<strong>MAC10</strong> / <strong>MAC11</strong> / <strong>EFC</strong><br />
Constant pressure and<br />
electronic speed regulators<br />
• <strong>MAC10</strong> / <strong>MAC11</strong><br />
• <strong>EFC</strong>16EU01<br />
• <strong>EFC</strong>35 / <strong>EFC</strong>35G / <strong>EFC</strong>35S<br />
• <strong>EFC</strong>50 / <strong>EFC</strong>80 / <strong>EFC</strong>80C<br />
• <strong>EFC</strong>1P<br />
Above set point limit<br />
Pressure set point<br />
Below set point limit<br />
Time before alarm ALARM!<br />
Measured pressure<br />
Product information - Version 2
Table of contents<br />
Constant pressure regulator <strong>MAC10</strong> . . 4<br />
- Dimensional sketches and technical specifi cations ............ 4<br />
- Voltage regulator <strong>MAC10</strong>MPR .................................... 5<br />
- Pressure transducer MAC XTP ..................................... 5<br />
- Outside air temperature sensor <strong>MAC10</strong> XTT .............. 6<br />
- Cable plans ............................................................. 6-7<br />
Constant pressure regulator <strong>MAC11</strong> . . 8<br />
- Dimensional sketch and technical specifi cations ............. 8<br />
- Pressure transducer (XTP sensor) ................................. 9<br />
- Outside air temperature sensor (XTT sensor) ............. 10<br />
- Bus communication (LON network) ........................... 10<br />
- Cable plans .............................................................. 11<br />
Electronic speed regulators ............ 12<br />
- <strong>EFC</strong>16EU01 - Technical specifi cations ........................ 12<br />
- <strong>EFC</strong>35/<strong>EFC</strong>35G/<strong>EFC</strong>35S - Tech. specifi cations ............ 13<br />
- <strong>EFC</strong>50/<strong>EFC</strong>80/<strong>EFC</strong>80C - Tech. specifi cations .............. 14<br />
Electronic speed regulator for<br />
ventilator units with FC motors ..... 15<br />
- <strong>EFC</strong>1P - Technical specifi cations ............................... 15<br />
For more information<br />
- Visit our website<br />
<strong>MAC11</strong><br />
<strong>MAC10</strong><br />
2<br />
On-demand controlled<br />
<strong>EXHAUSTO</strong> constant pressure and speed regulators are used to<br />
variably regulate <strong>EXHAUSTO</strong> ventilators and air handling units.<br />
The <strong>EFC</strong>16-<strong>EFC</strong>80 voltage regulators variably regulate the speed<br />
of 1 x 230 V <strong>EXHAUSTO</strong> ventilators.<br />
Voltage regulation<br />
Fan<br />
n<br />
Rpm<br />
U<br />
Volt<br />
I<br />
Amp<br />
P 1<br />
kW<br />
P 2<br />
kW<br />
Regulator type<br />
Manual Constant pressure<br />
BESB250-4-1 1400 1x230 0,98 0,22 0,10 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
BESB315-4-1 1400 1x230 2,60 0,45 0,30 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
BESF146-4-1 1400 1x230 0,40 0,10 0,04 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
BESF160-4-1 1400 1x230 0,80 0,19 0,09 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
BESF180-4-1 1400 1x230 1,80 0,35 0,18 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
BESF200-4-1 1400 1x230 2,60 0,53 0,30 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
BESF225-4-1 1400 1x230 3,90 0,75 0,45 <strong>EFC</strong>50 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTV160-4-1 1400 1x230 0,20 0,04 0,01 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTV200-4-1 1400 1x230 0,40 0,07 0,04 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTV250-4-1 1400 1x230 0,80 0,16 0,09 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTV315-4-1 1400 1x230 1,80 0,37 0,25 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTV400-4-1 1400 1x230 2,90 0,60 0,40 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTH160-4-1 1400 1x230 0,20 0,04 0,01 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTH200-4-1 1400 1x230 0,40 0,07 0,04 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTH250-4-1 1400 1x230 0,80 0,16 0,09 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTH315-4-1 1400 1x230 1,80 0,37 0,25 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
DTH400-4-1 1400 1x230 2,60 0,60 0,40 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />
