6<br />

6.17.10 Cumulative operation time alarm setting<br />

: Cumulative operation time alarm setting<br />

F-66<br />

E6581381<br />

• Function<br />

This parameter allows you to set the inverter so that it will put out an alarm signal after a lapse of the<br />

cumulative operation time set with .<br />

* "0.1" displayed on the monitor refers to 10 hours, and therefore "1" denotes 100 hours.<br />

Ex.: 38.5 displayed on the monitor = 3850 (hours)<br />

Title Function Adjustment range Default setting<br />

<br />

Cumulative operation time<br />

alarm setting<br />

0.0-999.9 610.0<br />

■ Setting of output signal l<br />

Ex.: When assigning the cumulative operation alarm signal output function to the RY-RC terminals<br />

Title Function Adjustment range Setting value<br />

<br />

Output terminal selection 1A<br />

(RY-RC)<br />

0-255<br />

6.17.11 Over-voltage stall protection level<br />

: Over-voltage stall protection level<br />

⇒ For more details, see section 6.12.4.<br />

42 (negative<br />

logic 43)