3 Installation<br />
3.1 Mounting of casing<br />
The <strong>ELC</strong> must be installed in a control cabinet with at least IP 54 protection (see<br />
EN 60529). Operation without a control cabinet or in a control cabinet with a<br />
lower degree of protection is not permitted.<br />
It is only permitted to install the appliance in the positions described in 3.1.1 or<br />
3.1.2. When installed vertically, as described in Fig. 1, the control connections<br />
must be positioned at the bottom and supply connections at the top. Installation<br />
must allow for the minimum spacing.<br />
The <strong>ELC</strong> should not be mounted in the immediate proximity of sensitive<br />
<strong>electronic</strong> equipment. An appropriate distance must be maintained to scatter<br />
field transformers or other inductors.<br />
The flow of cool air for the <strong>ELC</strong> must be safeguarded. The ambient temperature<br />
must not exceed the values prescribed in chapter 6.<br />
Ventilation must be provided for the switch cabinet.<br />
The amount of air necessary is determined by the size and positioning of the<br />
switch cabinet, the total electrical losses and the external temperature. Please<br />
consult your switch cabinet manufacturer. For the recommended throughput of<br />
air please see the technical data in chapter 6.<br />
Impure cooling air could affect the functionality of the <strong>ELC</strong>. This can be avoided<br />
by installing a fine air filter.<br />
<strong>ELC</strong> <strong>PE22</strong>_PE32-V2.2-09.11-GB Subject to technical alterations