<strong>MAC10</strong> / <strong>MAC11</strong> / <strong>EFC</strong><br />

Constant pressure and<br />

electronic speed regulators<br />

• <strong>MAC10</strong> / <strong>MAC11</strong><br />

• <strong>EFC</strong>16EU01<br />

• <strong>EFC</strong>35 / <strong>EFC</strong>35G / <strong>EFC</strong>35S<br />

• <strong>EFC</strong>50 / <strong>EFC</strong>80 / <strong>EFC</strong>80C<br />

• <strong>EFC</strong>1P<br />

Above set point limit<br />

Pressure set point<br />

Below set point limit<br />

Time before alarm ALARM!<br />

Measured pressure<br />

Product information - Version 2


Table of contents<br />

Constant pressure regulator <strong>MAC10</strong> . . 4<br />

- Dimensional sketches and technical specifi cations ............ 4<br />

- Voltage regulator <strong>MAC10</strong>MPR .................................... 5<br />

- Pressure transducer MAC XTP ..................................... 5<br />

- Outside air temperature sensor <strong>MAC10</strong> XTT .............. 6<br />

- Cable plans ............................................................. 6-7<br />

Constant pressure regulator <strong>MAC11</strong> . . 8<br />

- Dimensional sketch and technical specifi cations ............. 8<br />

- Pressure transducer (XTP sensor) ................................. 9<br />

- Outside air temperature sensor (XTT sensor) ............. 10<br />

- Bus communication (LON network) ........................... 10<br />

- Cable plans .............................................................. 11<br />

Electronic speed regulators ............ 12<br />

- <strong>EFC</strong>16EU01 - Technical specifi cations ........................ 12<br />

- <strong>EFC</strong>35/<strong>EFC</strong>35G/<strong>EFC</strong>35S - Tech. specifi cations ............ 13<br />

- <strong>EFC</strong>50/<strong>EFC</strong>80/<strong>EFC</strong>80C - Tech. specifi cations .............. 14<br />

Electronic speed regulator for<br />

ventilator units with FC motors ..... 15<br />

- <strong>EFC</strong>1P - Technical specifi cations ............................... 15<br />

For more information<br />

- Visit our website<br />

<strong>MAC11</strong><br />

<strong>MAC10</strong><br />

2<br />

On-demand controlled<br />

<strong>EXHAUSTO</strong> constant pressure and speed regulators are used to<br />

variably regulate <strong>EXHAUSTO</strong> ventilators and air handling units.<br />

The <strong>EFC</strong>16-<strong>EFC</strong>80 voltage regulators variably regulate the speed<br />

of 1 x 230 V <strong>EXHAUSTO</strong> ventilators.<br />

Voltage regulation<br />

Fan<br />

n<br />

Rpm<br />

U<br />

Volt<br />

I<br />

Amp<br />

P 1<br />

kW<br />

P 2<br />

kW<br />

Regulator type<br />

Manual Constant pressure<br />

BESB250-4-1 1400 1x230 0,98 0,22 0,10 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

BESB315-4-1 1400 1x230 2,60 0,45 0,30 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

BESF146-4-1 1400 1x230 0,40 0,10 0,04 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

BESF160-4-1 1400 1x230 0,80 0,19 0,09 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

BESF180-4-1 1400 1x230 1,80 0,35 0,18 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

BESF200-4-1 1400 1x230 2,60 0,53 0,30 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

BESF225-4-1 1400 1x230 3,90 0,75 0,45 <strong>EFC</strong>50 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTV160-4-1 1400 1x230 0,20 0,04 0,01 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTV200-4-1 1400 1x230 0,40 0,07 0,04 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTV250-4-1 1400 1x230 0,80 0,16 0,09 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTV315-4-1 1400 1x230 1,80 0,37 0,25 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTV400-4-1 1400 1x230 2,90 0,60 0,40 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTH160-4-1 1400 1x230 0,20 0,04 0,01 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTH200-4-1 1400 1x230 0,40 0,07 0,04 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTH250-4-1 1400 1x230 0,80 0,16 0,09 <strong>EFC</strong>16 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTH315-4-1 1400 1x230 1,80 0,37 0,25 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

