04.01.2013 Views

Evolis HP circuit breaker

Evolis HP circuit breaker

Evolis HP circuit breaker

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Technical data sheet<br />

<strong>Evolis</strong> <strong>HP</strong> <strong>circuit</strong> <strong>breaker</strong> is used<br />

to protect and control MV public<br />

or industrial distribution network.<br />

<strong>Evolis</strong> <strong>HP</strong> is an indoor switchgear<br />

b Rated voltage up to 15 kV<br />

b Rated short-<strong>circuit</strong> breaking current 50 kA<br />

b Rated normal current up to 3150 A.<br />

<strong>Evolis</strong> <strong>HP</strong> is available in withdrawable<br />

version with MC cassette.<br />

PE56545<br />

Medium Voltage Distribution<br />

<strong>Evolis</strong> <strong>HP</strong> <strong>circuit</strong> <strong>breaker</strong><br />

Vacuum breaking<br />

Conformity with standards<br />

b IEC 62271-1: common specifications for high voltage switchgear<br />

and controlgear standards<br />

b IEC 62271-100: high voltage alternating current <strong>circuit</strong> <strong>breaker</strong><br />

b IEC 62271-200: AC metal-enclosed switchgear and controlgear for rated voltages<br />

above 1 kV and up to and including 52 kV.<br />

Certification<br />

b By independent laboratories in accordance with ISO/IEC 17025<br />

and EN 45011 standards<br />

b Our factories implement a quality system certified to ISO 9001: 2000<br />

and ISO 14001 standards by IQNET.<br />

Installation<br />

b Withdrawable with MC cassette<br />

b Designed for retrofit.<br />

Operation<br />

b The operating mechanism is activated by a spring.


Electrical characteristics according to IEC 62271-100<br />

Phase to phase 240<br />

Basic device<br />

Withdrawable with MC3 cassette<br />

Dimensions (mm) W 886<br />

H 980<br />

D 902<br />

Weight (kg) 338<br />

DE57194EN<br />

A full range of accessories and auxiliaries<br />

factory-mounted or delivered separately<br />

b Electric motor (M)<br />

b Undervoltage release (YM)<br />

b Shunt opening release (YO)<br />

b Low energy release (MITOP)<br />

b Shunt closing release (YF)<br />

b Auxiliary contacts<br />

b Operations counter.<br />

Cassette type MC3<br />

Rated voltage<br />

Insulation level<br />

Ur kV 50/60 Hz 7.2 12 15<br />

- power frequency withstand Ud kV 50 Hz 1 min 20 28 38<br />

- lightning impulse withstand Up kV peak 60 75 95<br />

Rated current Ir A 1250 – – – – – – – b – – – b<br />

2500 – – – b – – – b – – – b<br />

3150 b b b b b b b b b b b b<br />

Short <strong>circuit</strong> current Isc kA 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50<br />

Short time withstand current Ik/tk kA/3 s 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50<br />

Short-<strong>circuit</strong> making current Ip kA peak 50 Hz 63 79 100 125 63 79 100 125 (*) 63 79 100 125 (*)<br />

60 Hz 65 82 104 130 65 82 104 130 (*) 65 82 104 130 (*)<br />

Common characteristics according to IEC 62271-100<br />

Rated switching sequence O-3 min-CO-3 min-CO b<br />

O-0.3 s-CO-3 min-CO b<br />

O-0.3 s-CO-15 s-CO b<br />

Operating times Opening ms < 52<br />

Breaking ms < 73<br />

Closing ms < 61<br />

Service temperature T °C – 5 to + 40<br />

Mechanical endurance Class M2<br />

Number of operations 10 000<br />

Electrical endurance Class E2<br />

Number of switching operations 25 kA 100<br />

at full Isc value<br />

31.5 kA 50<br />

40 kA 30<br />

50 kA 30<br />

Capacitive current breaking capacity Class C1<br />

Average relative humidity Over 24 h < 95%<br />

Over 1 month < 90%<br />

Schneider Electric Industries SAS<br />

35, rue Joseph Monier<br />

CS 30323<br />

F - 92506 Rueil Malmaison Cedex<br />

RCS Nanterre 954 503 439<br />

Capital social 896 313 776 €<br />

www.schneider-electric.com<br />

Dimensions and weights<br />

240 240<br />

W<br />

321 611 100<br />

D<br />

AMTED307009EN 03-2010<br />

H<br />

805<br />

370<br />

300<br />

b Available<br />

– Not available<br />

(*) 150 kA available on request.<br />

As standards, specifications and designs change from time to time, please ask for confirmation<br />

of the information given in this publication.<br />

This document has been printed<br />

on ecological paper<br />

Publishing: Schneider Electric Industries SAS<br />

Design: Schneider Electric Industries SAS<br />

Printing: Imprimerie du Pont de Claix/JPF - Made in France<br />

550<br />

285<br />

ART.830621 © Schneider Electric Industries SAS - All rights reserved

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!