2) Types of PID control interfaces<br />

F-45<br />

E6581381<br />

Process quantity input data (frequency) and feedback input data can be combined as follows for the PID<br />

control of the <strong>VF</strong>-<strong>FS1</strong>:<br />

Process quantity input data (frequency setting) Feedback input data<br />

Setting method<br />

Frequency setting mode selection<br />

/ <br />

PID control<br />

<br />

(1) External analog setting<br />

VIA (DC: 4-20mA / 0-10V)<br />

(2) External analog setting<br />

VIB (DC: 0-10V)<br />

<br />

<br />

: External analog input<br />

VIA (DC:4-20mA / DC:0-10V)<br />

: External analog input<br />

(3) Panel input setting Internal<br />

preset-speed setting<br />

<br />

VIB (DC:0-10V)<br />

(4) RS485 communication <br />

(5) UP/DOWN from external<br />

contact<br />

<br />

(6) Internal preset-speed setting - (=0)<br />

Note 1: About the setting of and : Do not select the same terminal that is used feedback<br />

terminal (VIA or VIB).<br />

Note 2: When using VIA terminal, set or respectively to 52 or 53 to put out signals to RY-RC<br />

or FLA-FLB-FLC.<br />

When using VIB terminal, set or respectively to 60 or 61 to put out signals to RY-RC<br />

or FLA-FLB-FLC.<br />

You can also specify a frequency agreement detection range ().<br />

⇒ For more information, see section 6.3.5.<br />

3) Setting PID control<br />

Set "" or "2" in the extended parameter (PID control)<br />

(1) Set parameters (acceleration time), and (deceleration time) to the system fitting values.<br />

(2) To limit the output frequency, set parameters (upper limit frequency) and (lower limit<br />

frequency). If process quantities are set from the operation panel, however, the process quantity setting<br />

range will be limited by the settings of and .<br />

(3) Input terminal function “PID control prohibited” (function No.14) can changing PID control or open-loop<br />

control. Also Input terminal function “PID control integral value clear” (function No.65) can use.<br />

(4) By the set the f380 or Input terminal function “PID forward/reverse switching” (function No.72) , PID<br />

control is reverse. When a reverse-characteristic is selected at the same time with the parameter and<br />

the terminal, it becomes a forward characteristic.<br />