Modbus RTU Server<br />
Protocol Settings<br />
In this page you can make changes to the Modbus communication configuration.<br />
A Modbus RTU connection can be established over each of the 3 electrical<br />
interfaces: RS-232, RS-485 and Ethernet (TCP/IP). It’s recommended to use one<br />
connection at the same time. Check the checkbox next to Enabled of the electrical<br />
interface you want to use and uncheck the other two.<br />
At RS-232 and RS-485 you can specify a ‘Slave-address’. This is the modbus<br />
slave address the gateway will respond to at modbus requests form a modbus<br />
client.<br />
Also the modbus inter-frame timeout can be specified. If the checkbox before ‘Auto’<br />
is checked, the gateway will calculate the inter-frame timeout automatically. In most<br />
cases this auto timeout is sufficient for reliable communication.<br />
Sometimes it’s desirable to manually specify the inter-frame timeout to be able to<br />
adjust the value to the connected client. For example if the client drops out in the<br />
middle of a modbus frame for a long period of time, the frames don’t always survive<br />
intact when they’ve reached the gateway. This could lead to frame-errors and<br />
delays in the communication. In this case uncheck the checkbox before ‘Auto’ and<br />
specify the inter-frame timeout in the field next to it (in tenths of milliseconds).<br />
Under ‘Modbus on TCP/IP’ you can specify the TCP Port number at which the<br />
gateway listens for modbus requests. Match this to the Port number at which the<br />
modbus client sends out its requests. The default TCP Port for modbus<br />
communications and also the gateway’s factory default is 502.<br />
NOTE:<br />
!! When applying the settings (‘Apply Settings’) all communications could be<br />
interrupted temporarily.<br />
14/17<br />
Persy Control Services B.V.<br />
Netherlands<br />
<strong>PBGW2.128</strong> – P-bus <strong>Gateway</strong><br />
PCS0113en<br />