<strong>Rittal</strong> <strong>RiLine</strong> <strong>NH</strong><br />
Technical information<br />
<strong>NH</strong> on-load isolator<br />
Page 10 <strong>–</strong> 13<br />
Hole size<br />
Size 00 (SV 9344.000 <strong>–</strong> 9344.050) Size 1 (SV 9344.100 <strong>–</strong> 9344.150)<br />
Size 2 (SV 9344.200 <strong>–</strong> 9344.250)<br />
Size 3 (SV 9344.300 <strong>–</strong> 9344.350)<br />
25<br />
12.5<br />
ø7<br />
66<br />
40<br />
75<br />
13<br />
97<br />
Busbar adaptor 100 mm<br />
for <strong>NH</strong> on-load isolator sizes 1 to 3, for mounting plate assembly<br />
Page 15<br />
100<br />
100<br />
Gr. A<br />
1 57 mm<br />
2 65 mm<br />
3 80 mm<br />
A A<br />
3<br />
4<br />
1<br />
164<br />
ø 5,5<br />
25<br />
25<br />
5<br />
ø11<br />
6<br />
A<br />
17 20 Nm<br />
19 30 Nm<br />
2,5 Nm TX 25<br />
Size A<br />
1 150<br />
2 166<br />
3 195<br />
Assembly instructions Note:<br />
For mounting <strong>NH</strong> on-load <strong>isolators</strong> size 1 to 3<br />
17/19<br />
(see page 11 <strong>–</strong> 13) on busbar systems with<br />
100 mm bar centre distance, an additional<br />
TX 25<br />
mounting hole (d = 5.5 mm) must be drilled in<br />
the respective isolator chassis as shown in the<br />
assembly instructions, stage 1 opposite. <strong>The</strong><br />
busbar adaptor is then mounted on the busbar<br />
using M10 screws, see stages 2 and 3, and the<br />
isolator is secured onto the adaptor as shown in<br />
2 M10<br />
stages 4 to 6.<br />
4<br />
22 <strong>Rittal</strong> <strong>RiLine</strong> <strong>NH</strong>