(D-gain adjustment parameter)<br />

F-47<br />

E6581381<br />

This parameter adjusts the differential gain level during PID control. This gain increases the speed of<br />

response to a rapid change in deviation (difference between the frequency setting and the amount of<br />

feedback).<br />

Note that setting the gain more than necessary may cause great fluctuations in output frequency, and<br />

thus operation to become unstable.<br />

5) Adjusting analog command voltages<br />

To use external analog setting (VIA or VIB) or feedback input (VIA or VIB), perform voltage-scaling<br />

adjustments (input point setting) as required. ⇒ See section 6.5.2 for further details.<br />

If the feedback input data is too small, voltage-scaling adjustment data can also be used for gain adjustment.<br />

Example of VIB terminal setting Example of VIA terminal setting<br />

(voltage input)<br />

Output frequency<br />

<br />

(60Hz)<br />

<br />

(0Hz)<br />

0V<br />

<br />

0%<br />

10V<br />

<br />

100%<br />

VIB input value<br />

Output frequency<br />

<br />

(60Hz)<br />

<br />

(0Hz)<br />

0V<br />

<br />

0%<br />

10V<br />

<br />

100%<br />

VIA input value<br />

Example of VIA terminal setting<br />

(current input)<br />

Output frequency<br />

<br />

(60Hz)<br />

<br />

(0Hz) 4mA<br />

<br />

20%<br />

VIA input value<br />

20mA<br />

<br />

100%<br />

6) Setting the time elapsed before PID control starts<br />

You can specify a waiting time for PID control to prevent the inverter from starting PID control before the<br />

control system becomes stable, for example, after start-up.<br />

The inverter ignores feedback input signals, carries out operation at the frequency determined by the amount<br />

of processing for the period of time specified with and enters the PID control mode after a lapse of<br />

the specified time.<br />