Chapter 5 — ConfigurationBulletin No. 50006-519-01B7 →General Configuration Menu December 1996SP GAIN17 – 8= ⎛---------------⎞× 9999 = 6000⎝20 – 5⎠OFFSET8–5= ⎛---------------⎞× 9999 = 2000⎝20 – 5⎠5. Select FEED BACK in the PI Regulator screen.6. Select FB INPUT.7. Select AI2 for feedback input.8. Select MIN FEED BACK.9. Enter 5 for the minimum process level.10. Select MAX FEED BACK.11. Enter 20 for the maximum process level.12. If desired, enter optional LOW LEVEL ALM and HIGH LEVEL ALM values.13. Select YES for REV. ACTION in PI PARAMETERS menu.14. Adjust KP and KI to achieve the best system response.Example 2This example is the same as Example 1, except it uses the keypad as the means forsetpoint entry. The desired setpoint is 12.5 feet.1. Select YES, SET POINT in the PI Regulator menu.2. Select KEYPAD as means for setpoint entry.3. Calculate SP GAIN and OFFSET as illustrated in Example 1 and enter thevalue.4. Select FEED BACK in the PI Regulator screen.5. Select FB INPUT.6. Select AI2 for feedback input.7. Select MIN FEED BACK.8. Enter 8 for the minimum process level.9. Select MAX FEED BACK.10. Enter 17 for the maximum process level.11. If desired, enter optional LOW LEVEL ALM and HIGH LEVEL ALM values.12. Calculate PI SET POINT and enter the value in the 1→Parameter Settingmenu.PI SET POINT12.5 – 8= ⎛--------------------⎞× 9999 = 5000⎝ 17 – 8 ⎠13. Select YES for REV. ACTION in PI PARAMETERS menu.14. Adjust KP and KI to achieve the best system response.Example 3In this example, the drive controller will be used to regulate the volume of waterin a vat. The pump will be pumping water into the vat to maintain the levelbetween 100 m 3 and 10 m 3 . The feedback signal is 0 to 20 mA. At 5 m 3 the feedbacksignal is 0 mA, and at 100 m 3 the feedback signal is 20 mA. A 0 to 10 V signal isused for the setpoint. At 0 V the process level is 100 m 3 , and at 10 V the process levelis 10 m 3 .1. Select YES, SET POINT in the PI Regulator menu.2. Select SP INPUT.92 © 1996 Square D All Rights Reservedηττπ://νιχοντρολσ.χοm

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!