6.8 Auto-stop in case of lower-limit frequency continuous<br />

operation<br />

6.8.1 Auto-stop in case of lower-limit frequency continuous<br />

operation<br />

: Auto-stop in case of lower-limit frequency continuous operation<br />

: Hysteresis for LL stop operation<br />

: Restart deviation for LL stop operation<br />

: Restart feedback for LL stop operation<br />

• Function<br />

If operation is carried out continuously at a frequency command below the lower-limit frequency () for<br />

the period of time set with , the inverter will automatically slow down the motor to a stop. At that<br />

time, “” is displayed (alternately) on the operation panel.<br />

This function will be canceled if a frequency command above the lower-limit frequency ()<br />

+Hz.<br />

PID control selected-> The stop of this function will be canceled by deviation and feedback when<br />

f392 and f393 is setting.<br />

[Parameter setting]<br />

Title Function Adjustment range Default setting<br />

<br />

Auto-stop in case of lower-limit<br />

frequency continuous operation time<br />

0.0: Disabled<br />

0.1-600.0 (s)<br />

f391 Hysteresis for LL stop operation 0.0-fh 0.2<br />

f392 Restart deviation for LL stop operation 0.0-fh 0.0<br />

f393 Restart feedback for LL stop operation 0.0-fh 0.0<br />

0.0