– The Approach and Experiences in ICC - Department of Building ...
– The Approach and Experiences in ICC - Department of Building ...
– The Approach and Experiences in ICC - Department of Building ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
CPD Technical Sem<strong>in</strong>ar, CIBSE (Hong Kong Branch), ASHRAE<br />
(Hong Kong Chapter) <strong>and</strong> HKIE (BS division)<br />
17, March 2010, Hong Kong<br />
Build<strong>in</strong>g Energy Sav<strong>in</strong>g through Optimization<br />
<strong>and</strong> Life-cycle Commission<strong>in</strong>g<br />
<strong>–</strong> <strong>The</strong> <strong>Approach</strong> <strong>and</strong> <strong>Experiences</strong> <strong>in</strong> <strong>ICC</strong><br />
Shengwei Wang (王盛衛 王盛衛 王盛衛) 王盛衛<br />
Chair Pr<strong>of</strong>essor <strong>of</strong> Build<strong>in</strong>g Services Eng<strong>in</strong>eer<strong>in</strong>g<br />
<strong>Department</strong> <strong>of</strong> Build<strong>in</strong>g Services Eng<strong>in</strong>eer<strong>in</strong>g<br />
<strong>The</strong> Hong Kong Polytechnic University<br />
A A Simple Simple View View <strong>of</strong> <strong>of</strong> Energy Energy Sav<strong>in</strong>g Sav<strong>in</strong>g Potentials Potentials for for Build<strong>in</strong>g<br />
Build<strong>in</strong>g<br />
HVAC&R HVAC&R Systems Systems <strong>in</strong> <strong>in</strong> Operation<br />
Operation<br />
- HVAC, light<strong>in</strong>g, lift, …<br />
Design: Configuration,<br />
Components selection, etc.<br />
10~20%<br />
Sav<strong>in</strong>g Potential<br />
System operation <strong>and</strong><br />
Control Optimization<br />
Build<strong>in</strong>g Build<strong>in</strong>g Build<strong>in</strong>g Energy Energy Sav<strong>in</strong>g<br />
Sav<strong>in</strong>g<br />
HVAC&R Systems<br />
Energy Sav<strong>in</strong>g Potential<br />
20~30%<br />
Sav<strong>in</strong>g Potential<br />
System, component <strong>and</strong> BAS<br />
commission<strong>in</strong>g <strong>and</strong> diagnosis
Outl<strong>in</strong>e <strong>of</strong> Presentation<br />
• Introduction to <strong>ICC</strong> build<strong>in</strong>g systems;<br />
• Our roles <strong>in</strong> <strong>ICC</strong> project;<br />
• <strong>The</strong> concept <strong>of</strong> “commission<strong>in</strong>g”<br />
• Examples <strong>of</strong> commission<strong>in</strong>g efforts at design,<br />
<strong>in</strong>stallation, T&C <strong>and</strong> operation stages;<br />
• Sav<strong>in</strong>g Energy through Control Optimization<br />
control strategies implemented<br />
examples <strong>of</strong> control strategies<br />
• Summary <strong>of</strong> energy benefits<br />
• Summary <strong>of</strong> experiences <strong>in</strong> <strong>ICC</strong><br />
International F<strong>in</strong>ance Centre (<strong>ICC</strong>)<br />
Floor Area:<br />
Hotel 70,000 (m 2 )<br />
Office 286,000 (m 2 )<br />
Commercial center<br />
67,000 (m 2 )<br />
Gross 440,000 (m 2 )<br />
Six-star Hotel<br />
High-rank<br />
commercial<br />
<strong>of</strong>fice<br />
Commercial center <strong>and</strong><br />
basement<br />
490 m<br />
118 F
A<br />
D<br />
E<br />
F<br />
G<br />
PCHWP-06-01<br />
EVAPORAROR<br />
WCC-06a-01<br />
(2040 Ton)<br />
COOLING<br />
TOWER 1<br />
FROM PODIUM & BASEMENT<br />
TO PODIUM & BASEMENT<br />
HX HX<br />
(S-B) (S-B)<br />
SCHWP-06-10 to 12<br />
SCHWP-06-01 to 02<br />
COOLING<br />
TOWER 2<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
EVAPORATOR<br />
COOLING<br />
TOWER 3<br />
B<br />
COOLING<br />
TOWER 4<br />
FROM OFF<strong>ICC</strong>E FLOORS(7-41)<br />
TO OFFICE FLOORS(7-41)<br />
EVAPORATOR EVAPORATOR EVAPORATOR EVAPORATOR<br />
COOLING<br />
TOWER 5<br />
COOLING<br />
TOWER 6<br />
HX HX HX HX HX HX HX<br />
PCHWP-06-02 PCHWP-06-03 PCHWP-06-04 PCHWP-06-05 PCHWP-06-06<br />
WCC-06a-02<br />
(2040 Ton)<br />
Secondary water circuit for Zone 1<br />
Secondary water circuit for Zone 2<br />
Secondary water circuit for Zone<br />
3 <strong>and</strong> Zone 4<br />
Primary water circuit<br />
Chiller circuit<br />
Cool<strong>in</strong>g water circuit<br />
Cool<strong>in</strong>g tower circuit<br />
(S-B)<br />
WCC-06a-03<br />
(2040 Ton)<br />
WCC-06a-04<br />
(2040 Ton)<br />
COOLING<br />
TOWER 7<br />
COOLING<br />
TOWER 8<br />
WCC-06a-05<br />
(2040 Ton)<br />
CDWP-06-01 CDWP-06-02 CDWP-06-03 CDWP-06-04<br />
CDWP-06-05 CDWP-06-06<br />
C<br />
COOLING<br />
TOWER 9<br />
FROM OFFICE FLOORS (43-77)<br />
COOLING<br />
TOWER 10<br />
TO OFFICE FLOORS (43-77)<br />
WCC-06a-06<br />
(2040 Ton)<br />
CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER<br />
CT-06a-01 CT-06a-02 CT-06a-03 CT-06a-04 CT-06a-05 CT-06a-06 CTA-06a-01 CTA-06a-02 CTA-06a-03 CTA-06a-04 CTA-06a-05<br />
CTA Towers (without heat<strong>in</strong>g coil)<br />
SCHWP-06-03 to 05<br />
HX<br />
SCHWP-78-01 to 03<br />
PCHWP-78-01 PCHWP-78-02<br />
HX<br />
SCHWP-42-04 to 06<br />
FROM OFFICE FLOORS (79-98)<br />
TO OFFICE FLOORSS (79-98)<br />
PCHWP-78-03<br />
HX<br />
(S-B)<br />
(S-B)<br />
(S-B)<br />
(S-B)<br />
SCHWP-42-01 to 03<br />
PCHWP-42-01 PCHWP-42-02 PCHWP-42-03 PCHWP-42-04 PCHWP-42-05 PCHWP-42-06 PCHWP-42-07<br />
SCHWP-06-06 to 09<br />
CTB Towers (with heat<strong>in</strong>g coil)<br />
Our Our Our Our Our Roles Roles Roles Roles <strong>in</strong> <strong>in</strong> <strong>in</strong> <strong>in</strong> <strong>ICC</strong> <strong>ICC</strong> <strong>ICC</strong> <strong>ICC</strong> Project<br />
Project<br />
Project<br />
Project<br />
� Independent Energy Consultant<br />
(Independent Commission<strong>in</strong>g<br />
Agent)<br />
� Developer <strong>of</strong> HVAC Energy<br />
Optimization System (EOS)<br />
<strong>and</strong> Energy Performance<br />
Diagnosis System (EPDS)<br />
COOLING<br />
TOWER 11
� Summary <strong>of</strong> design power load <strong>of</strong> ma<strong>in</strong> HVAC<br />
equipments<br />
Chiller Pump Cool<strong>in</strong>g Tower Fan PAU Fan AHU Fan Total<br />
Number 6 36 11 29 152 234<br />
Rated Power (kW ) 1346 152<br />
Total load (kW ) 8076 4374 1672 513 4600 19235<br />
Percentage 41.99% 22.74% 8.69% 2.67% 23.91%<br />
� Annual electricity consumption <strong>of</strong> the central<br />
air-condition<strong>in</strong>g system is about 50,000,000 kWh<br />
Pr<strong>in</strong>ciple <strong>of</strong> Commission<strong>in</strong>g<br />
(校核 校核 校核/校校 校核 校核 校核 校核 校核 校校 校校及及及及及及及及改進<br />
校校 校校 校校 校校 校校 改進) 改進 改進 改進 改進 改進 改進<br />
� Commission<strong>in</strong>g is the process throughout the<br />
whole build<strong>in</strong>g lifecycle rather that one-<strong>of</strong>f task.<br />
� Commission<strong>in</strong>g is a valid means for<br />
improv<strong>in</strong>g energy performance <strong>of</strong><br />
build<strong>in</strong>gs <strong>and</strong> HVAC systems<br />
throughout the build<strong>in</strong>g life cycle.
Categories <strong>of</strong> Commission<strong>in</strong>g<br />
� Initial commission<strong>in</strong>g: Applied to a production <strong>of</strong> a new<br />
build<strong>in</strong>g <strong>and</strong>/or an <strong>in</strong>stallation <strong>of</strong> new systems.<br />
� Retro-commission<strong>in</strong>g: <strong>The</strong> first time commission<strong>in</strong>g<br />
implemented <strong>in</strong> an exist<strong>in</strong>g build<strong>in</strong>g <strong>in</strong> which a documented<br />
commission<strong>in</strong>g was not implemented before.<br />
� Re-commission<strong>in</strong>g: Implemented after the <strong>in</strong>itial<br />
commission<strong>in</strong>g or the retro-commission<strong>in</strong>g when the owner hopes to<br />
verify, improve <strong>and</strong> document the performance <strong>of</strong> build<strong>in</strong>g systems.<br />
� On-go<strong>in</strong>g/cont<strong>in</strong>uous commission<strong>in</strong>g: Conducted<br />
cont<strong>in</strong>ually for the purposes <strong>of</strong> ma<strong>in</strong>ta<strong>in</strong><strong>in</strong>g, improv<strong>in</strong>g <strong>and</strong><br />
optimiz<strong>in</strong>g the performance <strong>of</strong> build<strong>in</strong>g systems after the <strong>in</strong>itial<br />
commission<strong>in</strong>g or the retro-commission<strong>in</strong>g.<br />
Life-Cycle Life ycle Commission<strong>in</strong>g<br />
ommission<strong>in</strong>g<br />
� <strong>The</strong> build<strong>in</strong>g pr<strong>of</strong>ession <strong>in</strong> Northern American <strong>and</strong><br />
European countries has been promot<strong>in</strong>g the new concept <strong>of</strong><br />
life-cycle “Commission<strong>in</strong>g” <strong>and</strong> role <strong>of</strong> “Independent<br />
Commission<strong>in</strong>g Agent” over the last few years.<br />
� Commission<strong>in</strong>g is the process throughout the whole<br />
build<strong>in</strong>g lifecycle rather that one-<strong>of</strong>f task as conventional<br />
“Test <strong>and</strong> Commission<strong>in</strong>g”.<br />
It is performed regularly throughout the whole build<strong>in</strong>g lifecycle from<br />
early plann<strong>in</strong>g, design, construction <strong>and</strong> <strong>in</strong>stallation to operation<br />
for ensur<strong>in</strong>g that systems are designed, <strong>in</strong>stalled, functionally tested<br />
<strong>and</strong> capable <strong>of</strong> be<strong>in</strong>g operated <strong>and</strong> ma<strong>in</strong>ta<strong>in</strong>ed properly.<br />
� Commission<strong>in</strong>g is an effective means for improv<strong>in</strong>g<br />
energy performance <strong>of</strong> build<strong>in</strong>gs <strong>and</strong> HVAC systems<br />
throughout the build<strong>in</strong>g life cycle.<br />
• An average payback period for commission<strong>in</strong>g <strong>of</strong> new<br />
build<strong>in</strong>gs is 4.8 years <strong>in</strong> United States.<br />
• Average energy cost sav<strong>in</strong>g for periodical commission<strong>in</strong>g<br />
<strong>of</strong> exist<strong>in</strong>g build<strong>in</strong>g is 15%.