<strong>MAC10</strong> and <strong>MAC11</strong> constant pressure regulators<br />
<strong>EXHAUSTO</strong> constant pressure regulators <strong>MAC10</strong> and <strong>MAC11</strong> are<br />
the perfect choice for controlling on-demand, energy-optimised<br />
ventilator solutions. They meet the need for low energy consumption,<br />
reliability and the required ventilation requirements.<br />
The <strong>MAC10</strong> and <strong>MAC11</strong> (Multi Application Controller) microprocessor-based<br />
constant pressure regulators are designed for
ventilation with constant pressure & speed regulators<br />
All regulators have a control panel with control knob to variably<br />
adjust the airfl ow as required. The control knob on an<br />
<strong>EFC</strong>12-<strong>EFC</strong>80 control panel also functions as start/stop.<br />
All control panels have a green LED to indicate the ventilator<br />
motor is running.<br />
Frequency regulation<br />
Fan<br />
n<br />
Rpm<br />
U<br />
Volt<br />
I<br />
Amp<br />
P 1<br />
kW<br />
P 2<br />
kW<br />
3<br />
Regulator type<br />
Manual Constant pressure<br />
BESB250-4-1FC 1400 1x230 1,40 0,20 0,18 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESB315-4-1FC 1400 1x230 2,40 0,39 0,37 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESB250-4-1FC 1400 1x230 3,70 0,84 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESB400-4-1FC 1300 1x230 6,80 1,01 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESB500-4-3FC 1700 3x400 6,10 2,30 2,20 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESB500-4-3 1400 3x230D/400Y 5,00/2,90 1,47 1,10 Fixed rpm*<br />
BESF180-4-1FC 1400 1x230 1,90 0,31 0,18 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESF200-4-1FC 1400 1x230 2,40 0,55 0,37 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESF225-4-1FC 1400 1x230 3,70 0,84 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESF250-4-1FC 1400 1x230 9,50 1,47 1,10 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESF280-4-3FC 1400 3x400 6,50 2,55 2,20 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
BESF250-4-3 1400 3x230D/400Y 5,00/2,90 1,47 1,10 Fixed rpm*<br />
BESF280-4-3 1400 3x230D/400Y 9,30/5,40 2,55 2,20 Fixed rpm*<br />
DTV250-4-1FC 1600 1x230 1,40 0,21 0,18 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
DTV315-4-1FC 1600 1x230 2,70 0,44 0,37 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
DTV400-4-1FC 1600 1x230 3,70 0,85 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
DTV450-4-1FC 1700 1x230 9,40 1,47 1,10 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />
* If appropriate, frequency converter<br />
<strong>EFC</strong>16 <strong>EFC</strong>35 <strong>EFC</strong>50 <strong>EFC</strong>80<br />
<strong>EFC</strong>1P<br />
ventilators with FC motors. They can be supplied with outside<br />
air temperature sensors, allowing operation with outside air<br />
temperature compensation.<br />
For single-phase motors without FC use the <strong>MAC10</strong> with<br />
the <strong>MAC10</strong>MPR add-on module. <strong>MAC11</strong> is available with<br />
LonWorks ® – a communication platform for DDC units.<br />
The regulator’s built-in potentiometer can set a minimum<br />
voltage/airfl ow. <strong>EFC</strong>1P is an electronic speed regulator for<br />
<strong>EXHAUSTO</strong> FC motors (motors with frequency converters).<br />
They are used to manually regulate the speed of revolution of<br />
<strong>EXHAUSTO</strong> ventilators which are fi tted to FC motors.<br />
P = maximum power consumption (Watt).<br />
1<br />
P = power rating (Watt), which is the<br />
2<br />
power rating marked on the motor.<br />
BESB box fan<br />
BESF box fan<br />
DTV roof fan<br />
DTH roof fan<br />
BESB box fan<br />
with frequency converter<br />
BESF box fan<br />
with frequency converter<br />
DTV roof fan<br />
with frequency converter<br />
The <strong>MAC10</strong> constant pressure regulators and the <strong>MAC11</strong>,<br />
which can be set to a high or low pressure setting, are wellsuited<br />
to the comfort ventilation of residences and other<br />
indoor environments, such as offi ces, restaurants, etc. The<br />
high and low pressure setting can be made manually, with<br />
help from an external timer, other third-party control system<br />
or via an outside air temperature sensor.
