Title Function Adjustment range Default setting<br />

<br />

Detection of output short-circuit during<br />

start-up<br />

6.17.9 Over-torque trip<br />

: Over-torque trip/alarm selection<br />

: Over-torque detection level<br />

: Over-torque detection time<br />

: Over-torque detection level hysteresis<br />

0: Each time (standard pulse)<br />

1: Only one time after power is<br />

turned on (standard pulse)<br />

2: Each time (short-time pulse)<br />

3: Only one time after power is<br />

turned on (short-time pulse)<br />

• Function<br />

Use the parameter to trip the inverter or to output the alarm if a torque currrent exceeding the<br />

-specified level flows for more than the -specified time. Trip information is displayed<br />

as "".<br />

=: ..........No tripping (FL relay deactivated).<br />

An over-torque alarm can be put out by setting the output terminal function selection<br />

parameter.<br />

=: ..........The inverter is tripped (FL relay activated) only after a torque current exceeding the<br />

-specified level has been detected for more than the -specified time.<br />

Title Function Adjustment range Default setting<br />

Over-torque trip/alarm selection<br />

0: Alarm only<br />

1: Tripping<br />

0<br />

Over-torque detection level 0-250 (%) 130<br />

Over-torque detection time 0.0-10.0 [s] 0.5<br />

Over-torque detection level hysteresis 0-100 (%) 10<br />

0