Life-Cycle Life ycle Commission<strong>in</strong>g<br />
ommission<strong>in</strong>g<br />
� <strong>The</strong> build<strong>in</strong>g pr<strong>of</strong>ession <strong>in</strong> Northern American <strong>and</strong><br />
European countries has been promot<strong>in</strong>g the new concept <strong>of</strong><br />
life-cycle “Commission<strong>in</strong>g” <strong>and</strong> role <strong>of</strong> “Independent<br />
Commission<strong>in</strong>g Agent” over the last few years.<br />
� Commission<strong>in</strong>g <strong>ICC</strong> project is the is one process <strong>of</strong> the throughout very first the whole full scale<br />
build<strong>in</strong>g trial lifecycle <strong>of</strong> the new rather concept that one-<strong>of</strong>f <strong>of</strong> “Commission<strong>in</strong>g”<br />
task as conventional<br />
“Test <strong>and</strong> Commission<strong>in</strong>g”.<br />
<strong>and</strong> “Independent Commission<strong>in</strong>g Agent” <strong>in</strong><br />
It is performed regularly throughout the whole build<strong>in</strong>g lifecycle from<br />
early very plann<strong>in</strong>g, large design, <strong>and</strong> construction complex <strong>and</strong> build<strong>in</strong>g <strong>in</strong>stallation system to operation <strong>in</strong><br />
for ensur<strong>in</strong>g that systems are designed, <strong>in</strong>stalled, functionally tested<br />
<strong>and</strong> Asia. capable It <strong>of</strong> be<strong>in</strong>g is a very operated attractive <strong>and</strong> ma<strong>in</strong>ta<strong>in</strong>ed contribution properly. to the<br />
IEA Research programme Annex 47.<br />
� Commission<strong>in</strong>g is an effective means for improv<strong>in</strong>g<br />
energy performance <strong>of</strong> build<strong>in</strong>gs <strong>and</strong> HVAC systems<br />
throughout the build<strong>in</strong>g life cycle.<br />
• An average payback period for commission<strong>in</strong>g <strong>of</strong> new<br />
build<strong>in</strong>gs is 4.8 years <strong>in</strong> United States.<br />
• Average energy cost sav<strong>in</strong>g for periodical commission<strong>in</strong>g<br />
<strong>of</strong> exist<strong>in</strong>g build<strong>in</strong>g is 15%.<br />
Commission<strong>in</strong>g Commission<strong>in</strong>g <strong>and</strong> <strong>and</strong> <strong>and</strong> examples examples <strong>of</strong><br />
<strong>of</strong><br />
efforts efforts at at design, design, design, <strong>in</strong>stallation, <strong>in</strong>stallation, T&C<br />
T&C<br />
<strong>and</strong> <strong>and</strong> operation operation stages<br />
stages
Development <strong>of</strong> Virtual Build<strong>in</strong>g System - Dynamic<br />
simulation platform <strong>of</strong> the complex HVACR system<br />
Load & status <strong>of</strong> AHUs<br />
Zone airflow rates<br />
Load & status <strong>of</strong> AHUs<br />
On/Off<br />
<strong>of</strong> AHUs<br />
On/Off <strong>of</strong> AHUs<br />
TYPE 49<br />
Ma,i&Ta,<strong>in</strong><br />
On/Off <strong>of</strong> AHUs<br />
TYPE 35<br />
On/Off <strong>of</strong> AHUs Ma,i&Ta,<strong>in</strong><br />
On/Off <strong>of</strong> AHUs Ma,i&Ta,<strong>in</strong><br />
Pump & network Mw,i AHUs<br />
TYPE 17 TYPE 63<br />
Mw,i<br />
Pump & network AHUs<br />
TYPE 13 TYPE 21<br />
Freq<br />
Tao,i<br />
PID control PID control<br />
TYPE 43 TYPE 20<br />
VPi<br />
Pump sequence Npu PD<br />
optimizer<br />
TYPE 39<br />
TYPE 7<br />
PDset<br />
Mix<strong>in</strong>g<br />
TYPE 60<br />
Tw,<strong>in</strong> &Mw<br />
HX sequence Nhx HX model<strong>in</strong>g<br />
&mix<strong>in</strong>g<br />
TYPE 39<br />
TYPE 41<br />
Nhx<br />
Pump & network<br />
TYPE 14<br />
Freq Mw,meas<br />
Tw,out<br />
PID control Mw,set PID control<br />
TYPE 43 TYPE 43<br />
Zone 1 Zone 1<br />
Return pipe<br />
TYPE 31<br />
Pump & network Mw,i AHUs<br />
TYPE 12 TYPE 63<br />
Freq<br />
Tao,i<br />
PID control PID control<br />
TYPE 43 TYPE 42<br />
VPi<br />
Pump sequence Npu PD<br />
optimizer<br />
TYPE 39<br />
TYPE 6<br />
PDset<br />
Mix<strong>in</strong>g<br />
Zone 2<br />
TYPE 48<br />
Zone 2<br />
Mw & Tw,rtn Mw & Tw,rtn<br />
Mix<strong>in</strong>g<br />
TYPE 61<br />
Mw,tot & Tw,rtn<br />
Mw & Tw,rtn<br />
Tw,rtn & Mw,tot<br />
Mw,i<br />
Pump & network AHUs<br />
Freq<br />
Tao,i<br />
TYPE 18 TYPE 63<br />
PID control PID control<br />
Freq<br />
Tao,i<br />
TYPE 43 TYPE 42<br />
PID control PID control<br />
VPi<br />
TYPE 43 TYPE 42<br />
Pump sequence Npu PD<br />
VPi<br />
optimizer<br />
TYPE 39 TYPE 62<br />
Pump sequence Npu PD<br />
PDset<br />
optimizer<br />
TYPE 39<br />
TYPE 8<br />
HX sequence Mix<strong>in</strong>g<br />
Load<br />
PDset<br />
TYPE 39 TYPE 47<br />
Nhx<br />
HX sequence Mix<strong>in</strong>g<br />
Pump & network HX model<strong>in</strong>g<br />
Mw &mix<strong>in</strong>g<br />
TYPE 39 Nhx TYPE Zones 47 3&4 3&4<br />
TYPE 15<br />
TYPE 36<br />
Freq Mw,meas<br />
Tw,<strong>in</strong><br />
Pump sequence HX model<strong>in</strong>g<br />
&mix<strong>in</strong>g<br />
TYPE 39<br />
PID control<br />
TYPE 37<br />
TYPE 43<br />
Mw Npu<br />
Tw,sup<br />
Mw,set<br />
&Mw<br />
Pump & network<br />
PID control Mix<strong>in</strong>g &<br />
TYPE 16<br />
TYPE 43<br />
bypass<br />
Freq Mw,meas<br />
Tw,out<br />
TYPE 19<br />
PID control Mw,set PID control<br />
Pump sequence<br />
TYPE 43 TYPE 43<br />
TYPE 39<br />
Tw,rtn & Mw Mix<strong>in</strong>g & bypass<br />
Tw,sup & Mw TYPE 45 Zone 3&4<br />
Tsup Supply pipe<br />
TYPE 31<br />
Mix<strong>in</strong>g & Bypass<br />
TYPE XX: Component type number<br />
TYPE 67<br />
T: Temperature<br />
Tw,sup<br />
Mw & PDmeas<br />
Data Reader<br />
TYPE 9<br />
Twb&Tdb<br />
Mw,tot& Trtn<br />
Mw<br />
Ma,i&Ta,<strong>in</strong><br />
Tsup<br />
Chiller sequence controller<br />
TYPE 50<br />
Cool<strong>in</strong>g tower controller<br />
TYPE 3&54&55<br />
Tw,out,i On/Off,i&Freq,i<br />
On/Off<br />
<strong>of</strong> AHUs<br />
Tw,sup<br />
Mw & PDmeas<br />
Chiller One<br />
TYPE 23<br />
Chiller Two<br />
TYPE 23<br />
Chiller Three<br />
TYPE 23<br />
Chiller Four<br />
TYPE 23<br />
Mix<strong>in</strong>g after chiller condensers<br />
TYPE 4<br />
Chiller Five<br />
TYPE 23<br />
Chiller Six<br />
TYPE 23<br />
CTA One CTA Two CTA Three CTA Four CTA Five CTA Six CTB One CTB Two CTB Three CTB Four CTB Five<br />
TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2<br />
Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw<br />
Mix<strong>in</strong>g after cool<strong>in</strong>g towers<br />
TYPE 5<br />
Tw,sup<br />
On/Off<br />
<strong>of</strong> AHUs<br />
Tw,ch,out Tw,ch,out Tw,ch,out Tw,ch,out Tw,ch,out Tw,ch,out<br />
Nch On/Off On/Off On/Off On/Off On/Off On/Off<br />
Nch Tw,cd,out Tw,cd,out Tw,cd,out Tw,cd,out Tw,cd,out Tw,cd,out<br />
Mw,tot&Tw,ct,<strong>in</strong><br />
Mw,tot&Tw,ct,out<br />
Tw,cd,out<br />
Load<br />
Nhx<br />
Mw<br />
On/Off<br />
<strong>of</strong> AHUs<br />
Tw,cd,<strong>in</strong><br />
Tw,sup<br />