Constant pressure regulator - <strong>MAC10</strong><br />
The <strong>MAC10</strong> controls fan unit operation and maintains the<br />
required pressure.<br />
The <strong>MAC10</strong> offers two pre-set pressures (high/low), so that<br />
ventilation can be adjusted to meet operational requirements.<br />
The high and low pressure settings are set individually in the<br />
constant pressure regulator using a simple menu.<br />
The <strong>MAC10</strong> has a built-in alarm function that automatically<br />
displays a message when the required pressure cannot be<br />
met.<br />
The unit also includes an isolator switch for use with an<br />
external alarm.<br />
The <strong>MAC10</strong> lets the user set the pressure deviation required to<br />
trigger the alarm, as well as how long this deviation can<br />
continue before the alarm is activated.<br />
Type <strong>MAC10</strong><br />
Supply voltage 230 VAC<br />
Recommended operating range 50-500 Pa<br />
Ambient temperature -20ºC to +50ºC<br />
Settings’ range - alarm pressure 0-500 Pa<br />
Settings’ range - alarm time 0-1000 secs.<br />
Settings’ temp. - low -25ºC to 0ºC<br />
Settings’ temp. - high -10ºC to 15ºC<br />
Alarm switch (max. load) Isolator switch: 230 VAC, 8 A, AC1<br />
Ingress protection IP54<br />
4<br />
The constant pressure regulator will continue to operate after<br />
the alarm has been triggered and continue to attempt to<br />
maintain the required pressure.<br />
The <strong>MAC10</strong> can be connected to a thermal circuit breaker<br />
located in the fan motor. Any cut-out of this unit will also<br />
trigger an alarm.<br />
The <strong>MAC10</strong> also has an external start/stop system option and<br />
an override setting to max. airfl ow.<br />
The <strong>MAC10</strong> can be located wherever it is most appropriate<br />
– in a control room or next to the fan unit with a signal to the<br />
control room.<br />
The <strong>MAC10</strong> is supplied with an XTP sensor as standard.
Pressure transducer - MACXTP<br />
The pressure transducer is supplied with plug outlet,<br />
measuring probe and hose.<br />
The pressure transducer measures the current pressure in the<br />
duct system, and the <strong>MAC10</strong> regulates the fan unit's output<br />
in line with the pre-set pressure. The pressure measured in the<br />
duct system can be read on the <strong>MAC10</strong>'s display.<br />
A different pressure transducer to the one provided can be<br />
used, as the value can be changed in the <strong>MAC10</strong>.<br />
Type XTP-sensor<br />
Supply voltage (from MAC)<br />
15 VDC to 38 VDC,<br />
12 VAC to 28 VAC<br />
Operating range 0-500 Pa<br />
Permissible ambient temp. -18ºC to +60ºC<br />
Output signal 0-10 VDC<br />
Accuracy ±3% full scale<br />
Linearity ±2% full scale<br />
Ingress protection IP54<br />
Max. cable length to <strong>MAC10</strong> 80 m shielded cable<br />
Voltage regulator - <strong>MAC10</strong>MPR<br />
The <strong>MAC10</strong> MPR is used for controlling motors without a<br />
built-in control function.<br />
The <strong>MAC10</strong> MPR can be linked directly to the <strong>MAC10</strong>.<br />
Type <strong>MAC10</strong> MPR<br />
Supply voltage 230 VAC, 50 Hz, max. 13 A<br />
Output voltage 25-230 VAC<br />
Ambient temperature -20ºC to +50ºC<br />
Max. load 4 A<br />
Input signal 0-10 VDC<br />
120 x 170 x 59 mm<br />
Size (H x W x D)<br />
See dimensional sketches for<br />
the <strong>MAC10</strong><br />
Ingress protection IP54<br />
5<br />
The pressure transducer has two pressure connections. The<br />
fi rst links to the duct system, where the pressure is to be kept<br />
at a constant level. The second is used as a reference and can<br />
be led to a neutral reference area.<br />
The pressure transducer should be placed appropriately in<br />
relation to the measuring probe and should be easily<br />
accessible.<br />
The <strong>MAC10</strong> MPR has MAX/MIN trimmers (potentiometers) for<br />
setting up the limits for the output voltage.
