Modbus RTU Server<br />

Protocol Settings<br />

In this page you can make changes to the Modbus communication configuration.<br />

A Modbus RTU connection can be established over each of the 3 electrical<br />

interfaces: RS-232, RS-485 and Ethernet (TCP/IP). It’s recommended to use one<br />

connection at the same time. Check the checkbox next to Enabled of the electrical<br />

interface you want to use and uncheck the other two.<br />

At RS-232 and RS-485 you can specify a ‘Slave-address’. This is the modbus<br />

slave address the gateway will respond to at modbus requests form a modbus<br />

client.<br />

Also the modbus inter-frame timeout can be specified. If the checkbox before ‘Auto’<br />

is checked, the gateway will calculate the inter-frame timeout automatically. In most<br />

cases this auto timeout is sufficient for reliable communication.<br />

Sometimes it’s desirable to manually specify the inter-frame timeout to be able to<br />

adjust the value to the connected client. For example if the client drops out in the<br />

middle of a modbus frame for a long period of time, the frames don’t always survive<br />

intact when they’ve reached the gateway. This could lead to frame-errors and<br />

delays in the communication. In this case uncheck the checkbox before ‘Auto’ and<br />

specify the inter-frame timeout in the field next to it (in tenths of milliseconds).<br />

Under ‘Modbus on TCP/IP’ you can specify the TCP Port number at which the<br />

gateway listens for modbus requests. Match this to the Port number at which the<br />

modbus client sends out its requests. The default TCP Port for modbus<br />

communications and also the gateway’s factory default is 502.<br />

NOTE:<br />

!! When applying the settings (‘Apply Settings’) all communications could be<br />

interrupted temporarily.<br />

14/17<br />

Persy Control Services B.V.<br />

Netherlands<br />

<strong>PBGW2.128</strong> – P-bus <strong>Gateway</strong><br />

PCS0113en<br />

02.2009