DTH400-4-1 1400 1x230 2,60 0,60 0,40 <strong>EFC</strong>35 <strong>MAC10</strong>+<strong>MAC10</strong>MPR<br />

<strong>MAC10</strong> and <strong>MAC11</strong> constant pressure regulators<br />

<strong>EXHAUSTO</strong> constant pressure regulators <strong>MAC10</strong> and <strong>MAC11</strong> are<br />

the perfect choice for controlling on-demand, energy-optimised<br />

ventilator solutions. They meet the need for low energy consumption,<br />

reliability and the required ventilation requirements.<br />

The <strong>MAC10</strong> and <strong>MAC11</strong> (Multi Application Controller) microprocessor-based<br />

constant pressure regulators are designed for


ventilation with constant pressure & speed regulators<br />

All regulators have a control panel with control knob to variably<br />

adjust the airfl ow as required. The control knob on an<br />

<strong>EFC</strong>12-<strong>EFC</strong>80 control panel also functions as start/stop.<br />

All control panels have a green LED to indicate the ventilator<br />

motor is running.<br />

Frequency regulation<br />

Fan<br />

n<br />

Rpm<br />

U<br />

Volt<br />

I<br />

Amp<br />

P 1<br />

kW<br />

P 2<br />

kW<br />

3<br />

Regulator type<br />

Manual Constant pressure<br />

BESB250-4-1FC 1400 1x230 1,40 0,20 0,18 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESB315-4-1FC 1400 1x230 2,40 0,39 0,37 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESB250-4-1FC 1400 1x230 3,70 0,84 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESB400-4-1FC 1300 1x230 6,80 1,01 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESB500-4-3FC 1700 3x400 6,10 2,30 2,20 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESB500-4-3 1400 3x230D/400Y 5,00/2,90 1,47 1,10 Fixed rpm*<br />

BESF180-4-1FC 1400 1x230 1,90 0,31 0,18 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESF200-4-1FC 1400 1x230 2,40 0,55 0,37 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESF225-4-1FC 1400 1x230 3,70 0,84 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESF250-4-1FC 1400 1x230 9,50 1,47 1,10 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESF280-4-3FC 1400 3x400 6,50 2,55 2,20 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

BESF250-4-3 1400 3x230D/400Y 5,00/2,90 1,47 1,10 Fixed rpm*<br />

BESF280-4-3 1400 3x230D/400Y 9,30/5,40 2,55 2,20 Fixed rpm*<br />

DTV250-4-1FC 1600 1x230 1,40 0,21 0,18 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

DTV315-4-1FC 1600 1x230 2,70 0,44 0,37 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

DTV400-4-1FC 1600 1x230 3,70 0,85 0,75 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

DTV450-4-1FC 1700 1x230 9,40 1,47 1,10 <strong>EFC</strong>1P <strong>MAC10</strong>/<strong>MAC11</strong><br />

* If appropriate, frequency converter<br />

<strong>EFC</strong>16 <strong>EFC</strong>35 <strong>EFC</strong>50 <strong>EFC</strong>80<br />

<strong>EFC</strong>1P<br />

ventilators with FC motors. They can be supplied with outside<br />

air temperature sensors, allowing operation with outside air<br />

temperature compensation.<br />

For single-phase motors without FC use the <strong>MAC10</strong> with<br />

the <strong>MAC10</strong>MPR add-on module. <strong>MAC11</strong> is available with<br />

LonWorks ® – a communication platform for DDC units.<br />

The regulator’s built-in potentiometer can set a minimum<br />

voltage/airfl ow. <strong>EFC</strong>1P is an electronic speed regulator for<br />