Mw & Tw,<strong>in</strong><br />
Mw & PDmeas<br />
Mw<br />
Npu<br />
M:<br />
Load:<br />
Freq:<br />
N:<br />
VP:<br />
PD:<br />
Subscript<br />
w:<br />
ao:<br />
<strong>in</strong>:<br />
rtn:<br />
cd:<br />
ct:<br />
hx:<br />
wb:<br />
Water<br />
Air outlet<br />
Inlet<br />
Return<br />
Nhx<br />
Tw,out<br />
Number<br />
Condenser<br />
Tw,rtn& Mw<br />
Water or air flow rate<br />
Cool<strong>in</strong>g load<br />
Frequency<br />
Valve position<br />
meas: Measurement<br />
Pressure differential<br />
Cool<strong>in</strong>g tower<br />
Heat exchanger<br />
Wet-bulb<br />
a:<br />
i:<br />
Air<br />
tot: Total<br />
pu: Pump<br />
sup: Supply<br />
Mw,&w,<strong>in</strong><br />
Tw,rtn& Mw<br />
Individual<br />
set: Set-po<strong>in</strong>t<br />
ch: Chiller<br />
out: Outlet<br />
db: Dry-bulb<br />
Development <strong>of</strong> Virtual Build<strong>in</strong>g System - Dynamic<br />
simulation platform <strong>of</strong> the complex HVACR system<br />
Load & status <strong>of</strong> AHUs<br />
Zone airflow rates<br />
Load & status <strong>of</strong> AHUs<br />
On/Off<br />
<strong>of</strong> AHUs<br />
On/Off <strong>of</strong> AHUs<br />
TYPE 49<br />
Ma,i&Ta,<strong>in</strong><br />
On/Off <strong>of</strong> AHUs<br />
Mw,i<br />
Pump & network AHUs<br />
Pump & network Mw,i<br />
TYPE 13 TYPE 21<br />
AHUs<br />
Freq<br />
Tao,i<br />
TYPE 12 TYPE 63<br />
PID control PID control<br />
Freq<br />
Tao,i<br />
TYPE 43 TYPE 20<br />
PID control PID control<br />
VPi<br />
TYPE 43 TYPE 42<br />
PD<br />
VPi<br />
Pump sequence Npu<br />
optimizer<br />
TYPE 39<br />
TYPE 7<br />
Pump sequence Npu PD<br />
optimizer<br />
PDset<br />
TYPE 39<br />
TYPE 6<br />
Mix<strong>in</strong>g<br />
PDset<br />
TYPE 60<br />
Tw,<strong>in</strong> &Mw<br />
Mix<strong>in</strong>g<br />
HX sequence Nhx HX model<strong>in</strong>g Zone 2<br />
&mix<strong>in</strong>g<br />
TYPE 48<br />
TYPE 39<br />
TYPE 41<br />
Nhx<br />
Zone Zone 2<br />
Pump & network<br />
Mw & Tw,rtn Mw & Tw,rtn<br />
TYPE 14<br />
Freq Mw,meas<br />
Tw,out<br />
PID control Mw,set PID control<br />
TYPE 43 TYPE 43<br />
Mix<strong>in</strong>g<br />
Zone 1<br />
TYPE 61<br />
Zone 1<br />
Mw,tot & Tw,rtn<br />
Mw & Tw,rtn<br />
Return pipe<br />
Tw,rtn & Mw,tot<br />
TYPE 31<br />
On/Off <strong>of</strong> AHUs Ma,i&Ta,<strong>in</strong><br />
TYPE 35<br />
Pump & network Mw,i AHUs<br />
On/Off <strong>of</strong> AHUs Ma,i&Ta,<strong>in</strong><br />
TYPE 17 TYPE 63<br />
Mw,i<br />
Pump & network AHUs<br />
Freq<br />
Tao,i<br />
TYPE 18 TYPE 63<br />
PID control PID control<br />
Freq<br />
Tao,i<br />
TYPE 43 TYPE 42<br />
PID control PID Virtual<br />
control<br />
VPi<br />
TYPE 43 TYPE 42<br />
Pump sequence Npu PD<br />
VPi<br />
optimizer<br />
TYPE 39 TYPE 62<br />
Pump sequence Npu PD<br />
PDset<br />
optimizer<br />
TYPE 39<br />
TYPE 8<br />
HX sequence Mix<strong>in</strong>g<br />
Load<br />
PDset<br />
TYPE 39 TYPE 47<br />
Nhx<br />
HX sequence Mix<strong>in</strong>g<br />
Pump & network HX model<strong>in</strong>g Build<strong>in</strong>g Mw &mix<strong>in</strong>g<br />
TYPE 39 Nhx TYPE Zones 47 3&4<br />
TYPE 15<br />
TYPE 36<br />
Freq Mw,meas<br />
Tw,<strong>in</strong><br />
Pump sequence HX model<strong>in</strong>g<br />
&mix<strong>in</strong>g<br />
TYPE 39<br />
PID control<br />
TYPE 37<br />
TYPE 43<br />
Mw Npu<br />
Tw,sup<br />
Mw,set<br />
&Mw<br />
Pump & network<br />
PID control Mix<strong>in</strong>g &<br />
TYPE 16<br />
TYPE 43<br />
bypass<br />
Freq Mw,meas<br />
Tw,out<br />
TYPE 19 System<br />
PID control Mw,set PID control<br />
Pump sequence<br />
TYPE 43 TYPE 43<br />
TYPE 39<br />
Tw,rtn & Mw Mix<strong>in</strong>g & bypass<br />
Tw,sup & Mw TYPE 45 Zone 3&4<br />
Tsup Supply pipe<br />
TYPE 31<br />
Mix<strong>in</strong>g & Bypass<br />
TYPE XX: Component type number<br />
TYPE 67<br />
T: Temperature<br />
Tw,sup<br />
Mw & PDmeas<br />
Mw,tot& Trtn<br />
Mw<br />
Ma,i&Ta,<strong>in</strong><br />
Tsup<br />
On/Off<br />
<strong>of</strong> AHUs<br />
Tw,sup<br />
Mw & PDmeas<br />
Tw,sup<br />
On/Off<br />
<strong>of</strong> AHUs<br />
Data Reader<br />
Tw,ch,out Tw,ch,out Tw,ch,out Tw,ch,out Tw,ch,out Tw,ch,out<br />
M: Water or air flow rate<br />
TYPE 9<br />
Chiller sequence controller Nch<br />
TYPE 50<br />
Nch<br />
Cool<strong>in</strong>g tower controller<br />
TYPE 3&54&55<br />
Tw,out,i On/Off,i&Freq,i<br />
Chiller One Chiller Two Chiller Three Chiller Four Chiller Five Chiller Six<br />
Load: Cool<strong>in</strong>g load<br />
TYPE 23 TYPE 23 TYPE 23 TYPE 23 TYPE 23 TYPE 23<br />
Freq: Frequency<br />
On/Off On/Off On/Off On/Off On/Off On/Off<br />
N: Number<br />
Tw,cd,<strong>in</strong> VP: Valve position<br />
Tw,cd,out Tw,cd,out Tw,cd,out Tw,cd,out Tw,cd,out Tw,cd,out<br />
PD: Pressure differential<br />
Mix<strong>in</strong>g after chiller condensers (updated throughout<br />
Subscript<br />
TYPE 4<br />
Mw,tot&Tw,ct,<strong>in</strong><br />
Tw,cd,out<br />
w: Water<br />
a: Air<br />
meas: Measurement i: Individual<br />
ao: Air outlet tot: Total<br />
<strong>in</strong>: Inlet<br />
pu: Pump<br />
CTA One CTA Two CTA Three CTA Four CTA Five CTA Six CTB One CTB Two CTB Three the CTB Fourentire<br />
CTB Five process)<br />
rtn: Return set: Set-po<strong>in</strong>t<br />
TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2<br />
cd: Condenser ch: Chiller<br />
Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw Tw,out & Mw<br />
ct: Cool<strong>in</strong>g tower out: Outlet<br />
Mix<strong>in</strong>g after cool<strong>in</strong>g towers<br />
hx: Heat exchanger sup: Supply<br />
TYPE 5<br />
Mw,tot&Tw,ct,out<br />
wb: Wet-bulb db: Dry-bulb<br />
Twb&Tdb<br />
Load<br />
Nhx<br />
Mw<br />
On/Off<br />
<strong>of</strong> AHUs<br />
Tw,sup<br />
Mw & Tw,<strong>in</strong><br />
Mw & PDmeas<br />
Mw<br />
Simulated<br />
Npu<br />
Nhx<br />
Tw,out<br />
Tw,rtn& Mw<br />
Mw,&w,<strong>in</strong><br />
Tw,rtn& Mw<br />
Tw,sup<br />
Tw,sup
A<br />
D<br />
E<br />
F<br />
Design Commission<strong>in</strong>g<br />
<strong>The</strong> design commission<strong>in</strong>g ma<strong>in</strong>ly concerns the<br />
future operation <strong>and</strong> control performance <strong>of</strong> HVAC<br />
systems, <strong>and</strong> <strong>in</strong>cludes:<br />
• Verification the system configuration <strong>and</strong> component<br />
selection <strong>in</strong>clud<strong>in</strong>g the chiller system, water system<br />
(primary/secondary system), heat rejection system<br />
(cool<strong>in</strong>g towers), fresh air system etc.<br />
• Verification <strong>of</strong> the meter<strong>in</strong>g system for proper local<br />
control, <strong>and</strong> the orig<strong>in</strong>al proposed control logics at the<br />
design stage.<br />
• Proposal <strong>of</strong> additional meter<strong>in</strong>g system for implement<strong>in</strong>g<br />
supervisory control strategies <strong>and</strong> diagnosis strategies<br />
<strong>and</strong> related facilities for implement<strong>in</strong>g these strategies<br />
