 4.79 • 4.804.88 4.31 4.31 • 4.88 2.64 2.27 2.27 • 2.645.11 4.50 4.50 • 5.11 2.75 2.37 2.37 • 2.755.33 4.68 4.68 • 5.33 2.85 2.45 2.45 • 2.855.53 4.85 4.85 • 5.53 2.94 2.53 2.53 • 2.945.72 5.01 5.01 • 5.72 3.01 2.60 2.60 • 3.015.87 5.12 5.12 • 5.87 3.06 2.65 2.65 • 3.065.80 5.03 5.03 • 5.80 2.96 2.57 2.57 • 2.960.95 1.0 1.10 1.0 1.1 1.200.82 0.82 0.82 0.82 0.82 0.8255 55 55 55 55 557.3 10.9 10.9 • 7.3 9.5 14.2 14.2 9.5-5/+50 -5/+50 -5/+50 -5/+50 -5/+50 5/+50Short circuit protection for Zucchini’s product ranges (In100A)Zucchini busbar trunking systems with a rated current lower thanor equal to 100A (LB-HL-SL-MS 63 and 100) are properly protectedthrough an MCB (Modular Circuit Breaker) with a rated current lowerthan or equal to that of the busbar. This protection is guaranteed upto the MCB breaking capacity.The busbar trunking systems are FIRE RETARDANT in compliance withIEC 20-22 (IEC 332-3: 1992).Product fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and2, DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 / 2- 3)Cyclical humid climate (DIN IEC 68 / 2- 30)Temperature rating schedule according to the room temperatureRoom temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40° CTable for mechanical loads permitted (with busbar installed on edge)When distributing loads, if any, the maximum weight (kg) that can be supported isgiven in the tables below:For point loads, multiply the values in the table below by 0.5.fixing centres (distance) m.maximum deflection = 1/350 x distance m 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0kg 17.2 15.8 14.6 13.4 12.5 11.6 11 10maximum deflection = 1/500 x distance m 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0kg 15.4 14 13 12 11.2 10.4 9.6 9128


Technical informationHLModel 252 402 254 404 2522 4022 2542 4042 2544 4044 2x4Number of live conductorsNo.Casing overall dimensionsA x B [mm]Rated currentI n [A]Cross-section of conductors (3P+N) S [mm 2 ]Cross-section of protective conductor eq. Cu S PE [mm 2 ]Operating voltageU e [V]Insulation voltageU i [V]Rated frequencyf [Hz]Rated short-time current (0.1 s)I CW [kA]rmsAllowable peak currentI pk [kA]Thermal limit I 2 t [A 2 s x 10 6 ]Phase resistanceR 20 [m/m]Phase reactance (50Hz)X [m/m]Phase impedanceZ [m/m]Resistance of the protective conductor R PE [m/m]Reactance of the protective conductor (50Hz) X PE [m/m]Resistance of the fault loopR o [m/m]Reactance of the fault loop (50Hz)X o [m/m]Impedance of the fault loopZ o [m/m]V [V/m/A]10 -3 cos = 0.70= 0.75V 1F =1(2 R 20 cos + 2 X sen )2= 0.80Voltage drop with distributed load (k) = 0.85V 3F = 32(R 20 cos + X sen )Straight element weightFire loadDegree of protectionJoule effect losses at rated currentAmbient temperature min./MAX.= 0.90= 0.95= 1.00p [kg/m][kWh/m]IPP [W/m]t [°C]HLssingleHLddoubleside side side side2 2 4 4 2+2 2+2 4 • 2 4 • 2 4+4 4+4 2+2+2+226x62 26x62 26x62 26x62 40.4x70 40.4x70 40.4x70 40.4x70 40.4x70 40.4x70 40.4x7025 40 25 40 25 40 25 40 25 40 253.14 6.15 3.14 6.15 3.14 6.15 3.14 6.15 3.14 6.15 3.1417 17 17 17 20 20 20 20 20 20 20400 400 400 400 400 400 400 400 400 400 400500 500 500 500 500 500 500 500 500 500 50050/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/602.5 3.2 2.5 3.2 2.5 3.2 2.5 3.2 2.5 3.2 2.510 10 10 10 10 10 10 10 10 10 100.64 1.00 0.64 1.00 0.64 1.00 0.64 1.00 0.64 1.00 0.645.73 2.93 5.73 2.93 5.73 2.93 5.73 • 5.73 2.93 • 2.93 5.73 2.93 5.731.40 1.58 1.27 0.77 1.40 1.58 1.27 • 1.40 0.77 • 1.58 1.27 0.77 1.275.90 3.33 