Installation and connection 2 Connection diagram Special precautions b Never connect or disconnect a connector while the device is energised. b Check voltages before connecting. b Always energise the RM12T multiplexer before the Vigirex RMH. Protection of the device b The Vigirex RMH is supplied by 220/240 V AC 50/60 Hz power. b Recommended protection for wiring of the Vigirex RMH: v C60N phase + neutral or 2-pole circuit breaker or DPN phase + neutral circuit breaker (1 A, curve C or D) v STI isolatable fuse carrier (with 1 A fuse). Types of toroids to be used Two types of toroids may be connected: types A and OA. The toroid characteristics are indicated in the Vigirex catalogue. Compatibility with E toroids in existing installations: b TE (Ø 30 mm) ; PE (Ø 50 mm) : total compatibility b IE (Ø 80 mm) ; ME (Ø 120 mm) ; SE (Ø 200 mm) ATTENTION The thresholds should never be set to less than 300mA for these threetoroids, IE, ME and SE. b Maximum cable lengths between toroid and RM12T multiplexer 10 m. Connecting the toroids: The toroids (12 maximum) are connected to the RMH via a RM12T selector. Requirements concerning the cable connecting the RMH to the RM12T: b maximum length of 10 metres. four wires (two twisted pairs). b The Vigirex RMH automatically recognises any new toroid added when it is energised. Connection of the toroids to the RM12T selector: (see diagram opposite) Toroid no. 1 2 3 4 5 6 7 8 9 10 11 12 RM12T terminals 1 3 4 6 7 9 10 12 15 17 18 20 2 2 5 5 8 8 11 11 16 16 19 19 5100512174-03 Released for Manufacturing Printed on 2013/01/09 43/69

Installation and connection Cable cross-section: b α cables: 1.5 mm 2 to 2.5 mm 2 b β cables: twisted 0.75 mm 2 to 2.5 mm 2. Colour code for internal bus connection: b 24 V Red b 0 V Black b SIGNAL - White b SIGNAL + Blue Internal bus cable: b length Cat. No. v 20 meters 50779 v 100 meters. 50780 DB125383 Internal bus β cables RMH 220-240Va.c. Bus 24V 0V B α cables alarm pre-al. 32 34 31 41 44 (1) (2) 32 34 31 41 44 A 21 22 RM12T 24 23 21 22 no wire 24 23 21 22 24 23 D (3) 11 14 A1 A2 C 11 on 14 A1 A2 α cables Relay protection Power supply β cables 1 2 3 4 5 6 7 8 9 10 11 12 13 5100512174-03 RM12T multiplexer 14 15 16 17 18 19 20 21 22 23 24 25 26 β cables α cables RMH-CA2 RMH-CA1 RMH-D24 RMH-D23 RMH-D22 RMH-D21 (1) Alarm contact (2) Pre-alarm contact (3) Voltage presence contact Released for Manufacturing Printed on 2013/01/09 Measurement toroid 12 maxi. 44/69

Program_-Guide_2015-03-03
Issue 03
03/2008
ISSUE #03
03 noncompliance
03-DK_BIS_NEWS_Edition_1_Mar_2015_web_version
NEWS 03