<strong>EXHAUSTO</strong> FC motors (motors with frequency converters).<br />

They are used to manually regulate the speed of revolution of<br />

<strong>EXHAUSTO</strong> ventilators which are fi tted to FC motors.<br />

P = maximum power consumption (Watt).<br />

1<br />

P = power rating (Watt), which is the<br />

2<br />

power rating marked on the motor.<br />

BESB box fan<br />

BESF box fan<br />

DTV roof fan<br />

DTH roof fan<br />

BESB box fan<br />

with frequency converter<br />

BESF box fan<br />

with frequency converter<br />

DTV roof fan<br />

with frequency converter<br />

The <strong>MAC10</strong> constant pressure regulators and the <strong>MAC11</strong>,<br />

which can be set to a high or low pressure setting, are wellsuited<br />

to the comfort ventilation of residences and other<br />

indoor environments, such as offi ces, restaurants, etc. The<br />

high and low pressure setting can be made manually, with<br />

help from an external timer, other third-party control system<br />

or via an outside air temperature sensor.


Constant pressure regulator - <strong>MAC10</strong><br />

The <strong>MAC10</strong> controls fan unit operation and maintains the<br />

required pressure.<br />

The <strong>MAC10</strong> offers two pre-set pressures (high/low), so that<br />

ventilation can be adjusted to meet operational requirements.<br />

The high and low pressure settings are set individually in the<br />

constant pressure regulator using a simple menu.<br />

The <strong>MAC10</strong> has a built-in alarm function that automatically<br />

displays a message when the required pressure cannot be<br />

met.<br />

The unit also includes an isolator switch for use with an<br />

external alarm.<br />

The <strong>MAC10</strong> lets the user set the pressure deviation required to<br />

trigger the alarm, as well as how long this deviation can<br />

continue before the alarm is activated.<br />

Type <strong>MAC10</strong><br />

Supply voltage 230 VAC<br />

Recommended operating range 50-500 Pa<br />

Ambient temperature -20ºC to +50ºC<br />

Settings’ range - alarm pressure 0-500 Pa<br />

Settings’ range - alarm time 0-1000 secs.<br />

Settings’ temp. - low -25ºC to 0ºC<br />

Settings’ temp. - high -10ºC to 15ºC<br />

Alarm switch (max. load) Isolator switch: 230 VAC, 8 A, AC1<br />

Ingress protection IP54<br />

4<br />

The constant pressure regulator will continue to operate after<br />

the alarm has been triggered and continue to attempt to<br />

maintain the required pressure.<br />

The <strong>MAC10</strong> can be connected to a thermal circuit breaker<br />

located in the fan motor. Any cut-out of this unit will also<br />

trigger an alarm.<br />

The <strong>MAC10</strong> also has an external start/stop system option and<br />

an override setting to max. airfl ow.<br />

The <strong>MAC10</strong> can be located wherever it is most appropriate<br />

– in a control room or next to the fan unit with a signal to the<br />

control room.<br />

The <strong>MAC10</strong> is supplied with an XTP sensor as standard.


Pressure transducer - MACXTP<br />

The pressure transducer is supplied with plug outlet,<br />

measuring probe and hose.<br />

The pressure transducer measures the current pressure in the<br />

duct system, and the <strong>MAC10</strong> regulates the fan unit's output<br />

in line with the pre-set pressure. The pressure measured in the<br />

duct system can be read on the <strong>MAC10</strong>'s display.<br />

A different pressure transducer to the one provided can be<br />

used, as the value can be changed in the <strong>MAC10</strong>.<br />

Type XTP-sensor<br />

Supply voltage (from MAC)<br />

15 VDC to 38 VDC,<br />

12 VAC to 28 VAC<br />

Operating range 0-500 Pa<br />

Permissible ambient temp. -18ºC to +60ºC<br />

Output signal 0-10 VDC<br />

Accuracy ±3% full scale<br />

Linearity ±2% full scale<br />

Ingress protection IP54<br />

Max. cable length to <strong>MAC10</strong> 80 m shielded cable<br />

Voltage regulator - <strong>MAC10</strong>MPR<br />

The <strong>MAC10</strong> MPR is used for controlling motors without a<br />

built-in control function.<br />

The <strong>MAC10</strong> MPR can be linked directly to the <strong>MAC10</strong>.<br />

