2) Types of PID control interfaces<br />
F-45<br />
E6581381<br />
Process quantity input data (frequency) and feedback input data can be combined as follows for the PID<br />
control of the <strong>VF</strong>-<strong>FS1</strong>:<br />
Process quantity input data (frequency setting) Feedback input data<br />
Setting method<br />
Frequency setting mode selection<br />
/ <br />
PID control<br />
<br />
(1) External analog setting<br />
VIA (DC: 4-20mA / 0-10V)<br />
(2) External analog setting<br />
VIB (DC: 0-10V)<br />
<br />
<br />
: External analog input<br />
VIA (DC:4-20mA / DC:0-10V)<br />
: External analog input<br />
(3) Panel input setting Internal<br />
preset-speed setting<br />
<br />
VIB (DC:0-10V)<br />
(4) RS485 communication <br />
(5) UP/DOWN from external<br />
contact<br />
<br />
(6) Internal preset-speed setting - (=0)<br />
Note 1: About the setting of and : Do not select the same terminal that is used feedback<br />
terminal (VIA or VIB).<br />
Note 2: When using VIA terminal, set or respectively to 52 or 53 to put out signals to RY-RC<br />
or FLA-FLB-FLC.<br />
When using VIB terminal, set or respectively to 60 or 61 to put out signals to RY-RC<br />
or FLA-FLB-FLC.<br />
You can also specify a frequency agreement detection range ().<br />
⇒ For more information, see section 6.3.5.<br />
3) Setting PID control<br />
Set "" or "2" in the extended parameter (PID control)<br />
(1) Set parameters (acceleration time), and (deceleration time) to the system fitting values.<br />
(2) To limit the output frequency, set parameters (upper limit frequency) and (lower limit<br />
frequency). If process quantities are set from the operation panel, however, the process quantity setting<br />
range will be limited by the settings of and .<br />
(3) Input terminal function “PID control prohibited” (function No.14) can changing PID control or open-loop<br />
control. Also Input terminal function “PID control integral value clear” (function No.65) can use.<br />
(4) By the set the f380 or Input terminal function “PID forward/reverse switching” (function No.72) , PID<br />
control is reverse. When a reverse-characteristic is selected at the same time with the parameter and<br />
the terminal, it becomes a forward characteristic.<br />
6