( This is a typical energy-sav<strong>in</strong>g implementation from<br />
the earlier design <strong>and</strong> <strong>in</strong>stallation phase)<br />
HX-06<br />
PCHWP-06-01<br />
EVAPORAROR<br />
WCC-06a-01<br />
(2040 Ton)<br />
FROM PODIUM & BASEMENT<br />
TO PODIUM & BASEMENT<br />
HX-06<br />
(S-B) (S-B)<br />
A Secondary water circuit for Zone 1 C<br />
B Secondary water circuit for Zone 2<br />
C<br />
D Primary water circuit<br />
E Chiller circuit<br />
F Cool<strong>in</strong>g water circuit<br />
B<br />
EVAPORATOR<br />
FROM OFF<strong>ICC</strong>E FLOORS(7-41)<br />
TO OFFICE FLOORS(7-41)<br />
HX-42<br />
PCHWP-06-02 PCHWP-06-03 PCHWP-06-04 PCHWP-06-05 PCHWP-06-06<br />
WCC-06a-02<br />
(2040 Ton)<br />
Secondary water circuit for Zone<br />
3 <strong>and</strong> Zone 4<br />
(S-B)<br />
EVAPORATOR EVAPORATOR EVAPORATOR EVAPORATOR<br />
WCC-06a-03<br />
(2040 Ton)<br />
WCC-06a-04<br />
(2040 Ton)<br />
WCC-06a-05<br />
(2040 Ton)<br />
FROM OFFICE FLOORS (43-77)<br />
TO OFFICE FLOORS (43-77)<br />
CDWP-06-01 CDWP-06-02 CDWP-06-03 CDWP-06-04<br />
CDWP-06-05 CDWP-06-06<br />
(S-B)<br />
WCC-06a-06<br />
(2040 Ton)<br />
CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER CONDENSER<br />
From cool<strong>in</strong>g towers<br />
SCHWP-06-10 to 12<br />
SCHWP-06-01 to 02<br />
System Design Verification -<br />
Secondary water loop systems <strong>of</strong> 3rd <strong>and</strong> 4 th zones<br />
SCHWP-06-03 to 05<br />
HX-78<br />
SCHWP-78-01 to 03<br />
PCHWP-78-01 PCHWP-78-02<br />
HX-78<br />
SCHWP-42-04 to 06<br />
FROM OFFICE FLOORS (79-98)<br />
TO OFFICE FLOORSS (79-98)<br />
PCHWP-78-03<br />
HX-78<br />
(S-B)<br />
(S-B)<br />
(S-B)<br />
SCHWP-42-01 to 03<br />
PCHWP-42-01 PCHWP-42-02 PCHWP-42-03 PCHWP-42-04 PCHWP-42-05 PCHWP-42-06 PCHWP-42-07<br />
HX-42 HX-42 HX-42 HX-42 HX-42 HX-42<br />
SCHWP-06-06 to 09<br />
Orig<strong>in</strong>al Orig<strong>in</strong>al Orig<strong>in</strong>al Orig<strong>in</strong>al System System System System<br />
HX-78<br />
SCHWP-78-01 to 03<br />
HX-78<br />
SCHWP-42-04 to 06<br />
HX-78<br />
FROM OFFICE FLOORS (79-98)<br />
(S-B)<br />
TO OFFICE FLOORSS (79-98)<br />
HX-42 HX-42 HX-42 HX-42 HX-42 HX-42 HX-42<br />
From Zone 3&4<br />
SCHWP-06-06 to 09<br />
To cool<strong>in</strong>g towers<br />
Primary pumps are omitted<br />
(S-B)<br />
To Zone 3&4<br />
(S-B)<br />
FROM OFFICE FLOORS (43-77)<br />
(S-B)<br />
TO OFFICE FLOORS (43-77)<br />
SCHWP-42-01 to 03<br />
Revised Revised Revised Revised System System System System<br />
(operation (operation (operation (operation mode) mode) mode) mode)<br />
Flow meter<br />
Bypass valve
Pump power (kW )<br />
1400<br />
1200<br />
1000<br />
800<br />
600<br />
400<br />
200<br />
0<br />
Comparison between Two systems<br />
Orig<strong>in</strong>al design<br />
Alternative design<br />
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24<br />
Time (h )<br />
Typical sunnysummer<br />
day<br />
Annual Pump<br />
Energy Sav<strong>in</strong>g is<br />
1M kWh<br />
System Design Verification-<br />
Verification<br />
Cool<strong>in</strong>g tower system<br />
• A very special cool<strong>in</strong>g tower with large heat rejection<br />
capacity <strong>and</strong> a very large dimension (4*10*9)<br />
• High pressure drop through fill pack<strong>in</strong>g <strong>and</strong> silencer<br />
• Energy consumption is about 3.6 million a year with<br />
<strong>in</strong>tended two-stage control<br />
Annual sav<strong>in</strong>g potential <strong>of</strong> us<strong>in</strong>g variable speed<br />
cool<strong>in</strong>g towers is 2.4M compared with that<br />
us<strong>in</strong>g constant speed towers. It is 1.4M<br />
compared with that us<strong>in</strong>g two speed towers.<br />
• Energy consumption is about 2.6<br />
million a year with <strong>in</strong>tended<br />
VFD control from PolyU<br />
• However, energy consumption<br />
will <strong>in</strong>crease greatly to about 5.0<br />
million when s<strong>in</strong>gle-stage is used<br />
Silencer<br />
100 Pa<br />
Fill pack<strong>in</strong>g<br />
300 Pa 50 Pa<br />
Pressure drop<br />
From chiller<br />
To chiller
Example <strong>of</strong> CO 2 Sensor<br />
Installation<br />
Morgan<br />
Stanley<br />
CO CO22<br />
CO CO22<br />
CO CO22<br />
CO CO22<br />
CO CO22<br />
CO CO22<br />
AHU<br />
Flow stations<br />
CO CO2 2<br />
CO CO22<br />
CO CO22<br />
CO CO22<br />
CO CO22<br />
AHU<br />
CO CO22<br />
CO CO22<br />
CO CO22 CO2 CO2<br />
Kaish<strong>in</strong>g<br />
� CO 2 sensor calibration <strong>and</strong> commission<strong>in</strong>g<br />
CO2 concentration (ppm)<br />
Measurement accuracy <strong>of</strong> CO 2 sensors directly affects<br />
<strong>in</strong>door air quality <strong>and</strong> energy performance <strong>of</strong> air side<br />
system, which is therefore essential for implement<strong>in</strong>g<br />
optimal ventilation control strategy.<br />
700<br />
650<br />
600<br />
550<br />
500<br />
450<br />
400<br />
350<br />
300<br />
250<br />
Before calibration<br />
Fresh air (Measured) Return air (Measured)<br />
Supply air (Measured) Supply air (Calculated)<br />
200<br />
9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00<br />
Simple time (h)<br />
CO2 concentration (ppm)<br />
700<br />
650<br />
600<br />
550<br />
500<br />
450<br />
400<br />
350<br />
300<br />
250<br />
200<br />
Empty<br />
IC<br />
After calibration<br />
CO CO22<br />
CO CO22<br />
Fresh air (Measured) Return air (Measured)<br />
Supply air (Measured) Supply air (Calculated)<br />
CO CO22<br />
BB<br />
CO CO22<br />
CO CO22<br />
Empty<br />
Empty<br />
9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00<br />
Sample time (h)
∆P<br />
Q = A ⋅ v = A ⋅ 2∆P<br />
Example <strong>of</strong> air flow<br />
station Installation<br />
Cool<strong>in</strong>g Cool<strong>in</strong>g tower tower site site operation operation issue issue<br />
• We suggest all the cool<strong>in</strong>g tower fans are equipped with<br />
VFD for significant energy sav<strong>in</strong>gs, <strong>and</strong> the variable<br />
frequency range is from 50 Hz to 25 Hz at least.<br />
• At the test stage, the manufacture<br />
stated the m<strong>in</strong>imum frequency is 37<br />
Hz for cool<strong>in</strong>g requirement <strong>of</strong> the<br />
<strong>in</strong>side motor.<br />
• <strong>The</strong> manufacture f<strong>in</strong>ally confirmed the<br />
m<strong>in</strong>imum frequency is 20 Hz ensur<strong>in</strong>g<br />
the normal operation <strong>of</strong> the fan.<br />
This This This This low low low low frequency frequency frequency frequency <strong>in</strong>creases <strong>in</strong>creases <strong>in</strong>creases <strong>in</strong>creases the the the the<br />
energy energy energy energy sav<strong>in</strong>g sav<strong>in</strong>g sav<strong>in</strong>g sav<strong>in</strong>g potential potential potential potential greatly greatly greatly greatly<br />
at at at at partial partial partial partial load load load load conditions conditions conditions conditions !<br />
! ! !