Type <strong>MAC10</strong> MPR<br />

Supply voltage 230 VAC, 50 Hz, max. 13 A<br />

Output voltage 25-230 VAC<br />

Ambient temperature -20ºC to +50ºC<br />

Max. load 4 A<br />

Input signal 0-10 VDC<br />

120 x 170 x 59 mm<br />

Size (H x W x D)<br />

See dimensional sketches for<br />

the <strong>MAC10</strong><br />

Ingress protection IP54<br />

5<br />

The pressure transducer has two pressure connections. The<br />

fi rst links to the duct system, where the pressure is to be kept<br />

at a constant level. The second is used as a reference and can<br />

be led to a neutral reference area.<br />

The pressure transducer should be placed appropriately in<br />

relation to the measuring probe and should be easily<br />

accessible.<br />

The <strong>MAC10</strong> MPR has MAX/MIN trimmers (potentiometers) for<br />

setting up the limits for the output voltage.


The outside air temperature sensor - <strong>MAC10</strong>XTT<br />

The MAX10 constant pressure regulator can be connected to<br />

an outside temperature sensor (available as an accessory),<br />

making it possible to operate with outside temperature<br />

compensation. This means that the high setting for pressure<br />

can be lowered if the outside temperature falls. This compensation<br />

continues lineally between the two pre-set temperatures<br />

and pressure (high/low). When the compensation function<br />

is active, it can be read in the <strong>MAC10</strong>'s display.<br />

Type 22K NTC 2% XTT-sensor<br />

Operating range -40ºC to +60ºC<br />

Accuracy ±2% of full scale<br />

80 x 80 x 55 mm<br />

Size (H x W x D)<br />

See dimensional sketches for<br />

MAC XTP<br />

Ingress protection IP54<br />

Max. cable length to <strong>MAC10</strong> 40 m<br />

Cable plans - <strong>MAC10</strong><br />

Fan motor type: DTV/BESB/BESFxxx-4-1<br />

6<br />

The outside air temperature sensor is placed in an appropriate<br />

outside location where it can measure the real outdoor<br />

temperature. The sensor must not be placed so that it can be<br />

affected by external factors that might infl uence the measured<br />

temperature, e.g. sun and wind.<br />

The <strong>MAC10</strong> constant pressure regulator is used for fan units with motors that are equipped with motor power relays (MPR),<br />

frequency converters or single-phase motors set up with the <strong>MAC10</strong> MPR. The cable plans show the default confi guration.<br />

No connection is shown to: an XTT sensor, an external on/off clock, an external mode switch, or an alarm output.<br />

* Not fitted by <strong>EXHAUSTO</strong>


Cable plans – <strong>MAC10</strong><br />

Fan motor type: DTV/BESB/BESFxxx-x-1FC<br />

Fan motor type: BESB/BESFxxx-4-3FC (Omron freq. conv.)<br />

* Not fitted by <strong>EXHAUSTO</strong><br />

7


Constant pressure regulator - <strong>MAC11</strong> with LON communication<br />

<strong>MAC11</strong> controls the Start/Stop of the ventilation fan and<br />

constantly modulates the fan speed to maintain the pre-set<br />

pressure in the entire ductwork system.<br />

<strong>MAC11</strong> offers the possibility of setting two different pressure<br />

levels. The high and low pressure level is adjusted via the<br />

simple menu on the control unit.<br />

<strong>MAC11</strong> has a built-in alarm, which is activated and displayed<br />