5.87 3.03 5.90 3.33 5.87 • 5.90 3.03 • 3.33 5.87 3.03 5.871.06 1.06 1.06 1.06 0.90 0.90 0.90 • 0.90 0.90 • 0.90 0.90 0.90 0.901.10 1.10 1.10 1.10 1.00 1.00 1.00 • 1.00 1.00 • 1.00 1.00 1.00 1.006.79 3.99 6.79 3.99 6.63 3.83 6.63 • 6.63 3.83 • 3.83 6.63 3.83 6.632.50 2.68 2.37 1.87 2.40 2.58 2.27 • 2.40 1.77 • 2.58 2.27 1.77 2.277.24 4.80 7.19 4.40 7.05 4.62 7.01 • 7.05 4.22 • 4.62 7.01 4.22 7.015.01 3.18 4.26 2.25 5.01 3.18 4.26 • 5.01 2.25 • 3.18 4.26 2.25 4.925.23 3.24 4.45 2.34 5.23 3.24 4.45 • 5.23 2.34 • 3.24 4.45 2.34 5.145.43 3.29 4.63 2.43 5.43 3.29 4.63 • 5.43 2.43 • 3.29 4.63 2.43 5.355.61 3.32 4.80 2.51 5.61 3.32 4.80 • 5.61 2.51 • 3.32 4.80 2.51 5.545.77 3.32 4.95 2.57 5.77 3.32 4.95 • 5.77 2.57 • 3.32 4.95 2.57 5.715.88 3.27 5.06 2.62 5.88 3.27 5.06 • 5.88 2.62 • 3.27 5.06 2.62 5.845.73 2.93 4.96 2.53 5.73 2.93 4.96 • 5.73 2.53 • 2.93 4.96 2.53 5.731.5 1.6 1.6 1.7 2.8 2.9 2.9 3.1 2.9 3.2 2.90.82 0.82 0.82 0.82 1.64 1.64 1.64 1.64 1.64 1.64 1.6455 55 55 55 55 55 55 55 55 55 557.2 9.4 10.7 14.0 7.2 9.4 10.7 • 7.2 14.0 • 9.4 10.7 14.0 7.2-5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50 -5/+50Short circuit protection for Zucchini’s product ranges (In100A)Zucchini busbar trunking systems with a rated current lower thanor equal to 100A (LB-HL-SL-MS 63 and 100) are properly protectedthrough an MCB (Modular Circuit Breaker) with a nominal currentlower than or equal to that of the busbar. This protection isguaranteed up to the MCB breaking capacity.The busbar trunking systems are FIRE RETARDANT in compliance withIEC 20-22 (IEC 332-3: 1992).Product fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and2, DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 / 2- 3)Cyclical humid climate (DIN IEC 68 / 2- 30)Temperature rating schedule according to the room temperatureRoom temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40° CTable for mechanical loads permitted (with busbar installed on edge)When distributing loads, if any, the maximum weight (kg) that can be supported isgiven in the tables below:For point loads, multiply the values in the table below by 0.6.fixing centres (distance) m.maximum deflection = 1/250 x distance m 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0kg 82.3 71.1 52.2 40.0 31.6 25.6 21.1 17.8(busbar installed on edge)TECHNICAL INFORMATIONLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE129TECHNICALINFORMATION


Technical informationSLModel 40 63Number of live conductorsNo.Casing overall dimensionsA x B [mm]Rated currentIn [A]Cross-section of conductors (3P+N) S [mm 2 ]Cross-section of protective conductor eq. Cu S PE [mm 2 ]Operating voltageU e [V]Insulation voltageU i [V]Rated frequencyf [Hz]Rated short-time current (0.1 s)I CW [kA]rmsAllowable peak currentI pk [kA]Thermal limit I 2 t [A 2 s x 10 6 ]Phase resistanceR 20 [m/m]Phase reactance (50Hz)X [m/m]Phase impedanceZ [m/m]Resistance of the protective conductorR PE [m/m]Reactance of the protective conductor (50Hz)X PE [m/m]Resistance of the fault loopR o [m/m]Reactance of the fault loop (50Hz)X o [m/m]Impedance of the fault loopZ o [m/m]V [V/m/A]10 -3 cos = 0.70V [V/m/A]10 -3 cos = 0.75V1F =1(2 R20 cos + 2 X sen )2V [V/m/A]10 -3 cos = 0.80Voltage drop with distributed load (k) V [V/m/A]10 -3 cos = 0.85V3F =32(R20 cos + X sen )Straight element weightFire loadDegree of protectionJoule effect losses at rated currentAmbient temperature min./MAX.V [V/m/A]10 -3 cos = 0.90V [V/m/A]10 -3 cos = 0.95V [V/m/A]10 -3 cos = 1.00p [kg/m][kWh/m]IPP [W/m]t [°C]4 426 x 62 26 x 6240 639.5 12.317 17400 400750 75050/60 50/602.70 3.1010 107.29 9.61.811 1.3730.290 0.6371.834 1.5140.870 0.8700.090 0.0872.68 2.240.380 0.7242.71 2.361.28 1.231.34 1.261.41 1.281.47 1.301.52 1.311.57 1.301.57 1.192.2 2.30.80 0.8040/55 40/558.7 16.3-5/+50 -5/+50Short circuit protection for Zucchini’s product ranges (In100A)Zucchini busbar trunking systems with a rated current lower thanor equal to 100A (LB-HL-SL-MS 63 and 100) are properly protectedthrough an MCB (Modular Circuit Breaker) with a nominal currentlower than or equal to that of the busbar. This protection isguaranteed up to the MCB breaking capacity.The busbar trunking systems are FIRE RETARDANT in compliance withIEC 20-22 (IEC 332-3: 1992).Temperature rating schedule according to the room temperatureRoom temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40° CCoordination table with <strong>Legrand</strong> DPX at page 137Product fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and2, DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 / 2- 3)Cyclical humid climate (DIN IEC 68 / 2- 30)130


Technical informationMSModel 63 100 160Number of live conductorsNo.Casing overall dimensionsA x B [mm]Rated currentI n [A]Cross-section of conductors (3P+N) S [mm 2 ]Cross-section of protective conductor eq. Cu S PE [mm 2 ]Operating voltageU e [V]Insulation voltageU i [V]Rated frequencyf [Hz]Rated short-time current (0.1 s)I CW [kA]rmsAllowable peak currentI pk [kA]Thermal limit I 2 t [A 2 s x 10 6 ]Phase resistanceR 20 [m/m]Phase reactance (50Hz)X [m/m]Phase impedanceZ [m/m]Resistance of the protective conductorR PE [m/m]Reactance of the protective conductor (50Hz)X PE [m/m]Resistance of the fault loopR o [m/m]Reactance of the fault loop (50Hz)X o [m/m]Impedance of the fault loopZ o [m/m]V [V/m/A]10 -3 cos = 0.70V1F =1(2 R20 cos + 2 X sen )V [V/m/A]10 -3 cos = 0.752V [V/m/A]10 -3 cos = 0.80Voltage drop with distributed load (k) V [V/m/A]10 -3 cos = 0.85V3F =32(R20 cos + X sen )Straight element weightFire loadDegree of protectionJoule effect losses at rated currentAmbient temperature min./MAX.V [V/m/A]10 -3 cos = 0.90V [V/m/A]10 -3 cos = 0.95V [V/m/A]10 -3 cos = 1.00p [kg/m][kWh/m]IPP [W/m]t [°C]4 4 439 x 97 39 x 97 39 x 9763 100 16026 39 3921 21 21400 400 400750 750 75050/60 50/60 50/602.30 4.50 5.5010 10 105.29 20.25 30.251.250 0.837 0.4780.366 0.247 0.2471.302 0.873 0.5380.857 0.857 0.8570.090 0.102 0.1022.11 1.69 1.340.456 0.349 0.3492.16 1.73 1.380.98 0.66 0.441.02 0.69 0.451.06 0.71 0.461.09 0.73 0.461.11 0.75 0.471.13 0.76 0.461.08 0.72 0.412.0 2.5 2.81.64 1.64 1.6440/55 40/55 40/5514.9 25.1 36.7-5/+50 -5/+50 -5/+50Short circuit protection for Zucchini’s product ranges (In100A)Zucchini busbar trunking systems with a rated current lower thanor equal to 100A (LB-HL-SL-MS 63 and 100) are properly protectedthrough an MCB (Modular Circuit Breaker) with a nominal currentlower than or equal to that of the busbar.This protection is guaranteed up to the MCB breaking capacity. Thebusbar trunking systems are FIRE RETARDANT in compliance with IEC20-22 (IEC 332-3: 1992).Temperature rating schedule according to the room temperatureRoom temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40° CCoordination table with <strong>Legrand</strong> DPX at page 137Product fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and 2,DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 / 2- 3)Cyclical humid climate (DIN IEC 68 / 2- 30)TECHNICAL INFORMATIONLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE131TECHNICALINFORMATION