Cool<strong>in</strong>g Cool<strong>in</strong>g tower tower site site operation operation issue issue<br />
• We suggest all the cool<strong>in</strong>g tower fans are equipped with<br />
VFD for significant energy sav<strong>in</strong>gs, <strong>and</strong> the variable<br />
frequency range is from 50 Hz to 25 Hz at least.<br />
• At the test stage, the manufacture<br />
stated the m<strong>in</strong>imum frequency is 37<br />
Hz <strong>The</strong> for cool<strong>in</strong>g sav<strong>in</strong>gs requirement is about 607,000 <strong>of</strong> the kWh , 2.86% <strong>of</strong><br />
<strong>in</strong>side motor.<br />
annual energy consumption <strong>of</strong> chillers <strong>and</strong><br />
cool<strong>in</strong>g towers due to the lower frequency limit.<br />
• <strong>The</strong> manufacture f<strong>in</strong>ally confirmed the<br />
m<strong>in</strong>imum frequency is 20 Hz ensur<strong>in</strong>g<br />
the normal operation <strong>of</strong> the fan.<br />
This This This This low low low low frequency frequency frequency frequency <strong>in</strong>creases <strong>in</strong>creases <strong>in</strong>creases <strong>in</strong>creases the the the the<br />
energy energy energy energy sav<strong>in</strong>g sav<strong>in</strong>g sav<strong>in</strong>g sav<strong>in</strong>g potential potential potential potential greatly greatly greatly greatly<br />
at at at at partial partial partial partial load load load load conditions conditions conditions conditions ! ! ! !<br />
Low Delta-T Central Plant Syndrome<br />
� Nearly all large primary-secondary chilled water<br />
systems suffer from low chilled water temperature<br />
difference, known as low delta-T central plant<br />
syndrome, result<strong>in</strong>g <strong>in</strong> <strong>in</strong>efficient operation.<br />
� When the low delta-T syndrome exists, a series <strong>of</strong><br />
operation problems will be resulted<br />
� <strong>The</strong> <strong>in</strong>ability to sufficiently<br />
load chillers;<br />
� Excess water flow dem<strong>and</strong>;<br />
� An <strong>in</strong>crease <strong>in</strong> pump energy;<br />
� Either an <strong>in</strong>crease <strong>in</strong> chiller<br />
energy or a failure to meet<br />
cool<strong>in</strong>g load; etc.<br />
Water flow rate (L/s)<br />
500<br />
400<br />
300<br />
200<br />
100<br />
0<br />
-100<br />
-200<br />
-300<br />
-400<br />
-500<br />
Temp. difference after decouple<br />
Water flow<br />
Chiller operat<strong>in</strong>g number<br />
0 12 24 36 48 60 72 84 96 108 120 132 144 156<br />
0<br />
168<br />
Sample time (hour)<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
Chiller number <strong>and</strong> Temp. difference
Low Delta-T Central Plant Syndrome<br />
� Nearly all large primary-secondary chilled water<br />
systems suffer from low chilled water temperature<br />
difference, known as low delta-T central plant<br />
syndrome, result<strong>in</strong>g <strong>in</strong> <strong>in</strong>efficient operation.<br />
Each phase <strong>in</strong> the life cycle <strong>of</strong> air-condition<strong>in</strong>g<br />
systems, <strong>in</strong>clud<strong>in</strong>g design, equipment selection,<br />
commission<strong>in</strong>g, operation <strong>and</strong> ma<strong>in</strong>tenance,<br />
may result <strong>in</strong> low delta-T problems.<br />
� When the low delta-T syndrome exists, a series <strong>of</strong><br />
operation problems will be resulted<br />
� <strong>The</strong> <strong>in</strong>ability to sufficiently<br />
load chillers;<br />
� Excess water flow dem<strong>and</strong>;<br />
� An <strong>in</strong>crease <strong>in</strong> pump energy;<br />
� applications.<br />
Either an <strong>in</strong>crease <strong>in</strong> chiller<br />
energy or a failure to meet<br />
cool<strong>in</strong>g load; etc.<br />
Temp. difference after decouple<br />
400<br />
300<br />
Water flow<br />
Some causes can be avoided, 200 but some<br />
100<br />
0<br />
<strong>of</strong> them cannot be avoided <strong>in</strong> some<br />
-100<br />
� Potential solutions<br />
Water flow rate (L/s)<br />
500<br />
-200<br />
-300<br />
-400<br />
-500<br />
Chiller operat<strong>in</strong>g number<br />
0 12 24 36 48 60 72 84 96 108 120 132 144 156<br />
0<br />
168<br />
Sample time (hour)<br />
� <strong>The</strong> use <strong>of</strong> variable primary-only systems;<br />
� <strong>The</strong> use <strong>of</strong> pressure-<strong>in</strong>dependent modulat<strong>in</strong>g<br />
control valves;<br />
� <strong>The</strong> use <strong>of</strong> bypass check valves;<br />
� Advanced control <strong>and</strong> operation strategies.<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
Chiller number <strong>and</strong> Temp. difference
System Improvement by us<strong>in</strong>g a Check Valve<br />
Check valve<br />
Primary<br />
pumps 01-06<br />
CHILLER 01<br />
CHILLER 02<br />
CHILLER 03<br />
CHILLER 04<br />
CHILLER 05<br />
CHILLER 06<br />
FM<br />
Secondary water<br />
circuit for Zone 1<br />
AHU<br />
AHU<br />
AHU<br />
Secondary<br />
Pumps 01-02<br />
Secondary water<br />
circuit for Zone 2<br />
Secondary water<br />
circuit for Zone 3&4<br />
� Experimental validation prior to a check valve is really<br />
<strong>in</strong>stalled<br />
� by us<strong>in</strong>g a ‘conceptual’ check valve <strong>in</strong> the chiller<br />
decouple ---- through fully clos<strong>in</strong>g down one <strong>of</strong> the<br />
isolation valves <strong>in</strong> the chiller decouple when the<br />
deficit flow was observed.<br />
AHU<br />
AHU<br />
AHU<br />
Secondary<br />
pumps 03-05<br />
� Summary <strong>of</strong> experimental results<br />
Outlet air temp. <strong>of</strong> AHU 1 <strong>in</strong> L15 (°C)<br />
Deficit flow (L/S)<br />
12.5<br />
12<br />
50<br />
0<br />
-50<br />
-100<br />
-150<br />
-200<br />
-250<br />
10:09:59<br />
10:24:58<br />
10:42:56<br />
10:58:57<br />
10:00:58<br />
10:17:58<br />
Clos<strong>in</strong>g the valve <strong>in</strong><br />
the decouple<br />
10:36:58<br />
10:51:59<br />
11:10:59<br />
11:06:59<br />
11:19:04<br />
5.5 °C set-po<strong>in</strong>t<br />
11:23:01<br />
11:39:01<br />
12:03:03<br />
12:21:03<br />
12:35:00<br />
13:00:01<br />
11:32:56<br />
11:54:58<br />
12:14:56<br />
12:29:58<br />
13:14:04<br />
12:48:56<br />
13:07:58<br />
Reopen the valve<br />
<strong>in</strong> the decouple<br />
5.0 °C set-po<strong>in</strong>t<br />
13:29:01<br />
13:43:58<br />
13:56:59<br />
14:13:58<br />
14:38:58<br />
14:52:04<br />
15:02:58<br />
15:16:57<br />
15:33:04<br />
15:47:59<br />
16:06:59<br />
16:23:01<br />
13:24:59<br />
Time<br />
13:37:59<br />
13:50:59<br />
14:08:59<br />
14:34:00<br />
14:44:56<br />
14:58:58<br />
15:10:56<br />
15:29:01<br />
15:39:00<br />
15:57:59<br />
16:15:58<br />
Cool<strong>in</strong>g load <strong>of</strong> chiller(kW)<br />
7000<br />
6500<br />
6000<br />
5500<br />
5000<br />
4500<br />
4000<br />
200<br />
0<br />
10:17:58<br />
10:36:58<br />
Clos<strong>in</strong>g the valve<br />
<strong>in</strong> the decouple<br />
10:51:59<br />
11:06:59<br />
11:19:04<br />
11:32:56<br />
11:54:58<br />
12:14:56<br />
12:29:58<br />
12:48:56<br />
Reset supply water<br />
temp. set po<strong>in</strong>t from<br />
5.5°C to 5 °C<br />
13:07:58<br />
13:24:59<br />
13:37:59<br />
13:50:59<br />
AHU<br />
AHU<br />
AHU<br />
Secondary<br />
pumps 06-08<br />
14:08:59<br />
14:34:00<br />
Reopen the valve <strong>in</strong><br />
the decouple<br />
Time<br />
Time<br />
Test procedure Cool<strong>in</strong>g energy <strong>of</strong> chillers<br />
Clos<strong>in</strong>g the valve<br />
Reset supply water<br />
Annual energy Reopen the valve <strong>in</strong><br />
<strong>in</strong> the decouple<br />
temp. set po<strong>in</strong>t from sav<strong>in</strong>g potential by us<strong>in</strong>g the check<br />
the decouple<br />
1800<br />
5.5°C to 5 °C<br />
16<br />
1600<br />
15.5 valve <strong>in</strong> <strong>ICC</strong> is about 325,800 1400kWh<br />
when compared<br />
15<br />
14.5<br />
1200<br />
1000<br />
to that without us<strong>in</strong>g the check valve.<br />
14<br />
800<br />
13.5<br />
600<br />
Us<strong>in</strong>g 'conceptual' check valve<br />
with similar weather condition<br />
by without us<strong>in</strong>g the check<br />
13<br />
400<br />
valve<br />
Total power (kW)<br />
14:44:56<br />
14:58:58<br />
15:10:56<br />
15:29:01<br />
15:39:00<br />
15:57:59<br />
16:15:58<br />
11:19:56<br />
11:30:02<br />
11:42:58<br />
11:52:59<br />
12:05:56<br />
12:16:58<br />
12:32:03<br />
12:46:56<br />
12:57:00<br />
13:07:04<br />
13:17:59<br />
13:31:59<br />
13:48:03<br />
13:56:01<br />
14:09:57<br />
14:28:03<br />
14:39:56<br />
14:48:00<br />
14:57:59<br />
Supply air temperature Energy consumptions<br />
Time
Onl<strong>in</strong>e performance test<strong>in</strong>g <strong>of</strong> control<br />
optimizers <strong>and</strong> diagnostic tools on the<br />
simulated virtual system<br />
Control optimizers <strong>and</strong> diagnostic tools should be tested on the virtual<br />
systems prior to site implementation<br />
Virtual Plants<br />
Simulated<br />
Communication<br />
Interfaces<br />
IBmanager<br />
Sav<strong>in</strong>g Energy through<br />
Control Optimization<br />
System Control Optimizer<br />
Simplified<br />
Models<br />
Optimization<br />
Strategies<br />
Performance<br />
Models<br />
Diagnosis<br />
Strategies<br />
Performance<br />
Prediction<br />
Diagnostic Tool<br />
Performance<br />
Prediction
Optimization for HVAC&R systems<br />
Optimization allows the <strong>of</strong> HVAC&R systems<br />
provide expected quality <strong>of</strong> services (comfort <strong>and</strong><br />
health environment) with reduced energy<br />