The outside air temperature sensor - <strong>MAC10</strong>XTT<br />
The MAX10 constant pressure regulator can be connected to<br />
an outside temperature sensor (available as an accessory),<br />
making it possible to operate with outside temperature<br />
compensation. This means that the high setting for pressure<br />
can be lowered if the outside temperature falls. This compensation<br />
continues lineally between the two pre-set temperatures<br />
and pressure (high/low). When the compensation function<br />
is active, it can be read in the <strong>MAC10</strong>'s display.<br />
Type 22K NTC 2% XTT-sensor<br />
Operating range -40ºC to +60ºC<br />
Accuracy ±2% of full scale<br />
80 x 80 x 55 mm<br />
Size (H x W x D)<br />
See dimensional sketches for<br />
MAC XTP<br />
Ingress protection IP54<br />
Max. cable length to <strong>MAC10</strong> 40 m<br />
Cable plans - <strong>MAC10</strong><br />
Fan motor type: DTV/BESB/BESFxxx-4-1<br />
6<br />
The outside air temperature sensor is placed in an appropriate<br />
outside location where it can measure the real outdoor<br />
temperature. The sensor must not be placed so that it can be<br />
affected by external factors that might infl uence the measured<br />
temperature, e.g. sun and wind.<br />
The <strong>MAC10</strong> constant pressure regulator is used for fan units with motors that are equipped with motor power relays (MPR),<br />
frequency converters or single-phase motors set up with the <strong>MAC10</strong> MPR. The cable plans show the default confi guration.<br />
No connection is shown to: an XTT sensor, an external on/off clock, an external mode switch, or an alarm output.<br />
* Not fitted by <strong>EXHAUSTO</strong>
Cable plans – <strong>MAC10</strong><br />
Fan motor type: DTV/BESB/BESFxxx-x-1FC<br />
Fan motor type: BESB/BESFxxx-4-3FC (Omron freq. conv.)<br />
* Not fitted by <strong>EXHAUSTO</strong><br />
7
Constant pressure regulator - <strong>MAC11</strong> with LON communication<br />
<strong>MAC11</strong> controls the Start/Stop of the ventilation fan and<br />
constantly modulates the fan speed to maintain the pre-set<br />
pressure in the entire ductwork system.<br />
<strong>MAC11</strong> offers the possibility of setting two different pressure<br />
levels. The high and low pressure level is adjusted via the<br />
simple menu on the control unit.<br />
<strong>MAC11</strong> has a built-in alarm, which is activated and displayed<br />
when the pre-set pressure cannot be obtained. It is possible<br />
to adjust how large a deviation from the pre-set pressure will<br />
Type <strong>MAC11</strong><br />
Supply voltage 230 VAC<br />
Range 0-500 Pa<br />
Recommended operating range 50-500 Pa<br />
Regulating accuracy 10 Pa<br />
Ambient temperature -20ºC to +50ºC (Display function: 0-50ºC)<br />
Settings’ range - alarm pressure 10-500 Pa<br />
Settings’ range - alarm time 30-600 secs.<br />
Settings’ temp. - low -30ºC to 0ºC<br />
Settings’ temp. - high -10ºC to +20ºC<br />
Alarm contact Isolator switch (max load 230 VAC, 8 A, AC)<br />
Size (H x W x D) 124 x 175 x 95 mm (inkl. control knob)<br />
Ingress protection IP54<br />
Communication interface to LON network with FTT 10A transceiver<br />
Supply voltage for XTP and XTT sensor<br />
8<br />
activate the alarm.<br />
The time of deviation before the alarm is activated can be set<br />
between 30-600 seconds.<br />
The controller will continue to run the ventilation unit during<br />
the alarm period.<br />
The <strong>MAC11</strong> is supplied with an XTP sensor as standard.