Technical informationMR AluminiumMR (3L+N+PE)Rated currentIn [A]Operating voltageU e [V]Insulation voltageU i [V]Frequencyf [Hz]Rated short-time current for three-phase fault (1 s)I CW [kA] rmsAllowable specific energy for three-phase fault I 2 t [M A 2 s]Allowable peak current for three-phase faultI pk [kA]Rated short-time current for single-phase fault Ph-N (1 s)I CW [kA] rmsAllowable peak current for single-phase fault Ph-NI pk [kA]Rated short-time current for single-phase fault Ph-PE (1 s)I CW [kA] rmsRated peak current for single-phase fault Ph-PEI pk [kA]Phase resistance at 20 °CR 20 [m/m]Phase resistance at thermal conditions (In; 40°C)R t [m/m]Phase reactance (50 Hz)X [m/m]Neutral resistance at 20 °CRn20 [m/m]Neutral reactance (50 Hz)X n [m/m]Resistance of the protective conductorR PE [m/m]Reactance of the protective conductor (50 Hz)X PE [m/m]Resistance of the fault loop phase-PERPh-Pe fault loop [m/m]Reactance of the fault loop phase-PE (50 Hz)XRPh-Pe fault loop [m/m]Resistance of the fault loop phase-neutralRPh-N fault loop [m/m]Reactance of the fault loop phase-neutral (50 Hz) XRPh-N fault loop [m/m]v [V/m/A]10 -3 cos = 0.70v [V/m/A]10 -3 cos = 0.75Voltage drop v [V/m/A]10 -3 cos = 0.80with distributed load (k) v [V/m/A]10 -3 cos = 0.85v [V/m/A]10 -3 cos = 0.90v [V/m/A]10 -3 cos = 0.95v [V/m/A]10 -3 cos = 1.00Joule effect losses at rated currentP [W/m]Fire load[kWh/m]Weightp [kg/m]Outside dimensions of the busbarLxH [mm]Degree of protectionIPMechanical resistance of the casingsIK* Values referred to 0.1 s160 250 315 400 500 630 8<strong>001</strong>000 1000 1000 1000 1000 1000 10<strong>001</strong>000 1000 1000 1000 1000 1000 100050/60 50/60 50/60 50/60 50/60 50/60 50/6015* 25* 25* 25 30 36 3623 63 63 625 900 1296 129630 53 53 53 63 76 769* 15* 15* 15 18 22 2215 30 30 30 36 45 459* 15* 15* 15 18 22 2215 30 30 30 36 45 450.492 0.328 0.197 0.120 0.077 0.060 0.0520.665 0.443 0.266 0.163 0.104 0.081 0.0700.260 0.202 0.186 0.130 0.110 0.097 0.0960.492 0.328 0.197 0.120 0.077 0.060 0.0520.260 0.202 0.186 0.130 0.110 0.097 0.0960.341 0.341 0.341 0.283 0.283 0.283 0.2830.220 0.220 0.220 0.180 0.180 0.180 0.1801.006 0.784 0.607 0.445 0.387 0.364 0.3530.480 0.414 0.396 0.333 0.333 0.283 0.2751.157 0.771 0.463 0.283 0.181 0.141 0.1210.480 0.422 0.406 0.310 0.290 0.277 0.2760.564 0.394 0.276 0.179 0.131 0.109 0.1020.581 0.404 0.279 0.180 0.130 0.108 0.1000.596 0.412 0.281 0.180 0.129 0.107 0.0980.608 0.418 0.281 0.179 0.127 0.104 0.0950.616 0.422 0.277 0.176 0.122 0.100 0.0910.617 0.419 0.269 0.169 0.115 0.093 0.0830.576 0.384 0.230 0.141 0.090 0.070 0.06051 83 79 78 78 97 1341.3 1.3 1.3 1.8 1.8 1.8 1.87.4 7.7 8.4 10.7 12.3 13.8 14.776x195 76x195 76x195 136x195 136x195 136x195 136x19552-55 52-55 52-55 52-55 52-55 52-55 52-5510 10 10 10 10 10 10Temperature rating schedule according to the room temperatureProduct fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and 2,DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 / 2- 3)Cyclical humid climate (DIN IEC 68 / 2- 30)Room temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40° CCoordination table with <strong>Legrand</strong> DPX at page 137132