consumption by means <strong>of</strong> :<br />
• Optimiz<strong>in</strong>g design configuration;<br />
• Optimiz<strong>in</strong>g the selection <strong>and</strong> siz<strong>in</strong>g;<br />
• Optimal operation <strong>and</strong> control.<br />
Optimal control strategies for central<br />
air-condition<strong>in</strong>g air condition<strong>in</strong>g systems<br />
� Chiller sequence, optimal start<br />
Optimal chiller sequence - based on a more accurate cool<strong>in</strong>g load<br />
prediction us<strong>in</strong>g data fusion method, <strong>and</strong> consider<strong>in</strong>g dem<strong>and</strong> limit<strong>in</strong>g<br />
Adaptive onl<strong>in</strong>e strategy for optimal start - based on simplified subsystem<br />
dynamic models<br />
� Ventilation strategy for multi-zone air-condition<strong>in</strong>g<br />
system<br />
Optimal ventilation control strategy - based on ventilation needs <strong>of</strong><br />
<strong>in</strong>dividual zones <strong>and</strong> the energy benefits <strong>of</strong> fresh air <strong>in</strong>take<br />
� Peak dem<strong>and</strong> limit<strong>in</strong>g <strong>and</strong> global electricity cost<br />
management
Optimal control strategies for central<br />
air-condition<strong>in</strong>g air condition<strong>in</strong>g systems (cont’d) (cont d)<br />
� Chilled water system optimization<br />
Optimal pressure differential set po<strong>in</strong>t reset strategy<br />
Optimal pump sequence logic<br />
Optimal heat exchanger sequence logic<br />
Optimal control strategy for pumps <strong>in</strong> the cold water side <strong>of</strong> heat<br />
exchangers<br />
Optimal chilled water supply temperature set-po<strong>in</strong>t reset strategy<br />
� Cool<strong>in</strong>g water system optimization<br />
Optimal condenser <strong>in</strong>let water temperature set po<strong>in</strong>t reset strategy<br />
Optimal cool<strong>in</strong>g tower sequence<br />
Optimal control <strong>of</strong> condenser<br />
cool<strong>in</strong>g water systems
Optimal control <strong>of</strong> condenser cool<strong>in</strong>g water systems (cont’d) (cont d)<br />
� Formulation <strong>of</strong> the optimal control strategy<br />
It is designed us<strong>in</strong>g a model-based method<br />
• <strong>The</strong> overall structure <strong>of</strong> the optimal control strategy<br />
T wb, Q ev, N ch<br />
Def<strong>in</strong>e the search ranges<br />
for T w,cd,sup <strong>and</strong> N ct<br />
T w,cd,sup& N ct<br />
Onl<strong>in</strong>e measurements<br />
<strong>and</strong> control signals<br />
Measurement filter<br />
Simplified CTA <strong>and</strong><br />
Performance prediction<br />
CTB tower models<br />
Tw,cd,sup, NCTA, NCTB, Ma,, Pct , Freq<br />
Cost estimation & optimization algorithm<br />
Supervisory control strategy<br />
Simplified chiller<br />
model<br />
Optimal control sett<strong>in</strong>gs & cost<br />
(T w,cd,sup , N CTA , N CTB , Freq , P ch +P ct ) Optimization process<br />
N CTA<br />
T w,cd,sup<br />
N CTB<br />
Interface<br />
N ch &T wb<br />
T w,cd,sup<br />
Chiller plant control system<br />
(BAS)<br />
T w,cd,out<br />
P ch<br />
Freq<br />
Q ev , N ch , T w,ev,<strong>in</strong><br />
It consists <strong>of</strong> :<br />
Performance Performance predictor predictor<br />
predictor<br />
Cost Cost estimator estimator<br />
estimator<br />
Optimization Optimization tool<br />
tool<br />
Supervisory Supervisory strategy<br />
strategy<br />
• Objective function<br />
N ⎛ ch NCTA<br />
NCTB<br />
J = m<strong>in</strong>W<br />
= ⎜<br />
tot m<strong>in</strong>⎜∑<br />
Wch,<br />
k + ∑WCTA,<br />
i + ∑W<br />
Tw,<br />
cd , sup<br />
Tw,<br />
cd , sup ⎝ k=<br />
1 i=<br />
1<br />
j=<br />
1<br />
CTB,<br />
i<br />
Optimal control <strong>of</strong> condenser cool<strong>in</strong>g water systems (cont’d) (cont d)<br />
• Parameters to be optimized<br />
� <strong>The</strong> condenser water supply temperature set-po<strong>in</strong>t<br />
� <strong>The</strong> number <strong>of</strong> CTA towers operat<strong>in</strong>g<br />
� <strong>The</strong> number <strong>of</strong> CTB towers operat<strong>in</strong>g<br />
• Optimization tool ---HQS (hybrid quick search) method<br />
T<br />
T<br />
n,<br />
o<br />
w,<br />
cd , sup<br />
n,<br />
o<br />
w,<br />
cd,<br />
sup<br />
= h<br />
0<br />
+ h T<br />
1<br />
wb<br />
− ∆T<br />
≤ T<br />
⎛ Q<br />
+ h ⎜ 2 ⎜<br />
⎝ Qev,<br />
w,<br />
cd,<br />
sup<br />
ev<br />
≤ T<br />
des<br />
⎞<br />
⎟<br />
⎠<br />
n.<br />
o<br />
w,<br />
cd,<br />
sup<br />
• Operat<strong>in</strong>g constra<strong>in</strong>ts<br />
+ ∆T<br />
Control sett<strong>in</strong>g<br />
Upper limit<br />
Search range<br />
+Δx<br />
-Δx<br />
Low limit Search center (near optimal)<br />
� basic energy <strong>and</strong> mass balances (i.e., flow, heat, etc.)<br />
� mechanical limitations (i.e., fan speed, temperature, etc.)<br />
Time<br />
⎞<br />
⎟<br />
⎠
Temperature (°C )<br />
Optimal control <strong>of</strong> condenser cool<strong>in</strong>g water systems (cont’d) (cont d)<br />
� Performance tests <strong>and</strong> evaluation<br />
• Evaluation <strong>of</strong> control accuracy <strong>and</strong> computation performance<br />
32.00<br />
29.00<br />
26.00<br />
23.00<br />
20.00<br />
17.00<br />
14.00<br />
� Comparison between the HQS <strong>and</strong> GA-based strategies<br />
Items<br />
Seasons<br />
Spr<strong>in</strong>g Mild-summer Sunny-summer<br />
Typical work<strong>in</strong>g conditions<br />
Qload (kW) 25520.11 31213.61 37547.74<br />
Nch 4 5 6<br />
Tw,ev,<strong>in</strong> (°C) 9.92 9.82 9.83<br />
Tw,ev,out (°C) 5.50 5.50 5.50<br />
Tdb (°C) 22.55 27.76 33.66<br />
Twb (°C) 15.86 20.11 24.99<br />
Mw,cd (L/s) 410.10 410.10 410.10<br />
Items Tools<br />
HQS GA HQS GA HQS GA<br />
Optimization results<br />
Wch (kW) 3628.07 3644.90 5004.21 4994.37 6794.24 6799.59<br />
Wct (kW) 285.74 268.91 386.11 396.08 538.74 533.42<br />
Wch+Wct (kW) 3913.81 3913.81 5390.32 5390.45 7332.98 7333.01<br />
Optimal Tw,cd,sup (°C) 21.85 21.88 26.65 26.64 31.80 31.80<br />
NCTA 6 6 6 6 6 6<br />
NCTB 5 5 5 5 5 5<br />
Freq (Hz) 25.99 25.35 29.33 29.62 33.39 33.26<br />
Computational cost(s) 0.152 3.610 0.144 3.512 0.134 3.589<br />
<strong>The</strong> computational cost sav<strong>in</strong>g is 96.0%<br />
Dry-bulb Temp.<br />
Wet-bulb Temp.<br />
Optimal Temp. set-po<strong>in</strong>t<br />
Near optimal Temp. set-po<strong>in</strong>t<br />
Upper limit <strong>of</strong> set-po<strong>in</strong>t<br />
Low limit <strong>of</strong> set-po<strong>in</strong>t<br />
Optimal control <strong>of</strong> condenser cool<strong>in</strong>g water systems (cont’d) (cont d)<br />
• Evaluation <strong>of</strong> the Energy Performance<br />
� Comparison <strong>of</strong> condenser water supply temperature setpo<strong>in</strong>ts<br />
us<strong>in</strong>g HQS-based strategy <strong>and</strong> near optimal strategy<br />
0 2 4 6 8 10 12 14 16 18 20 22 24<br />
Time (h )<br />
Optimal temperature set-po<strong>in</strong>t<br />
Spr<strong>in</strong>g Spr<strong>in</strong>g case case<br />
38.00 Dry-bulb Temp.<br />
Wet-bulb Temp. Sunny<br />
Optimal Temp. set-po<strong>in</strong>t<br />
35.00 Near optimal Temp. set-po<strong>in</strong>t<br />
Upper limit <strong>of</strong> set-po<strong>in</strong>t<br />
32.00 Low limit <strong>of</strong> set-po<strong>in</strong>t<br />
Temperature (°C)<br />
29.00<br />
26.00<br />
23.00<br />
20.00<br />
0 2 4 6 8 10 12 14 16 18 20 22 24<br />
Time (h )<br />
Near-optimal temperature set-po<strong>in</strong>t<br />
Sunny-summer summer case case<br />
case
Power difference ( kW )<br />
Optimal control <strong>of</strong> condenser cool<strong>in</strong>g water systems (cont’d) (cont d)<br />
� Comparison <strong>of</strong> the hourly-based power consumptions us<strong>in</strong>g<br />
different control methods<br />
40<br />
30<br />
20<br />
10<br />
0<br />
-10<br />
-20<br />
Optimal strategy<br />
Near optimal strategy<br />
Fixed approach<br />
-30<br />
0 2 4 6 8 10 12 14 16 18 20 22 24<br />
Time (h )<br />
HQS-based strategy<br />
Spr<strong>in</strong>g case<br />
Spr<strong>in</strong>g case 210<br />
Optimal strategy Sunny<br />
180 Near optimal strategy<br />
Power difference ( kW )<br />
150<br />
120<br />
90<br />
60<br />
30<br />
0<br />
-30<br />
Fixed<br />
approach<br />
0 2 4 6 8 10 12 14 16 18 20 22 24<br />
Time (h )<br />
Near optimal strategy<br />
Sunny-summer summer case<br />
case<br />
Optimal control <strong>of</strong> condenser cool<strong>in</strong>g water systems (cont’d) (cont d)<br />
� Comparison <strong>of</strong> daily <strong>and</strong> annual power consumptions <strong>of</strong> the<br />
condenser cool<strong>in</strong>g water system us<strong>in</strong>g different control methods<br />
• Daily power consumptions<br />
Operation<br />
Strategies<br />
Fixed approach<br />
Wct+Wch<br />
(kWh)<br />
Near optimal strategy<br />
Wct+Wch Sav<strong>in</strong>g Sav<strong>in</strong>g<br />
(kWh) (kWh) (%)<br />
HQS-based strategy<br />
Wct+Wch Sav<strong>in</strong>g Sav<strong>in</strong>g<br />
(kWh) (kWh) (%)<br />
Spr<strong>in</strong>g 51,738 51,623 114.53 0.221 51,404 334.30 0.646<br />
Mild-summer 71,289 70,668 621.49 0.872 70,560 729.36 1.023<br />
Sunnysummer<br />
91,653 90,878 775.44 0.846 90,356 1,297.50 1.416<br />
• Annual power consumptions<br />
Operation<br />
strategies<br />
Wch<br />
(kWh)<br />
Wct<br />
(kWh)<br />
Wcd,pu<br />
(kWh)<br />
Wtot<br />
(kWh)<br />
Sav<strong>in</strong>g<br />
(kWh)<br />
Sav<strong>in</strong>g<br />
(%)<br />
Fixed approach 18,464,812 1,882,583 4,210,690 24,558,085 --- ---<br />
Near optimal 18,715,458 1,501,701 4,210,690 24,427,849 130,236 0.530<br />
HQS-based 18,715,134 1,448,765 4,210,690 24,374,589 183,496 0.747
Operation modes<br />