when the pre-set pressure cannot be obtained. It is possible<br />

to adjust how large a deviation from the pre-set pressure will<br />

Type <strong>MAC11</strong><br />

Supply voltage 230 VAC<br />

Range 0-500 Pa<br />

Recommended operating range 50-500 Pa<br />

Regulating accuracy 10 Pa<br />

Ambient temperature -20ºC to +50ºC (Display function: 0-50ºC)<br />

Settings’ range - alarm pressure 10-500 Pa<br />

Settings’ range - alarm time 30-600 secs.<br />

Settings’ temp. - low -30ºC to 0ºC<br />

Settings’ temp. - high -10ºC to +20ºC<br />

Alarm contact Isolator switch (max load 230 VAC, 8 A, AC)<br />

Size (H x W x D) 124 x 175 x 95 mm (inkl. control knob)<br />

Ingress protection IP54<br />

Communication interface to LON network with FTT 10A transceiver<br />

Supply voltage for XTP and XTT sensor<br />

8<br />

activate the alarm.<br />

The time of deviation before the alarm is activated can be set<br />

between 30-600 seconds.<br />

The controller will continue to run the ventilation unit during<br />

the alarm period.<br />

The <strong>MAC11</strong> is supplied with an XTP sensor as standard.


Pressure transducer (XTP-sensor)<br />

The XTP pressure transducer is supplied with plug, measuring<br />

probe and hoses. The pressure transducer measures the<br />

current pressure in the duct system, and the <strong>MAC11</strong> regulates<br />

the ventilator’s output in line with the pre-set pressure. The<br />

pressure measured in the duct system can be read on the<br />

<strong>MAC11</strong> display.<br />

Because the pressure sensitivity can be set in the <strong>MAC11</strong>, a<br />

pressure transducer with a different sensitivity than the one<br />

supplied, can be connected.<br />

The pressure transducer has two pressure connections. One<br />

connection links to the duct system, where the required pressure<br />

is to be kept at a constant level. The second is used as a<br />

pressure reference and can be led to a neutral reference area.<br />

The pressure transducer is positioned appropriately in relation to<br />

the measuring probe. It should be easily accessible.<br />

Type XTP-sensor<br />

Supply voltage (from MAC) 24 VAC<br />

Scope of operation 0-500 Pa<br />

Output signal accuracy (in area 50-500 Pa by 20ºC) 2.5% of measured value<br />

Operating temperature range<br />

(-20ºC to +60ºC in relation to 20ºC)<br />

10 Pa<br />

Permissible ambient temperature -20ºC to +60ºC<br />

Ambient temperature 0ºC to 40ºC<br />

Output signal 0-10 V<br />

Settings’ temperature - low -30ºC to 0ºC<br />

Ingress protection IP54<br />

9<br />

The pressure transducer must be positioned vertically as shown<br />

in the diagram. Delivered with 2 m hose.<br />

NB: As the values can be set in the <strong>MAC11</strong>, a pressure<br />

transducer with a maximum sensitivity in the range of 50-500<br />

Pa can be connected.


Outdoor temperature sensor (XTT-sensor)<br />

To be able to compensate for changes in the outdoor<br />

temperature the <strong>MAC11</strong> can be connected to an external<br />

temperature sensor. (Accessory).<br />

The high pressure setting will fall in line with falling outdoor<br />

temperatures. The compensation will be linear between two<br />

pre-set temperatures and pressures (high/low)<br />

Bus communication (LonWorks ® )<br />

LONWORKS ® is a standardised communication system which is<br />

used by most of the major suppliers of automation systems.<br />

The communication between two units using LON communication<br />

is through a four core cable. Two cores supply the power<br />

to the connected units, and two cores are used for<br />

communication.<br />

The LON bus can connect one or more <strong>MAC11</strong> units. The<br />

ventilation units can thus alter their output relative to outdoor<br />

temperature.<br />

65<br />

113<br />

50<br />

10<br />

The outdoor temperature sensor is connected to the <strong>MAC11</strong><br />

via a LON network. Several <strong>MAC11</strong> control units can be<br />

connected to the same outdoor temperature sensor. The<br />

sensor is placed where the actual outdoor temperature can be<br />

measured without influence from wind and sunshine.<br />

Type XTP-sensor<br />

Supply voltage (from MAC) 24 VAC<br />

Operating temperature -45ºC to +70ºC<br />

Output signal accuracy ±1% of measured value<br />

Resolution 0.1ºC<br />

Size (H x B x D) 50 x 113 x 37 mm<br />

Ingress Protection IP54<br />

By using the LON system for communication, the distance<br />

between the temperature sensor and the <strong>MAC11</strong> units will<br />

have no influence on the accuracy of the measuring signal.<br />

With LONWORKS ® the system can be further developed over<br />

time.