Technical informationMR CopperMR (3L+N 100% +PE)Rated currentI n [A]Operating voltageU e [V]Insulation voltageU i [V]Frequencyf [Hz]Rated short-time current for three-phase fault (1 s)I CW [kA] rmsAllowable specific energy for three-phase fault I 2 t [M A 2 s]Allowable peak current for three-phase faultI pk [kA]Rated short-time current for single-phase fault Ph-N (1 s)I CW [kA] rmsAllowable peak current for single-phase fault Ph-NI pk [kA]Rated short-time current for single-phase fault Ph-PE (1 s)I CW [kA]rmsRated peak current for single-phase fault Ph-PEI pk [kA]Phase resistance at 20 °CR 20 [m/m]Phase resistance at thermal conditions (In; 40°C)R t [m/m]Phase reactance (50 Hz)X [m/m]Neutral resistance at 20 °CRn 20 [m/m]Neutral reactance (50 Hz)X n [m/m]Resistance of the protective conductorR PE [m/m]Reactance of the protective conductor (50 Hz)X PE [m/m]Resistance of the fault loop Phase-PERPh-Pe fault loop [m/m]Reactance of the fault loop Phase-PE (50 Hz)XRPh-Pe fault loop [m/m]Resistance of the fault loop phase-neutralRPh-N fault loop [m/m]Reactance of the fault loop phase-neutral (50 Hz)XRPh-N fault loop [m/m]v [V/m/A]10 -3 cos = 0.70v [V/m/A]10 -3 cos = 0.75Voltage drop v [V/m/A]10 -3 cos = 0.80with distributed load (k) v [V/m/A]10 -3 cos = 0.85v [V/m/A]10 -3 cos = 0.90v [V/m/A]10 -3 cos = 0.95v [V/m/A]10 -3 cos = 1.00Joule effect losses at rated currentP [W/m]Fire load[kWh/m]Weightp [kg/m]Outside dimensions of the busbarLxH [mm]Degree of protectionIPMechanical resistance of the casingsIK* Values referred to 0.1 s250 315 400 630 800 10<strong>001</strong>000 1000 1000 1000 1000 10<strong>001</strong>000 1000 1000 1000 1000 100050/60 50/60 50/60 50/60 50/60 50/6025* 25* 30* 36 36 3663 63 90 1296 1296 129653 53 63 76 76 7615* 15* 18* 22 22 2230 30 36 45 45 4515* 15* 18* 22 22 2230 30 36 45 45 450.237 0.180 0.096 0.061 0.040 0.0320.320 0.243 0.129 0.082 0.053 0.0430.205 0.188 0.129 0.122 0.122 0.1200.237 0.180 0.096 0.061 0.040 0.0320.205 0.188 0.129 0.122 0.122 0.1200.336 0.336 0.336 0.279 0.279 0.2790.220 0.220 0.220 0.180 0.180 0.1800.657 0.579 0.466 0.361 0.332 0.3220.425 0.408 0.349 0.302 0.302 0.3000.558 0.423 0.225 0.143 0.093 0.0740.425 0.408 0.349 0.302 0.302 0.3000.321 0.263 0.158 0.125 0.108 0.1000.326 0.265 0.158 0.123 0.105 0.0960.329 0.266 0.157 0.120 0.100 0.0920.329 0.264 0.154 0.116 0.095 0.0860.327 0.260 0.149 0.110 0.088 0.<strong>079</strong>0.319 0.251 0.141 0.101 0.077 0.0680.277 0.210 0.112 0.071 0.046 0.03760 72 62 98 103 1281.3 1.3 1.3 1.8 1.8 1.89.3 10.2 13.3 18.2 23.9 27.976x195 76x195 76x195 136x195 136x195 136x19552-55 52-55 52-55 52-55 52-55 52-5510 10 10 10 10 10Temperature rating schedule according to the room temperatureProduct fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and2, DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 / 2- 3)Cyclical humid climate (DIN IEC 68 / 2- 30)Room temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40 °CCoordination table with <strong>Legrand</strong> DPX at page 137TECHNICAL INFORMATIONLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE133TECHNICALINFORMATION


Technical informationTSModel MTS 63A TS 5 70A TS 5 110A TS 150 A TS 250ANumber of live conductorsNo.Casing overall dimensionsA x B [mm]Rated currentI n [A]Cross-section of conductors (3P+N) S [mm 2 ]Cross-section of protective conductor eq. Cu SPE [mm 2 ]Operating voltageU e [V]Insulation voltageU i [V]Rated frequencyf [Hz]Rated short-time current (0.1 s)I CW [kA] rmsAllowable peak currentI pk [kA]Thermal limit I 2 t [A 2 s x 10 6 ]Phase resistanceR 20 [m/m]Phase reactance (50Hz)X [m/m]Phase impedanceZ [m/m]Resistance of the protective conductorR PE [m/m]Reactance