Pressure transducer (XTP-sensor)<br />
The XTP pressure transducer is supplied with plug, measuring<br />
probe and hoses. The pressure transducer measures the<br />
current pressure in the duct system, and the <strong>MAC11</strong> regulates<br />
the ventilator’s output in line with the pre-set pressure. The<br />
pressure measured in the duct system can be read on the<br />
<strong>MAC11</strong> display.<br />
Because the pressure sensitivity can be set in the <strong>MAC11</strong>, a<br />
pressure transducer with a different sensitivity than the one<br />
supplied, can be connected.<br />
The pressure transducer has two pressure connections. One<br />
connection links to the duct system, where the required pressure<br />
is to be kept at a constant level. The second is used as a<br />
pressure reference and can be led to a neutral reference area.<br />
The pressure transducer is positioned appropriately in relation to<br />
the measuring probe. It should be easily accessible.<br />
Type XTP-sensor<br />
Supply voltage (from MAC) 24 VAC<br />
Scope of operation 0-500 Pa<br />
Output signal accuracy (in area 50-500 Pa by 20ºC) 2.5% of measured value<br />
Operating temperature range<br />
(-20ºC to +60ºC in relation to 20ºC)<br />
10 Pa<br />
Permissible ambient temperature -20ºC to +60ºC<br />
Ambient temperature 0ºC to 40ºC<br />
Output signal 0-10 V<br />
Settings’ temperature - low -30ºC to 0ºC<br />
Ingress protection IP54<br />
9<br />
The pressure transducer must be positioned vertically as shown<br />
in the diagram. Delivered with 2 m hose.<br />
NB: As the values can be set in the <strong>MAC11</strong>, a pressure<br />
transducer with a maximum sensitivity in the range of 50-500<br />
Pa can be connected.
Outdoor temperature sensor (XTT-sensor)<br />
To be able to compensate for changes in the outdoor<br />
temperature the <strong>MAC11</strong> can be connected to an external<br />
temperature sensor. (Accessory).<br />
The high pressure setting will fall in line with falling outdoor<br />
temperatures. The compensation will be linear between two<br />
pre-set temperatures and pressures (high/low)<br />
Bus communication (LonWorks ® )<br />
LONWORKS ® is a standardised communication system which is<br />
used by most of the major suppliers of automation systems.<br />
The communication between two units using LON communication<br />
is through a four core cable. Two cores supply the power<br />
to the connected units, and two cores are used for<br />
communication.<br />
The LON bus can connect one or more <strong>MAC11</strong> units. The<br />
ventilation units can thus alter their output relative to outdoor<br />
temperature.<br />
65<br />
113<br />
50<br />
10<br />
The outdoor temperature sensor is connected to the <strong>MAC11</strong><br />
via a LON network. Several <strong>MAC11</strong> control units can be<br />
connected to the same outdoor temperature sensor. The<br />
sensor is placed where the actual outdoor temperature can be<br />
measured without influence from wind and sunshine.<br />
Type XTP-sensor<br />
Supply voltage (from MAC) 24 VAC<br />
Operating temperature -45ºC to +70ºC<br />
Output signal accuracy ±1% of measured value<br />
Resolution 0.1ºC<br />
Size (H x B x D) 50 x 113 x 37 mm<br />
Ingress Protection IP54<br />
By using the LON system for communication, the distance<br />
between the temperature sensor and the <strong>MAC11</strong> units will<br />
have no influence on the accuracy of the measuring signal.<br />
With LONWORKS ® the system can be further developed over<br />
time.