Plume Control <strong>and</strong> Energy Benefits<br />
Decision<br />
maker<br />
Platform for predict<strong>in</strong>g<br />
plume occurr<strong>in</strong>g possibility<br />
Cool<strong>in</strong>g<br />
Water<br />
Temp Setpo<strong>in</strong>t<br />
Operat<strong>in</strong>g Condition Power Consumption<br />
Cool<strong>in</strong>g<br />
Tower<br />
Number<br />
Cool<strong>in</strong>g<br />
Tower<br />
Freq<br />
Normal operation when there is<br />
no predicted plume occurs<br />
At first-level warn<strong>in</strong>g, <strong>in</strong>crease airflow rate<br />
by 20% when plume potential is marg<strong>in</strong>al<br />
At second-level warn<strong>in</strong>g, <strong>in</strong>crease airflow<br />
by 40% when plume potential is high<br />
Start heat<strong>in</strong>g us<strong>in</strong>g heat pumps when<br />
visual plume is observed<br />
Chiller<br />
Power<br />
Cool<strong>in</strong>g<br />
Tower<br />
Power<br />
Additional energy consumption for<br />
plume control could be reduced from<br />
Total<br />
Power<br />
Difference<br />
°C - Hz kW kW kW kW %<br />
Reference<br />
First-level warn<strong>in</strong>g<br />
22.7 3 26.51 856.2 59.1 32.8% to 5.5% or 1.5% at low Load<br />
21.3 3 30.74 836.2 93.0<br />
915.35<br />
929.2<br />
--<br />
14.0<br />
--<br />
1.5<br />
Second-level warm<strong>in</strong>g 20.1 3 35.52 819.9 145.9 965.8 50.6 5.5<br />
Us<strong>in</strong>g heat pumps 22.7 3CT+1HP 26.51 856.2 59.1 1215.2 300 32.8<br />
Chiller Plant Sequenc<strong>in</strong>g Control<br />
<strong>of</strong> Enhanced Robustness<br />
Us<strong>in</strong>g Data Fusion Technique
Types <strong>of</strong> chiller sequenc<strong>in</strong>g control<br />
� Return chilled water temperature based sequenc<strong>in</strong>g<br />
control<br />
Background (1)<br />
Chiller sequenc<strong>in</strong>g control<br />
� Aims to determ<strong>in</strong>e how many <strong>and</strong> which chillers are to be<br />
put <strong>in</strong>to operation accord<strong>in</strong>g to build<strong>in</strong>g cool<strong>in</strong>g load<br />
� Plays a significant role for build<strong>in</strong>g energy efficiency<br />
� Bypass flow based sequenc<strong>in</strong>g control<br />
� Direct power based sequenc<strong>in</strong>g control<br />
� Total cool<strong>in</strong>g load based sequenc<strong>in</strong>g control<br />
Background (2)<br />
Total cool<strong>in</strong>g load based chiller sequenc<strong>in</strong>g control<br />
� Build<strong>in</strong>g cool<strong>in</strong>g load measurement<br />
� Maximum cool<strong>in</strong>g capacity<br />
� Optimal number <strong>of</strong> chillers to be put <strong>in</strong>to operation<br />
N c = φ(Q cl, Q max)<br />
Problems<br />
� Build<strong>in</strong>g cool<strong>in</strong>g load cannot be measured accurately<br />
� Chiller maximum cool<strong>in</strong>g capacity vary with the<br />
operat<strong>in</strong>g conditions
Fused Cool<strong>in</strong>g Load Measurement<br />
Cool<strong>in</strong>g load measurement<br />
� Direct measurement <strong>of</strong> build<strong>in</strong>g cool<strong>in</strong>g load<br />
Q dm = c pwρ wM w(T w,rtn-T w,sup)<br />
where c pw is the water specific thermal capacity; ρ w is the<br />
water density; M w is water flow rate; T w,rtn,T w,sup are<br />
chilled water return/supply temp.<br />
� Indirect measurement <strong>of</strong> build<strong>in</strong>g cool<strong>in</strong>g load<br />
Q im = f(P com,T cd,T ev)<br />
where f is the chiller <strong>in</strong>verse model; P com is chiller power<br />
consumption; T cd,T ev are chiller condens<strong>in</strong>g/evaporat<strong>in</strong>g<br />
temperature<br />
Robust build<strong>in</strong>g cool<strong>in</strong>g load measurement technique<br />
� Data fusion to merge “Direct measurement” <strong>and</strong><br />
“Indirect measurement” improv<strong>in</strong>g the accuracy <strong>and</strong><br />
reliability <strong>of</strong> build<strong>in</strong>g cool<strong>in</strong>g load measurement<br />
T sup<br />
Advanced s<strong>of</strong>t measurement system<br />
Q dm<br />
Direct<br />
measurement<br />
T rtn M w<br />
Chiller<br />
Model 1<br />
Chiller<br />
Model 1<br />
Q im,1<br />
P com,1 T ev,1 ,T cd,1<br />
Data Fusion<br />
Eng<strong>in</strong>e<br />
+<br />
…<br />
Q im,n<br />
P com,n,T ev,n,T cd,n<br />
Central Chill<strong>in</strong>g Plant<br />
Chiller<br />
Model n<br />
Chiller<br />
Model n<br />
Q f<br />
γ f
Robust Chiller Sequenc<strong>in</strong>g Control Build<strong>in</strong>g Cool<strong>in</strong>g Load<br />
Measurement Technique<br />
Direct<br />
measurement<br />
Parameters<br />
sett<strong>in</strong>g<br />
Periodical<br />
analysis<br />
Central chill<strong>in</strong>g<br />
plant<br />
Indirect<br />
Measurement<br />
Data Fusion<br />
Eng<strong>in</strong>e<br />
Robust Cool<strong>in</strong>g Load<br />
Measurement<br />
Build<strong>in</strong>g Automation<br />
System<br />
Alarm<strong>in</strong>g<br />
subsystem<br />
Chiller sequenc<strong>in</strong>g<br />
control<br />
Temperature<br />
set-po<strong>in</strong>t<br />
Database<br />
Optimal Control <strong>of</strong> Variable Speed Pumps<br />
� Speed control <strong>of</strong> pumps distribut<strong>in</strong>g water to<br />
To term<strong>in</strong>al<br />
units<br />
heat exchangers<br />
� Orig<strong>in</strong>al implemented<br />
strategy --- differential<br />
pressure controller by<br />
resort<strong>in</strong>g to the<br />
modulat<strong>in</strong>g valve<br />
Secondary side <strong>of</strong> HX Primary side <strong>of</strong> HX<br />
From term<strong>in</strong>al units<br />
Temperature<br />
set-po<strong>in</strong>t<br />
TM T<br />
Temperature<br />
controller<br />
HX<br />
HX<br />
Water flow<br />
set-po<strong>in</strong>t<br />
TM<br />
Water flow<br />
controller<br />
From cool<strong>in</strong>g<br />
source<br />
To cool<strong>in</strong>g<br />
source<br />
Temperature Temperature<br />
set-po<strong>in</strong>t controller<br />
Modulat<strong>in</strong>g<br />
valves<br />
Secondary side <strong>of</strong> HX Primary side <strong>of</strong> HX<br />
From term<strong>in</strong>al units<br />
To term<strong>in</strong>al<br />
units<br />
T<br />
T<br />
Temperature<br />
controller<br />
HX<br />
HX<br />
M<br />
M<br />
Pressure<br />
differential set-po<strong>in</strong>t<br />
ΔP<br />
Differential<br />
pressure<br />
controller<br />
From cool<strong>in</strong>g<br />
source<br />
To cool<strong>in</strong>g<br />
source<br />
� Proposed strategy<br />
--- cascade controller<br />
without us<strong>in</strong>g any<br />
modulat<strong>in</strong>g valve
� Performance test <strong>and</strong> evaluation<br />
� Site practically test showed that the proposed<br />
strategy can provide stable <strong>and</strong> reliable control.<br />
Compared to orig<strong>in</strong>al implemented strategy, about<br />
22.0% sav<strong>in</strong>gs for pumps before heat exchangers <strong>in</strong><br />
Zone 1 was achieved.<br />
� Due to the low load <strong>of</strong> Zone 1 <strong>in</strong> <strong>ICC</strong> at current<br />
stage, a simulation test <strong>of</strong> annual energy sav<strong>in</strong>gs by<br />
us<strong>in</strong>g PolyU strategy is performed.<br />
Pumps<br />
Number<br />
(st<strong>and</strong>by)<br />
Energy consumption (kWh)<br />
Orig<strong>in</strong>al<br />
strategy<br />
(kWh)<br />
Energy sav<strong>in</strong>g <strong>of</strong> primary pumps before<br />
heat exchanges due to the use <strong>of</strong><br />
PolyU strategy is about 250000 kWh.<br />
Alternative<br />
Strategy<br />
(kWh)<br />
Sav<strong>in</strong>g<br />
(kWh)<br />
Primary pumps <strong>in</strong> Zone 1 1(1) 528,008 456,132 71,876<br />
Primary pumps for Zones 3&4 3(1) 921,235 795,830 125,405<br />
Primary pumps <strong>in</strong> Zone 4 2(1) 401,008 346,420 54,588<br />
Total sav<strong>in</strong>g <strong>of</strong> the primary pumps 251,869<br />
Optimal Outdoor air Ventilation Control<br />
Static pressure<br />
set po<strong>in</strong>t<br />
Static pressure<br />
Static pressure<br />
controller<br />
P<br />
<strong>The</strong> 7 th floor<br />
………….<br />
<strong>The</strong> 1 st floor<br />
Outdoor air<br />
controller<br />
Set po<strong>in</strong>t<br />
Adaptive DCV<br />
strategy<br />
Model-based<br />
outdoor air flow rate<br />
Control strategy
W<br />
Energy-based outdoor air flow rate set-po<strong>in</strong>t<br />
resett<strong>in</strong>g scheme<br />
cost<br />
= W<br />
fan<br />
Q<br />
+<br />
COP<br />
outdoor<br />
Iterative<br />
algorithm<br />
= C<br />
k<br />
v<br />
⋅ M<br />
k<br />
out,<br />
set<br />
Outdoor Air Optimal Scheme<br />
+<br />
Least Square Algorithm<br />
Set po<strong>in</strong>t trails<br />
Cost function<br />
estimator<br />
Optimal set po<strong>in</strong>t Range <strong>of</strong> set po<strong>in</strong>t<br />
Supervisor Constra<strong>in</strong>s<br />
Parameter estimators<br />
Parameter identification <strong>of</strong> the fan model<br />
Real process <strong>of</strong> the multi-zone<br />
air condition<strong>in</strong>g system<br />
M<br />
Model-based<br />
predictor<br />
k<br />
out,<br />
set<br />
⋅(<br />
H<br />
k<br />
out<br />
COP<br />
− H<br />
� Site Implementation <strong>and</strong> Validation <strong>of</strong> Optimal<br />
Ventilation Strategy for Fresh Air Control<br />
� CO2-based occupancy detection<br />
Number <strong>of</strong> occupancy<br />
� Site count<strong>in</strong>g the number <strong>of</strong><br />
occupancy <strong>in</strong> the typical floor<br />
100<br />
90<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
Dem<strong>and</strong>-controlled Ventilation control<br />
Counted<br />
Predicted<br />
0<br />
8:30 9:30 10:30 11:30 12:30 13:30 14:30 15:30 16:30 17:30 18:30<br />
