10. Peripheral devices<br />
Mandatory<br />
Be Grounded<br />
Warning<br />
• When using switchgear for the inverter, it must be installed in a cabinet.<br />
Failure to do so can lead to risk of electric shock and can result in death or serious injury.<br />
J-1<br />
E6581381<br />
• Connect earth cables securely.<br />
Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric<br />
leak.<br />
10.1 Selection of wiring materials and devices<br />
Voltage<br />
class<br />
Three-phase<br />
200V class<br />
Three-phase<br />
400V class<br />
Wire size (See Note 4)<br />
Power circuit<br />
(mm 2 ) Note 1)<br />
Earth cable<br />
(mm 2 Capacity of<br />
applicable motor<br />
(kW)<br />
<strong>Inverter</strong> model<br />
For IEC60364-5-<br />
For JAPAN<br />
523/54,<br />
JEAC8001-2005<br />
IEC60204-1<br />
)<br />
For IEC60364-5-<br />
For JAPAN<br />
523/54,<br />
JEAC8001-2005<br />
IEC60204-1<br />
0.4 <strong>VF</strong><strong>FS1</strong>-2004PM 1.5 2 2.5 2<br />
0.75 <strong>VF</strong><strong>FS1</strong>-2007PM 1.5 2 2.5 2<br />
1.5 <strong>VF</strong><strong>FS1</strong>-2015PM 1.5 2 2.5 2<br />
2.2 <strong>VF</strong><strong>FS1</strong>-2022PM 1.5 2 2.5 2<br />
4.0 <strong>VF</strong><strong>FS1</strong>-2037PM 2.5 2 2.5 2<br />
5.5 <strong>VF</strong><strong>FS1</strong>-2055PM 4 3.5 4 3.5<br />
7.5 <strong>VF</strong><strong>FS1</strong>-2075PM 6 5.5 6 3.5<br />
11 <strong>VF</strong><strong>FS1</strong>-2110PM 10 14 10 5.5<br />
15 <strong>VF</strong><strong>FS1</strong>-2150PM 16 14 16 5.5<br />
18.5 <strong>VF</strong><strong>FS1</strong>-2185PM 25 22 16 8<br />
22 <strong>VF</strong><strong>FS1</strong>-2220PM 25 38 16 8<br />
30 <strong>VF</strong><strong>FS1</strong>-2300PM 50 38 25 14<br />
0.4 <strong>VF</strong><strong>FS1</strong>-4004PL 1.5 2 2.5 2<br />
0.75 <strong>VF</strong><strong>FS1</strong>-4007PL 1.5 2 2.5 2<br />
1.5 <strong>VF</strong><strong>FS1</strong>-4015PL 1.5 2 2.5 2<br />
2.2 <strong>VF</strong><strong>FS1</strong>-4022PL 1.5 2 2.5 2<br />
4.0 <strong>VF</strong><strong>FS1</strong>-4037PL 1.5 2 2.5 2<br />
5.5 <strong>VF</strong><strong>FS1</strong>-4055PL 1.5 2 2.5 2<br />
7.5 <strong>VF</strong><strong>FS1</strong>-4075PL 1.5 2 2.5 2<br />
11 <strong>VF</strong><strong>FS1</strong>-4110PL 4 3.5 4 3.5<br />
15 <strong>VF</strong><strong>FS1</strong>-4150PL 6 5.5 6 3.5<br />
18.5 <strong>VF</strong><strong>FS1</strong>-4185PL 6 5.5 6 5.5<br />
22 <strong>VF</strong><strong>FS1</strong>-4220PL 10 8 10 5.5<br />
30 <strong>VF</strong><strong>FS1</strong>-4300PL 16 14 16 5.5<br />
37 <strong>VF</strong><strong>FS1</strong>-4370PL 25 22 16 8<br />
45 <strong>VF</strong><strong>FS1</strong>-4450PL 35 38 16 8<br />
55 <strong>VF</strong><strong>FS1</strong>-4550PL 50 38 25 6<br />
75 <strong>VF</strong><strong>FS1</strong>-4750PL 70 60 35 6<br />
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,<br />
V/T2 and W/T3 when the length of each wire does not exceed 30m.<br />
Note 2: For the control circuit, use shielded wires 0.75 mm 2 or more in diameter.<br />
Note 3: For grounding, use a cable with a size equal to or larger than the above.<br />
10