of the protective conductor (50Hz)X PE [m/m]Resistance of the fault loopR o [m/m]Reactance of the fault loop (50Hz)X o [m/m]Impedance of the fault loopZ o [m/m]V [V/m/A]10 -3 cos = 0.70V1F =1V [V/m/A]10 -3 cos = 0.75(2 R20 cos + 2 X sen )2V [V/m/A]10 -3 cos = 0.80Voltage drop with distributed load (k) V [V/m/A]10 -3 cos = 0.85V [V/m/A]10 -3 cos = 0.90V3F =3(R20 cos + X sen )V [V/m/A]10 -3 cos = 0.952V [V/m/A]10 -3 cos = 1.00Straight element weightp [kg/m]MAX travelling speed[m/min]Degree of protectionIPJoule effect losses at rated currentP [W/m]Ambient temperature min./MAX.t [°C]3P+N+T 3P+N+T 3P+N+T 3P+N+T 3P+T44.8x57 98x65.5 98x65.5 98x65.5 144x8963 70 110 150 25012 19 24 43 8512 19 24 24 120400 600 600 600 600750 750 750 750 75050/60 50/60 50/60 50/60 50/605 9 9 9 117.5 15.3 15.3 15.3 18.725 81 81 81 1211.500 0.947 0.785 0.515 0.2551.400 0.059 0.063 0.092 0.1612.052 0.949 0.788 0.523 0.3021.500 0.947 0.785 0.515 0.1500.080 0.100 0.100 0.100 0.1203.000 1.895 1.570 1.030 0.4051.480 0.159 0.163 0.192 0.2813.345 1.901 1.578 1.048 0.4931.775 0.611 0.515 0.369 0.2541.776 0.649 0.546 0.387 0.2581.767 0.687 0.577 0.405 0.2601.743 0.724 0.607 0.421 0.2611.698 0.761 0.636 0.436 0.2601.613 0.795 0.663 0.449 0.2531.299 0.820 0.680 0.446 0.2211.0 4.0 4.1 4.2 9.8150 90 90 90 9023 20 20 20 2017.9 13.9 28.5 34.8 47.8-5/+50 -5/+50 -5/+50 -5/+50 -5/+50Short circuit protection for Zucchini’s product ranges (In100A)Zucchini busbar trunking systems with a rated current lower thanor equal to 100A (LB-HL-SL-MS 63 and 100) are properly protectedthrough an MCB (Modular Circuit Breaker) with a nominal currentlower than or equal to that of the busbar. This protection isguaranteed up to the MCB breaking capacity.The busbar trunking systems are FIRE RETARDANT in compliance withCEI 20-22 (IEC 332-3: 1992).Temperature rating schedule according to the room temperatureRoom temperature [°C] 15 20 25 30 35 40 45 50 55 60K1 Factor 1.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89multiplier coefficient of rated current for room temperature values different from 40° CCoordination table with <strong>Legrand</strong> DPX at page 137Product fully in compliance with the followingStandards: IEC 439-1 and 2, IEC 60439 part 1 and2, DIN VDE 0660 part 500 and 502Product suitable for these climates:Constant humid climate (DIN IEC 68 et 2- 3)Cyclical humid climate (DIN IEC 68 et 2- 30)134


Determination of the operatingcurrent of a busbarIn order to determine the current whereby it is necessary to choose the busbar,the following planning data must be known:• type of load inputs: three-phase or single-phase;• type of circuit input: from one end, from both ends, central input, etc.;• nominal input voltage;• number, power and cos of loads which are to be fed by the busbar;• load diversity factor;• load use nominal factor;• assumed short circuit current at the input point;• room temperature;• type of busbar installation (edgewise, flat, vertical).VOLTAGE DROPv% = bdefinedI bVnLv%PTOT • • • dkI b=[A]3 • Ue • cos mediumb =2b =1ex: MR 160I b=15 20 25 30 35 40 45 50 55 601.