Time (hour)<br />
k<br />
rtn<br />
� Comparison<br />
between counted<br />
<strong>and</strong> predicted<br />
occupancies<br />
)
� Practically test <strong>and</strong> validation <strong>of</strong> the ventilation<br />
control strategy<br />
Tests aimed at validat<strong>in</strong>g the actual operational performance <strong>of</strong> the<br />
ventilation control strategy <strong>and</strong> also for verify<strong>in</strong>g whether the control<br />
sett<strong>in</strong>gs provided by PolyU strategy can be properly sent to the ATC<br />
system <strong>and</strong> further be used <strong>in</strong> practical control.<br />
AHU1<br />
AHU2<br />
Study cases<br />
Control strategy<br />
Fixed flow PolyU Fixed flow PolyU<br />
About 662,000 Primary fan energy kWh consumption energy sav<strong>in</strong>gs can be<br />
612.29 607.99 794.60<br />
761.92<br />
Site test case<br />
(kWh)<br />
(PolyU strategy achieved only applied to by Primary us<strong>in</strong>g fan energy sav<strong>in</strong>g PolyU (%) - ventilation +0.70 - control +4.11<br />
typical floor)<br />
(Nov., 2009)<br />
Energy saved due to fresh air<br />
7.90 3.04 4.96<br />
2.81<br />
strategy for all cool<strong>in</strong>g floors (kWh) per year <strong>in</strong> Zone 2!<br />
Estimation case<br />
(PolyU strategy applied to all<br />
floors <strong>in</strong> Zone 2)<br />
Summer case<br />
(PolyU strategy applied to all<br />
floors <strong>in</strong> Zone 2)<br />
Primary fan energy consumption<br />
(kWh)<br />
Primary fan energy sav<strong>in</strong>g (%)<br />
Primary fan energy consumption<br />
(kWh)<br />
Fresh air cool<strong>in</strong>g energy<br />
consumption (kWh)<br />
Total energy consumption (kWh)<br />
Total energy sav<strong>in</strong>g (%)<br />
612.29<br />
-<br />
612.29<br />
4754.4<br />
5366.7<br />
-<br />
288.3<br />
+52.9<br />
288.3<br />
1915.2<br />
2203.5<br />
+58.9<br />
794.60<br />
-<br />
794.60<br />
2985.6<br />
3780.2<br />
Site Implementation <strong>of</strong> <strong>The</strong><br />
Control Strategies<br />
-<br />
324.5<br />
+59.2<br />
324.5<br />
1725.6<br />
2050.1<br />
+45.8
Implementation Strategy <strong>of</strong> Optimal Control <strong>and</strong> Diagnosis<br />
Tools <strong>in</strong> <strong>ICC</strong><br />
BACnet SDK<br />
Control<br />
Parameters<br />
Optimizer<br />
Control Sett<strong>in</strong>g<br />
from PolyU<br />
Diagnosis<br />
Control Sett<strong>in</strong>g<br />
from ATC<br />
Decision Supervisor<br />
ATC<br />
VAV Box<br />
Overall KVA, etc.<br />
Manual<br />
Control<br />
Chiller Plant Control Optimizer<br />
<strong>and</strong> Diagnosis<br />
LAN<br />
Supply air control<br />
optimizer<br />
IBmanager<br />
AHU PAU<br />
Build<strong>in</strong>g<br />
Management<br />
System<br />
Fresh air control<br />
optimizer<br />
Fresh air<br />
term<strong>in</strong>al<br />
Intelligent build<strong>in</strong>g management system<br />
-- based on IBmanager<br />
� IBmanager is an open <strong>and</strong> <strong>in</strong>tegrated management platform. It<br />
employs st<strong>and</strong>ard middleware <strong>and</strong> web-service technologies to<br />
support the <strong>in</strong>tegration <strong>and</strong> <strong>in</strong>teroperation among distributed BASs.
Summary <strong>of</strong> Energy Benefits<br />
• 1,000,000 kWh energy consumption is saved due to the<br />
modification on the secondary water loops <strong>of</strong> Zone 3 & 4;<br />
• 2,360,000 kWh , (about 5.1% <strong>of</strong> annual energy<br />
consumption <strong>of</strong> chillers <strong>and</strong> cool<strong>in</strong>g towers) <strong>of</strong> the cool<strong>in</strong>g<br />
system can be sav<strong>in</strong>g due to the change from s<strong>in</strong>gle speed<br />
to variable speed us<strong>in</strong>g VFD.<br />
• 607,000 kWh , (about 2.8% <strong>of</strong> annual energy consumption<br />
<strong>of</strong> chillers <strong>and</strong> cool<strong>in</strong>g towers) <strong>of</strong> the cool<strong>in</strong>g system will<br />
be wasted when the lowest frequency is limited at 37 Hz.<br />
• 3, 500,000 kWh (about 7%) <strong>of</strong> the total energy<br />
consumption <strong>of</strong> HVAC system) can be saved us<strong>in</strong>g PoyU<br />
control strategies based on the orig<strong>in</strong>al design;<br />
Summary <strong>of</strong> Energy Benefits<br />
• 1,000,000 Sav<strong>in</strong>g Sav<strong>in</strong>g Sav<strong>in</strong>g Sav<strong>in</strong>g by by by by kWh Commission<strong>in</strong>g Commission<strong>in</strong>g<br />
Commission<strong>in</strong>g<br />
Commission<strong>in</strong>g energy consumption (Improv<strong>in</strong>g (Improv<strong>in</strong>g (Improv<strong>in</strong>g (Improv<strong>in</strong>g is saved the the the the due system system system system to the<br />
modification on the secondary water loops <strong>of</strong> Zone 3 & 4;<br />
configuration configuration configuration configuration <strong>and</strong> <strong>and</strong> <strong>and</strong> <strong>and</strong> selection selection selection selection <strong>–</strong> compared with the<br />
• 2,360,000 kWh , (about 5.1% <strong>of</strong> annual energy<br />
orig<strong>in</strong>al design.<br />
consumption <strong>of</strong> chillers <strong>and</strong> cool<strong>in</strong>g towers) <strong>of</strong> the cool<strong>in</strong>g<br />
system can be sav<strong>in</strong>g due to the change from s<strong>in</strong>gle speed<br />
to variable speed us<strong>in</strong>g VFD.<br />
• 607,000 kWh , (about 2.8% <strong>of</strong> annual energy consumption<br />
<strong>of</strong> chillers <strong>and</strong> cool<strong>in</strong>g towers) <strong>of</strong> the cool<strong>in</strong>g system will<br />
be wasted when the lowest frequency is limited at 37 Hz.<br />
• 3, Sav<strong>in</strong>g Sav<strong>in</strong>g Sav<strong>in</strong>g 500,000 by by by kWh Control Control Control (about Optimization<br />
Optimization<br />
Optimization 7%) <strong>of</strong> the total energy<br />
consumption <strong>of</strong> HVAC system) can be saved us<strong>in</strong>g PoyU<br />
case<br />
control<br />
when<br />
strategies<br />
the HVAC<br />
based<br />
system<br />
on the orig<strong>in</strong>al<br />
operates<br />
design;<br />
correctly<br />
Sav<strong>in</strong>g by Control Optimization <strong>–</strong> compared with the<br />
accord<strong>in</strong>g to the orig<strong>in</strong>al design <strong>in</strong>tend.
Summary <strong>of</strong> Energy Benefits<br />
• 1,000,000 Sav<strong>in</strong>g Sav<strong>in</strong>g Sav<strong>in</strong>g Sav<strong>in</strong>g by by by by kWh Commission<strong>in</strong>g Commission<strong>in</strong>g<br />
Commission<strong>in</strong>g<br />
Commission<strong>in</strong>g energy consumption (Improv<strong>in</strong>g (Improv<strong>in</strong>g (Improv<strong>in</strong>g (Improv<strong>in</strong>g is saved the the the the due system system system system to the<br />
modification on the secondary water loops <strong>of</strong> Zone 3 & 4;<br />
configuration configuration configuration configuration <strong>and</strong> <strong>and</strong> <strong>and</strong> <strong>and</strong> selection selection selection selection <strong>–</strong> compared with the<br />
• 2,360,000 kWh , (about 5.1% <strong>of</strong> annual energy<br />
orig<strong>in</strong>al design.<br />
consumption <strong>of</strong> chillers <strong>and</strong> cool<strong>in</strong>g towers) <strong>of</strong> the cool<strong>in</strong>g<br />
system can be sav<strong>in</strong>g due to the change from s<strong>in</strong>gle speed<br />
to variable speed us<strong>in</strong>g VFD.<br />
<strong>The</strong> annual total energy<br />
• 607,000 kWh , (about 2.8% <strong>of</strong> annual energy consumption<br />
<strong>of</strong> chillers sav<strong>in</strong>g <strong>and</strong> cool<strong>in</strong>g is towers) about <strong>of</strong> the 7.0M cool<strong>in</strong>g kWh system will !<br />
be wasted when the lowest frequency is limited at 37 Hz.<br />
• 3, Sav<strong>in</strong>g Sav<strong>in</strong>g Sav<strong>in</strong>g 500,000 by by by kWh Control Control Control (about Optimization<br />
Optimization<br />
Optimization 7%) <strong>of</strong> the total energy<br />
consumption <strong>of</strong> HVAC system) can be saved us<strong>in</strong>g PoyU<br />
case<br />
control<br />
when<br />
strategies<br />
the HVAC<br />
based<br />
system<br />
on the orig<strong>in</strong>al<br />
operates<br />
design;<br />
correctly<br />
Sav<strong>in</strong>g by Control Optimization <strong>–</strong> compared with the<br />
accord<strong>in</strong>g to the orig<strong>in</strong>al design <strong>in</strong>tend.<br />
Summary <strong>of</strong> Experience <strong>in</strong> <strong>ICC</strong><br />
• Significant energy sav<strong>in</strong>g can be achieved by<br />
allow<strong>in</strong>g the system as good as the design <strong>in</strong>tention<br />
by identify<strong>in</strong>g <strong>and</strong> correct<strong>in</strong>g the errors at different<br />
stages;<br />
• Significant energy sav<strong>in</strong>g can be achieved by<br />
mak<strong>in</strong>g the system better than the design <strong>in</strong>tention<br />
by enhanc<strong>in</strong>g <strong>and</strong> optimiz<strong>in</strong>g the systems at different<br />
stages;<br />
• <strong>The</strong> <strong>in</strong>volvement <strong>of</strong> a pr<strong>of</strong>essional energy consultant<br />
(commission<strong>in</strong>g agent) does not <strong>in</strong>troduce troubles<br />
to the build<strong>in</strong>g construction project, but <strong>in</strong>stead it<br />
facilitates different parties <strong>in</strong>volved to support each<br />
other to do their jobs smoothly <strong>and</strong> correctly.