Cable plans<br />

The <strong>MAC11</strong> constant pressure regulator is used with ventilators with FC motors. The cable plans show the default configuration.<br />

Connections to an XTT sensor, an external on/off clock, an external mode switch, or an alarm output are not shown.<br />

Fan motor type: DTV/BESB/BESFxxx-4-1FC<br />

Fan motor type: BESB/BESFxxx-4-3FC (Omron freq. conv.)<br />

* Not fitted by <strong>EXHAUSTO</strong><br />

11


<strong>EFC</strong> - Electronic speed regulator<br />

The <strong>EFC</strong> electronic speed regulator has been designed for<br />

variable speed regulation of <strong>EXHAUSTO</strong> fans and air handling<br />

units operating on 1 x 230 V. The <strong>EFC</strong> unit variably regulates<br />

the speed of the motor, making it possible to vary the capacity<br />

of the fan from 25–100 %.<br />

The knob on the speed regulator unit features a built-in on/off<br />

switch and the unit itself has an internal minimum-speed<br />

trimmer.<br />

<strong>EFC</strong>16EU01 – Technical specifications<br />

85<br />

85 32,5<br />

49,9<br />

Type <strong>EFC</strong>16EU01<br />

Voltage 230 VAC<br />

Load Max. 1.5 A<br />

Internal fuse T 1.6 AH<br />

Max. fuse 13 A<br />

Ambient temperature 0-40ºC<br />

Min. output voltage Built-in potentiometer<br />

Ingress protection IP20<br />

Material Thermoplastic ABS<br />

Colour White<br />

Min. opening for installation H 54 x W 68 x D 24 mm<br />

60<br />

70<br />

22 40<br />

12<br />

6,5<br />

12<br />

The regulators are CE marked and EMC certified.<br />

The <strong>EFC</strong> is available in the following models – 16, 35, 50, 80<br />

– and in a range of different designs. The <strong>EFC</strong>16 can be built<br />

into walls.<br />

RD11258-01<br />

Ventilator/fan<br />

2-conductor operation<br />

3-conductor operation<br />

2-conductor<br />

operation<br />

3-conductor<br />

operation<br />

BESB250-4-1 X<br />

BESF146-4-1 X<br />

BESF160-4-1 X<br />

DTV160-4-1 X<br />

DTV200-4-1 X<br />

DTV250-4-1 X<br />

DTH160-4-1 X<br />

DTH200-4-1 X<br />

DTH250-4-1 X


102<br />

<strong>EFC</strong>35 / <strong>EFC</strong>35G / <strong>EFC</strong>35S – Technical specifications<br />

74<br />

48,5<br />

Type <strong>EFC</strong>35 / <strong>EFC</strong>35G <strong>EFC</strong>35S<br />

