9<br />
Table 1 EMC standards<br />
Category Subcategory<br />
Product<br />
standards<br />
Test standard and level<br />
Emission<br />
Radiation noise<br />
Transmission noise<br />
CISPR11(EN55011)<br />
CISPR11(EN55011)<br />
Static discharge IEC61000-4-2<br />
Radioactive radio-frequency<br />
IEC61000-4-3<br />
Immunity<br />
magnetic contactor field<br />
First transient burst<br />
Lightning surge<br />
IEC 61800-3<br />
IEC61000-4-4<br />
IEC61000-4-5<br />
Radio-frequency<br />
induction/transmission interference<br />
IEC61000-4-6<br />
Voltage dip/Interruption of power<br />
IEC61000-4-11<br />
9.1.2 Measures to satisfy the EMC directive<br />
I-2<br />
E6581381<br />
This subsection explains what measures must be taken to satisfy the EMC directive.<br />
(1) Insert a recommended EMI filter (Table 2) on the input side of the inverter to reduce and transmission noise<br />
and radiation noise from input cables.<br />
In the combinations listed in Table 2, <strong>Inverter</strong>s are tested in these combination to see if they comply with<br />
transmission noise standards. For inverters used in Japan, it is recommended to use the NF series of noise<br />
filters.<br />
Table 2 lists noise filters recommended for the inverters.<br />
Table 2 Combinations of inverter and EMI filter<br />
Three-phase 200V class<br />
Combination of inverter and filter<br />
Transmission noise<br />
<strong>Inverter</strong><br />
EN61800-3, 1st Environment, C2<br />
Length of motor<br />
Applicable filters<br />
connecting cable (m)<br />
<strong>VF</strong><strong>FS1</strong>-2004PM EM<strong>FS1</strong>1-4015BZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2007PM EM<strong>FS1</strong>1-4015BZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2015PM EM<strong>FS1</strong>1-4015BZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2022PM EM<strong>FS1</strong>1-4015BZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2037PM EM<strong>FS1</strong>1-4025CZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2055PM EM<strong>FS1</strong>1-4047DZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2075PM EM<strong>FS1</strong>1-4047DZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2110PM EM<strong>FS1</strong>1-2083EZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2150PM EM<strong>FS1</strong>1-2083EZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2185PM EM<strong>FS1</strong>1-2083EZ 20<br />
<strong>VF</strong><strong>FS1</strong>-2220PM EMF3-4090F 20<br />
<strong>VF</strong><strong>FS1</strong>-2300PM EMF3-4180H 20