Cable plans<br />
The <strong>MAC11</strong> constant pressure regulator is used with ventilators with FC motors. The cable plans show the default configuration.<br />
Connections to an XTT sensor, an external on/off clock, an external mode switch, or an alarm output are not shown.<br />
Fan motor type: DTV/BESB/BESFxxx-4-1FC<br />
Fan motor type: BESB/BESFxxx-4-3FC (Omron freq. conv.)<br />
* Not fitted by <strong>EXHAUSTO</strong><br />
11
<strong>EFC</strong> - Electronic speed regulator<br />
The <strong>EFC</strong> electronic speed regulator has been designed for<br />
variable speed regulation of <strong>EXHAUSTO</strong> fans and air handling<br />
units operating on 1 x 230 V. The <strong>EFC</strong> unit variably regulates<br />
the speed of the motor, making it possible to vary the capacity<br />
of the fan from 25–100 %.<br />
The knob on the speed regulator unit features a built-in on/off<br />
switch and the unit itself has an internal minimum-speed<br />
trimmer.<br />
<strong>EFC</strong>16EU01 – Technical specifications<br />
85<br />
85 32,5<br />
49,9<br />
Type <strong>EFC</strong>16EU01<br />
Voltage 230 VAC<br />
Load Max. 1.5 A<br />
Internal fuse T 1.6 AH<br />
Max. fuse 13 A<br />
Ambient temperature 0-40ºC<br />
Min. output voltage Built-in potentiometer<br />
Ingress protection IP20<br />
Material Thermoplastic ABS<br />
Colour White<br />
Min. opening for installation H 54 x W 68 x D 24 mm<br />
60<br />
70<br />
22 40<br />
12<br />
6,5<br />
12<br />
The regulators are CE marked and EMC certified.<br />
The <strong>EFC</strong> is available in the following models – 16, 35, 50, 80<br />
– and in a range of different designs. The <strong>EFC</strong>16 can be built<br />
into walls.<br />
RD11258-01<br />
Ventilator/fan<br />
2-conductor operation<br />
3-conductor operation<br />
2-conductor<br />
operation<br />
3-conductor<br />
operation<br />
BESB250-4-1 X<br />
BESF146-4-1 X<br />
BESF160-4-1 X<br />
DTV160-4-1 X<br />
DTV200-4-1 X<br />
DTV250-4-1 X<br />
DTH160-4-1 X<br />
DTH200-4-1 X<br />
DTH250-4-1 X
102<br />
<strong>EFC</strong>35 / <strong>EFC</strong>35G / <strong>EFC</strong>35S – Technical specifications<br />
74<br />
48,5<br />
Type <strong>EFC</strong>35 / <strong>EFC</strong>35G <strong>EFC</strong>35S<br />
Voltage 230 VAC 230 VAC<br />
Load Max. 3.5A Max. 3.5A<br />
Internal fuse T 4 AH T 4 AH<br />
Max. fuse 13 A 13 A<br />
Ambient temperature 0-35ºC 0-35ºC<br />
Min. output voltage<br />
Built-in<br />
potentiometer<br />
Built-in<br />
potentiometer<br />
Ingress protection IP20 IP44<br />
Material Thermoplastic ABS Thermoplastic ABS<br />
Colour<br />
White (<strong>EFC</strong>35) /<br />
grey (<strong>EFC</strong>35G)<br />
Grey<br />
67<br />
52<br />
13<br />
11<br />
RD11262-01<br />
<strong>EFC</strong>35S dimensions:<br />
Height: 120 mm<br />
Width: 80 mm<br />
Depth without knob: 55 mm<br />
Depth with knob: 77 mm<br />
Ventilator/fan<br />
2-conductor<br />
operation<br />
2-conductor operation<br />
3-conductor operation<br />
3-conductor<br />
operation<br />
BESB250-4-1 X<br />
BESB315-4-1 X<br />
BESF146-4-1 X<br />
BESF160-4-1 X<br />
BESF180-4-1 X<br />
BESF200-4-1 X<br />
DTV160-4-1 X<br />
DTV200-4-1 X<br />
DTV250-4-1 X<br />
DTV315-4-1 X<br />
DTV400-4-1 X<br />
DTH160-4-1 X<br />
DTH200-4-1 X<br />
DTH250-4-1 X<br />
DTH315-4-1 X<br />
DTH400-4-1 X