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89I nt I bI nt= k 1• I nWhen using a three-phase power supply, the operating current is determinedby the following formula:where:I boperating current [A]; load diversity factor [.]; load use factor [.];d feed factor [.];P TOTsum of the total active power of installed loads [W];Ue operating voltage [V];cos mediumaverage load power factor [.];The “d” input factor has a value of 1 when the busbar is fed from one end only.The value is 1/2 if fed from the centre or if it is fed from each end.Once the operating current has been determined, choose the busbar with a ratedcurrent immediately higher than the one calculated.All Zucchini products have been designed and tested for an average roomtemperature of 40 °C; should they be installed in rooms with average dailytemperatures different from 40 °C the rated current of the busbar should bemultiplied by a k1 factor that is greater than the unit for temperatures lower than40°C and lower than the unit if the room temperature is higher than 40°C.Roomtemperature [°C]k 1thermal correctionfactor [.]Finally, the following should be considered for the most appropriate busbarchoice:where I ntrepresents the maximum current loaded by a busbar for an indefinitetime at the specified room temperature.JOULE EFFECT LOSSESLosses due to the Joule effect are essentially caused by the electrical resistanceof the busbar. Lost energy is transformed into heat and contributes to theheating of the conduit.If the length of the line is particularly long (>100m) it is necessary to check thevoltage drop (hereinafter specified as v.d.). If the installation is a three phasesystem and the power factor is not lower than cos = 0.7 the v.d. may be calculatedwith the coefficients of the voltage drop specified in the technical data table.k . I b . LVn. 100= the current that supplies the busbar [A]= the voltage power supply of the busbar [V]= the length of the busbar [m]= the voltage drop percentageb = the distribution factor of the current [.]= corresponding voltage drop factora cos [V/m/A] (see technical data table)The current distribution factor “b” depends on how the circuit is fed and on thedistribution of the electric loads along the busbar:supplies at one end and loadat the end of the linesupplies at one end and withload evenly distributedb =0.5 supplies at both ends and withload evenly distributedb =0.5 central supply with loadsat both endsb =0.25 central supply with loaddistributed evenly80A operating currentb=1 supply from one endk=0.608 see technical data tableCos = 0.85L= 100m line lengthVn= 400V operating voltageI bLI bI bLI bLI bI b2 Lv% = bk . I b . LVn . 10 3SHORT-CIRCUIT CURR<strong>EN</strong>TThe short circuit current value I CW that can be supported by our busbar trunking systemsallows for both electrodynamic stress and thermal energy dissipated during the fault.The busbars must be able to sustain the short circuit current for the entire durationof the fault - i.e. for the time required for the protective device (circ. breacker) to startoperating, cutting off the metal continuity and extinguishing the electric arc.I b. 100 =0.608 . 80 . 100400 . 10 3 . 100 = 1.22%I b2Three-phase ratingSingle phase ratingP = 3 • R t• I b2• 10 -3 [W/m]P = 2 • R t• I b2• 10 -3 [W/m]TECHNICAL INFORMATION135TECHNICALINFORMATIONLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE


Cableglands tabled1d2CableCableWhen choosing the cable glands, please referto the LEGRAND catalogueDimension d2 Ø cable [mm]...Dimension d2 Ø cable [mm]Ceramic fuse 5 x 20Operating featuresIn = 6.3 1.5 In 2.1 In 2.75 In 4 In 10 InOperating time > 1 h < 30 min 10 ms - 3 s 3 ms - 30 ms < 20 ms20Ø 5QUICK FUSE• I n= 6.3A• U e250V ceramic fuse IEC 127• Breaking capacity H 1500A• Voltage drop V = 150 mV• I 2 t = 48A 2 sWhen choosing all fuses, please refer to the LEGRAND catalogue136