Average temperature measurement with MPT / RTD<br />
___________________________________________________________________________<br />
4.2.2 Additional settings for and 877 FDI<br />
Item Name Description<br />
W2= Protection level 2 Enter protection level 2<br />
OB= Option board *) Three ASCII characters. This item informs the XPU what option<br />
board is installed. That can be:<br />
MPU : for HCU/ICU option board in MPU emulation mode<br />
HPU : for HCU/ICU option board in HPU emulation mode<br />
EG= Enable temperature One ASCII character; either ‘D’ or ‘E’. With this item can be<br />
transmission *)<br />
selected if the 877 FDI shall answer on a temperature request<br />
(C-record), addressed to the connected level gauge.<br />
E : transmission of temperature record enabled<br />
D : transmission of temperature record disabled<br />
Note:<br />
When item EG is set to ‘E’, make sure the related level gauge<br />
has no temperature option installed.<br />
TF= Temperature source One ASCII character; either ‘I’ or ‘E’. this item selects if there is<br />
Selection<br />
a temperature measurement inside the indicator (internal) or to<br />
be fetched from the Enraf field bus (external).<br />
E : Internal<br />
D : External<br />
EX Exit Exit protection level 2<br />
*) This item is not implemented in the XPU-2.<br />
4.2.3 Temperature verification MPT (Multiple Pt100 spots) probes<br />
After the settings described in section 4.2.1 and, if applicable in section 4.2.2, are entered the temperature<br />
measurement is operational.<br />
The following checks can be made to verify if the settings are made correct and the product temperature reading<br />
is correct.<br />
• Read item AP (Average Product temperature):<br />
This data item is preceded by four status characters. The first status character is a hexa-decimal number,<br />
indicating the highest selected element for average product temperature calculation. This can be judged,<br />
on basis of the product level, and with the items U0 – UF (calculated spot positions), item MO<br />
(temperature element offset), item MP (product immersion depth) and item MI (switch hysteresis).<br />
Refer to figure 4.2:<br />
A spot element will be used in the average product temperature calculation if its position is below the<br />
actual level minus the product immersion depth.<br />
A spot element won’t be used in the average product temperature calculation if it is above the actual level<br />
minus the product immersion depth plus the switch hysteresis.<br />
• Verify the average product temperature by manual measurement:<br />
Refer to Appendix C for the procedure to verify the average product temperature reading by using a<br />
portable electronic thermometer.<br />
Instruction manual VITO Page 31