200<br />
<strong>EFC</strong>50 / <strong>EFC</strong>80 / <strong>EFC</strong>80C - Technical specifi cations<br />
120<br />
<strong>EFC</strong>50 / <strong>EFC</strong>80 / <strong>EFC</strong>80C<br />
Type <strong>EFC</strong>50 <strong>EFC</strong>80 <strong>EFC</strong>80C<br />
Voltage 230 VAC 230 VAC 230 VAC<br />
Load Max. 5 A Max. 8 A Max. 8 A<br />
Internal fuse T 5 AH T 8 AH T 8 AH<br />
Max. fuse 13 A 13 A 13 A<br />
Ambient<br />
temperature<br />
Min. output<br />
voltage<br />
Max. output<br />
voltage<br />
75<br />
0-35ºC 0-35ºC 0-35ºC<br />
Built-in<br />
potentiometer<br />
Built-in<br />
potentiometer<br />
93<br />
Built-in<br />
potentiometer<br />
Built-in<br />
potentiometer<br />
2-speed operation Via external unit Via external unit<br />
Ingress protection IP32 IP32 IP22<br />
Material<br />
Thermoplastic<br />
ABS<br />
Thermoplastic<br />
ABS<br />
Colour White White White<br />
RD11263-01<br />
240<br />
Built-in<br />
potentiometer<br />
Built-in<br />
potentiometer<br />
Run by built-in<br />
timer<br />
Thermoplastic<br />
ABS<br />
14<br />
120<br />
Ventilator/fan<br />
2-conductor<br />
operation<br />
2-conductor operation<br />
3-conductor operation<br />
100<br />
118<br />
3-conductor<br />
operation<br />
BESB250-4-1 X<br />
BESB315-4-1 X<br />
BESF146-4-1 X<br />
BESF160-4-1 X<br />
BESF180-4-1 X<br />
BESF200-4-1 X<br />
BESF225-4-1 X<br />
DTV160-4-1 X<br />
DTV200-4-1 X<br />
DTV250-4-1 X<br />
DTV315-4-1 X<br />
DTV400-4-1 X<br />
DTH160-4-1 X<br />
DTH200-4-1 X<br />
DTH250-4-1 X<br />
DTH315-4-1 X<br />
DTH400-4-1 X<br />
RD11264-01
<strong>EFC</strong>1P - Electronic speed regulator<br />
For ventilators with fi tted <strong>EXHAUSTO</strong> FC motors.<br />
Control panel for fans with FC motor (dimensions in mm)<br />
<strong>EFC</strong>1P – Technical specifi cations<br />
Type <strong>EFC</strong>16EU01<br />
Ambient temperature -20°C to +40°C<br />
Min. output voltage Built-in potentiometer<br />
Ingress protection IP20<br />
Material Thermoplastic ABS<br />
Colour White<br />
Min. opening for installation H 53 x W 53 x D 56 mm<br />
<strong>EFC</strong>1P – Cable plans<br />
The supply cable must be dimensioned in accordance with<br />
applicable regulations and legislation. The conditions at the<br />
installation location, including temperature and the path of<br />
the cable must be taken into consideration.<br />
The FC motor has over current and overheating protection.<br />
The motor needs no additional protection. The fault indication<br />
output of the motor cannot be used for external fault<br />
reporting, as it is used with the <strong>EFC</strong>1P.<br />
When installing multiple single-phase ventilators with FC<br />
motors in the same network with a shared neutral conductor,<br />
special requirements apply to the dimensioning of this<br />
conductor, as the current is not a pure sine wave.<br />
For example, if three single-phase ventilators with FC motors<br />
are installed and divided between three phases, the current in<br />
the neutral conductor is equal to that of the three ventilators<br />
combined.<br />
If you are fi tting fan units to an existing installation, make sure<br />
that the neutral conductor can cope with the resultant load.<br />
15<br />
The <strong>EFC</strong>1P speed regulator control panel<br />
controls the frequency converter in the<br />
