10. Peripheral devices<br />

Mandatory<br />

Be Grounded<br />

Warning<br />

• When using switchgear for the inverter, it must be installed in a cabinet.<br />

Failure to do so can lead to risk of electric shock and can result in death or serious injury.<br />

J-1<br />

E6581381<br />

• Connect earth cables securely.<br />

Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric<br />

leak.<br />

10.1 Selection of wiring materials and devices<br />

Voltage<br />

class<br />

Three-phase<br />

200V class<br />

Three-phase<br />

400V class<br />

Wire size (See Note 4)<br />

Power circuit<br />

(mm 2 ) Note 1)<br />

Earth cable<br />

(mm 2 Capacity of<br />

applicable motor<br />

(kW)<br />

<strong>Inverter</strong> model<br />

For IEC60364-5-<br />

For JAPAN<br />

523/54,<br />

JEAC8001-2005<br />

IEC60204-1<br />

)<br />

For IEC60364-5-<br />

For JAPAN<br />

523/54,<br />

JEAC8001-2005<br />

IEC60204-1<br />

0.4 <strong>VF</strong><strong>FS1</strong>-2004PM 1.5 2 2.5 2<br />

0.75 <strong>VF</strong><strong>FS1</strong>-2007PM 1.5 2 2.5 2<br />

1.5 <strong>VF</strong><strong>FS1</strong>-2015PM 1.5 2 2.5 2<br />

2.2 <strong>VF</strong><strong>FS1</strong>-2022PM 1.5 2 2.5 2<br />

4.0 <strong>VF</strong><strong>FS1</strong>-2037PM 2.5 2 2.5 2<br />

5.5 <strong>VF</strong><strong>FS1</strong>-2055PM 4 3.5 4 3.5<br />

7.5 <strong>VF</strong><strong>FS1</strong>-2075PM 6 5.5 6 3.5<br />

11 <strong>VF</strong><strong>FS1</strong>-2110PM 10 14 10 5.5<br />

15 <strong>VF</strong><strong>FS1</strong>-2150PM 16 14 16 5.5<br />

18.5 <strong>VF</strong><strong>FS1</strong>-2185PM 25 22 16 8<br />

22 <strong>VF</strong><strong>FS1</strong>-2220PM 25 38 16 8<br />

30 <strong>VF</strong><strong>FS1</strong>-2300PM 50 38 25 14<br />

0.4 <strong>VF</strong><strong>FS1</strong>-4004PL 1.5 2 2.5 2<br />

0.75 <strong>VF</strong><strong>FS1</strong>-4007PL 1.5 2 2.5 2<br />

1.5 <strong>VF</strong><strong>FS1</strong>-4015PL 1.5 2 2.5 2<br />

2.2 <strong>VF</strong><strong>FS1</strong>-4022PL 1.5 2 2.5 2<br />

4.0 <strong>VF</strong><strong>FS1</strong>-4037PL 1.5 2 2.5 2<br />

5.5 <strong>VF</strong><strong>FS1</strong>-4055PL 1.5 2 2.5 2<br />

7.5 <strong>VF</strong><strong>FS1</strong>-4075PL 1.5 2 2.5 2<br />

11 <strong>VF</strong><strong>FS1</strong>-4110PL 4 3.5 4 3.5<br />

15 <strong>VF</strong><strong>FS1</strong>-4150PL 6 5.5 6 3.5<br />

18.5 <strong>VF</strong><strong>FS1</strong>-4185PL 6 5.5 6 5.5<br />

22 <strong>VF</strong><strong>FS1</strong>-4220PL 10 8 10 5.5<br />

30 <strong>VF</strong><strong>FS1</strong>-4300PL 16 14 16 5.5<br />

37 <strong>VF</strong><strong>FS1</strong>-4370PL 25 22 16 8<br />

45 <strong>VF</strong><strong>FS1</strong>-4450PL 35 38 16 8<br />

55 <strong>VF</strong><strong>FS1</strong>-4550PL 50 38 25 6<br />

75 <strong>VF</strong><strong>FS1</strong>-4750PL 70 60 35 6<br />

Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,<br />

V/T2 and W/T3 when the length of each wire does not exceed 30m.<br />

Note 2: For the control circuit, use shielded wires 0.75 mm 2 or more in diameter.<br />

Note 3: For grounding, use a cable with a size equal to or larger than the above.<br />

10