Views
7 months ago

5100512174-03

Operation 3 b press the

Operation 3 b press the key to change the value of the flashing field: v select (mA) or (A) if the field represents the units. The displayed value is converted automatically to the requested units v increment the flashing digit from 0 to 9 if the display field is a digit. DB125385 pre-al. alarm or mA A Please note: b if the selected current units are A, the value is incremented by steps of 100 mA b if the selected current units are mA,the value is incremented by steps of 1 mA. t l 1 2 3 4 5 6 7 8 9 10 11 12 I %(I al.) max I pre-al. t pre-al. (s) I alarm "on" = trip t alarm (s) "off" = no trip Modif mA A mA A Test Reset + mA A 5100512174-03 Released for Manufacturing Printed on 2013/01/09 57/69

Operation b press the key to move to the next field: v there are 4 fields (measurement units and the 3 digits of the display) for threshold settings v there are 3 fields (3 digits of the display) for trip delay settings.. DB125386 pre-al. alarm 1 2 3 4 5 6 7 8 9 10 11 12 mA A t l I %(I al.) max I pre-al. t pre-al. (s) I alarm "on" = trip t alarm (s) "off" = no trip Modif mA A or Test Reset mA A 5100512174-03 Released for Manufacturing Printed on 2013/01/09 58/69

feineadressen_berlinpotsdam_2015-03
Minimalistic 03
NEWS 03
benchmark_26-03-2014_insurance_banking_construction_government
03-schneider-electric
roadshow_am_ntct_assuring_user_experienct_2012-03 - NetScout
03-22-17_AR_16