Voltage 230 VAC 230 VAC<br />

Load Max. 3.5A Max. 3.5A<br />

Internal fuse T 4 AH T 4 AH<br />

Max. fuse 13 A 13 A<br />

Ambient temperature 0-35ºC 0-35ºC<br />

Min. output voltage<br />

Built-in<br />

potentiometer<br />

Built-in<br />

potentiometer<br />

Ingress protection IP20 IP44<br />

Material Thermoplastic ABS Thermoplastic ABS<br />

Colour<br />

White (<strong>EFC</strong>35) /<br />

grey (<strong>EFC</strong>35G)<br />

Grey<br />

67<br />

52<br />

13<br />

11<br />

RD11262-01<br />

<strong>EFC</strong>35S dimensions:<br />

Height: 120 mm<br />

Width: 80 mm<br />

Depth without knob: 55 mm<br />

Depth with knob: 77 mm<br />

Ventilator/fan<br />

2-conductor<br />

operation<br />

2-conductor operation<br />

3-conductor operation<br />

3-conductor<br />

operation<br />

BESB250-4-1 X<br />

BESB315-4-1 X<br />

BESF146-4-1 X<br />

BESF160-4-1 X<br />

BESF180-4-1 X<br />

BESF200-4-1 X<br />

DTV160-4-1 X<br />

DTV200-4-1 X<br />

DTV250-4-1 X<br />

DTV315-4-1 X<br />

DTV400-4-1 X<br />

DTH160-4-1 X<br />

DTH200-4-1 X<br />

DTH250-4-1 X<br />

DTH315-4-1 X<br />

DTH400-4-1 X


200<br />

<strong>EFC</strong>50 / <strong>EFC</strong>80 / <strong>EFC</strong>80C - Technical specifi cations<br />