FC motor. The linear 0-10 scale sets the<br />
ventilator’s speed of revolution.<br />
The control panel contains a potentiometer<br />
with a circuit breaker built into the switch.<br />
Functions:<br />
1. Start/stop and speed setting of the ventilator (potentiometer<br />
with built-in on/off switch)<br />
2. Operating LED (green) for the fan motor.<br />
3. Alarm LED (red) to indicate motor overheating or over current.<br />
1<br />
2<br />
3<br />
5509019-01<br />
6 x 0.6 mm<br />
E 1*<br />
7 x 0.6 mm<br />
Simplifi ed diagram<br />
*E 1 connection box<br />
(not supplied by <strong>EXHAUSTO</strong>)<br />
For more information regarding electrical connection, refer to<br />
the <strong>EFC</strong>1P product instructions.<br />
Earth leak circuit breakers:<br />
Only Type-A earth-leakage circuit breakers, in accordance<br />
with IEC 755, Amendment 2, can be used with single-phase<br />
ventilators with FC motors. These circuit breakers also break<br />
the circuit when DC current (pulsating DC) is detected.<br />
These circuit breakers are marked with:<br />
Only Type-B earth-leakage circuit breakers<br />
can be used with three-phase ventilators<br />
with FC motors.<br />
These circuit breakers are marked:<br />
See BESB product information.
3003151 - 04.2011 - We reserve the right to make changes without notice.<br />
<strong>EXHAUSTO</strong> - indoor air quality<br />
makes a difference<br />
Technologies<br />
<strong>EXHAUSTO</strong> provides three technologies within<br />
heat recovery, cross-fl ow heat exchangers,<br />
rotary heat exchangers and counter fl ow heat<br />
exchangers. The three technology platforms<br />
have their own unique advantages and<br />
applications.<br />
Our innovation is aimed at energy optimisation<br />
in all regards - we develop products<br />
that set the standard for future energy<br />
requirements.<br />
<strong>EXHAUSTO</strong> VENTILATION Ltd.<br />
Unit 1, Pelham Court<br />
Pelham Place<br />
Broadfield - Crawley<br />
West Sussex -�RH11 9SH<br />
System solutions<br />
<strong>EXHAUSTO</strong> consistently develops system<br />
solutions that support professional project<br />
planning of ventilation for residences, offi ces<br />
and schools. Every single system meets both<br />
regulatory requirements and building owners’<br />
needs and requirements.<br />
The individual systems are naturally supported<br />
by the <strong>EXHAUSTO</strong> products best suited to<br />
each and every installation.<br />
Tel. 01293 511555<br />
Fax 01293 533888<br />
info@exhausto-ventilation.co.uk<br />
www.exhausto-ventilation.co.uk<br />
Indoor air quality competences<br />
<strong>EXHAUSTO</strong> is part of VKR Holding A/S,<br />
incorporated in the company’s ventilation and<br />
indoor climate business area. VKR Holding A/S<br />
aims to provide customers with innovative and<br />
energy-effi cient solutions to ensure an excellent<br />
indoor climate in new and existing buildings.<br />
To read more visit www.vkr-holding.com<br />
At <strong>EXHAUSTO</strong>, we consistently strive to<br />
improve the performance of our products, to<br />
enhance not only indoor air quality but also the<br />
global climate – benefi ting everyone. It’s about<br />
fi nding the balance between comfort, energyeffi<br />
cient solutions and economically-viable<br />
operating solutions.