Operation 3 Resetting

Operation 3 Resetting the maximum current reading b Press the key to select a given channel. DB124934 b Press the current reading. b key to select display of the maximum Press the Test Reset key, the display flashes "0 00". pre-al. alarm 1 2 3 4 5 6 7 8 9 10 11 12 I %(I al.) max mA A t l I pre-al. t pre-al. (s) I alarm "on" = trip t alarm (s) "off" = no trip Modif Test Reset 5100512174-03 Released for Manufacturing Printed on 2013/01/09 51/69

Exploitation b Press the key to confirm. The new maximum current is displayed on the screen. DB124935 Please note: until the key has been pressed, the reset procedure can be cancelled by pressing the key. pre-al. alarm 1 2 3 4 5 6 7 8 9 10 11 12 Note: while resetting the maximum current, it is not possible to: b reset an alarm condition b run a test. t l I %(I al.) max I pre-al. t pre-al. (s) I alarm "on" = trip t alarm (s) "off" = no trip Test Reset Modif mA A mA A 5100512174-03 Released for Manufacturing Printed on 2013/01/09 52/69

Issue 03
ISSUE #03
03/2008