120<br />

<strong>EFC</strong>50 / <strong>EFC</strong>80 / <strong>EFC</strong>80C<br />

Type <strong>EFC</strong>50 <strong>EFC</strong>80 <strong>EFC</strong>80C<br />

Voltage 230 VAC 230 VAC 230 VAC<br />

Load Max. 5 A Max. 8 A Max. 8 A<br />

Internal fuse T 5 AH T 8 AH T 8 AH<br />

Max. fuse 13 A 13 A 13 A<br />

Ambient<br />

temperature<br />

Min. output<br />

voltage<br />

Max. output<br />

voltage<br />

75<br />

0-35ºC 0-35ºC 0-35ºC<br />

Built-in<br />

potentiometer<br />

Built-in<br />

potentiometer<br />

93<br />

Built-in<br />

potentiometer<br />

Built-in<br />

potentiometer<br />

2-speed operation Via external unit Via external unit<br />

Ingress protection IP32 IP32 IP22<br />

Material<br />

Thermoplastic<br />

ABS<br />

Thermoplastic<br />

ABS<br />

Colour White White White<br />

RD11263-01<br />

240<br />

Built-in<br />

potentiometer<br />

Built-in<br />

potentiometer<br />

Run by built-in<br />

timer<br />

Thermoplastic<br />

ABS<br />

14<br />

120<br />

Ventilator/fan<br />

2-conductor<br />

operation<br />

2-conductor operation<br />

3-conductor operation<br />

100<br />

118<br />

3-conductor<br />

operation<br />

BESB250-4-1 X<br />

BESB315-4-1 X<br />

BESF146-4-1 X<br />

BESF160-4-1 X<br />

BESF180-4-1 X<br />

BESF200-4-1 X<br />

BESF225-4-1 X<br />

DTV160-4-1 X<br />

DTV200-4-1 X<br />

DTV250-4-1 X<br />

DTV315-4-1 X<br />

DTV400-4-1 X<br />

DTH160-4-1 X<br />

DTH200-4-1 X<br />

DTH250-4-1 X<br />

DTH315-4-1 X<br />

DTH400-4-1 X<br />

RD11264-01


<strong>EFC</strong>1P - Electronic speed regulator<br />

For ventilators with fi tted <strong>EXHAUSTO</strong> FC motors.<br />

Control panel for fans with FC motor (dimensions in mm)<br />

<strong>EFC</strong>1P – Technical specifi cations<br />

Type <strong>EFC</strong>16EU01<br />

Ambient temperature -20°C to +40°C<br />

Min. output voltage Built-in potentiometer<br />

Ingress protection IP20<br />

Material Thermoplastic ABS<br />

Colour White<br />

Min. opening for installation H 53 x W 53 x D 56 mm<br />

<strong>EFC</strong>1P – Cable plans<br />

The supply cable must be dimensioned in accordance with<br />

applicable regulations and legislation. The conditions at the<br />

installation location, including temperature and the path of<br />

the cable must be taken into consideration.<br />

The FC motor has over current and overheating protection.<br />

The motor needs no additional protection. The fault indication<br />

output of the motor cannot be used for external fault<br />

reporting, as it is used with the <strong>EFC</strong>1P.<br />

When installing multiple single-phase ventilators with FC<br />

motors in the same network with a shared neutral conductor,<br />

special requirements apply to the dimensioning of this<br />

conductor, as the current is not a pure sine wave.<br />

For example, if three single-phase ventilators with FC motors<br />

are installed and divided between three phases, the current in<br />

the neutral conductor is equal to that of the three ventilators<br />

combined.<br />

If you are fi tting fan units to an existing installation, make sure<br />

that the neutral conductor can cope with the resultant load.<br />

15<br />

The <strong>EFC</strong>1P speed regulator control panel<br />

controls the frequency converter in the<br />

FC motor. The linear 0-10 scale sets the<br />

ventilator’s speed of revolution.<br />

The control panel contains a potentiometer<br />

with a circuit breaker built into the switch.<br />

Functions:<br />

1. Start/stop and speed setting of the ventilator (potentiometer<br />

with built-in on/off switch)<br />

2. Operating LED (green) for the fan motor.<br />

3. Alarm LED (red) to indicate motor overheating or over current.<br />

1<br />

2<br />

3<br />

5509019-01<br />

6 x 0.6 mm<br />

E 1*<br />

7 x 0.6 mm<br />

Simplifi ed diagram<br />

*E 1 connection box<br />

(not supplied by <strong>EXHAUSTO</strong>)<br />

For more information regarding electrical connection, refer to<br />

the <strong>EFC</strong>1P product instructions.<br />

Earth leak circuit breakers:<br />

Only Type-A earth-leakage circuit breakers, in accordance<br />

with IEC 755, Amendment 2, can be used with single-phase<br />

ventilators with FC motors. These circuit breakers also break<br />

the circuit when DC current (pulsating DC) is detected.<br />

These circuit breakers are marked with:<br />

Only Type-B earth-leakage circuit breakers<br />

can be used with three-phase ventilators<br />

with FC motors.<br />

These circuit breakers are marked:<br />

See BESB product information.


3003151 - 04.2011 - We reserve the right to make changes without notice.<br />

<strong>EXHAUSTO</strong> - indoor air quality<br />

makes a difference<br />

Technologies<br />

<strong>EXHAUSTO</strong> provides three technologies within<br />

heat recovery, cross-fl ow heat exchangers,<br />

rotary heat exchangers and counter fl ow heat<br />

exchangers. The three technology platforms<br />

have their own unique advantages and<br />

applications.<br />

Our innovation is aimed at energy optimisation<br />

in all regards - we develop products<br />

that set the standard for future energy<br />

requirements.<br />

<strong>EXHAUSTO</strong> VENTILATION Ltd.<br />

Unit 1, Pelham Court<br />

Pelham Place<br />

Broadfield - Crawley<br />

West Sussex -�RH11 9SH<br />

System solutions<br />

<strong>EXHAUSTO</strong> consistently develops system<br />

solutions that support professional project<br />

planning of ventilation for residences, offi ces<br />

and schools. Every single system meets both<br />

regulatory requirements and building owners’<br />

needs and requirements.<br />

The individual systems are naturally supported<br />

by the <strong>EXHAUSTO</strong> products best suited to<br />

each and every installation.<br />

Tel. 01293 511555<br />

Fax 01293 533888<br />

info@exhausto-ventilation.co.uk<br />

www.exhausto-ventilation.co.uk<br />

Indoor air quality competences<br />

<strong>EXHAUSTO</strong> is part of VKR Holding A/S,<br />

incorporated in the company’s ventilation and<br />

indoor climate business area. VKR Holding A/S<br />

aims to provide customers with innovative and<br />

energy-effi cient solutions to ensure an excellent<br />

indoor climate in new and existing buildings.<br />

To read more visit www.vkr-holding.com<br />

At <strong>EXHAUSTO</strong>, we consistently strive to<br />

improve the performance of our products, to<br />

enhance not only indoor air quality but also the<br />

global climate – benefi ting everyone. It’s about<br />

fi nding the balance between comfort, energyeffi<br />

cient solutions and economically-viable<br />

operating solutions.