[21 °C]<br />
<strong>GEA</strong> Heat Exchangers / HVAC Systems<br />
Lovely and flexible | Fan Coil Units<br />
<strong>GEA</strong> <strong>Flex</strong>-Geko ®<br />
Solutions for all demands | Basic and Comfort<br />
32 dB(A)
Unlike radiators and classical flat radiators, fan coil units not<br />
only can heat rooms, but can also cool and ventilate them.<br />
With 2-litre units, seasonal switch-over from heating to cooling<br />
operations is possible, and vice-versa (by reversing the medium<br />
supply). The 4-litre units additionally offer connections for heat-<br />
ing and cooling circulation systems, and therefore allow spon-<br />
taneous change-over between the modes of operation.<br />
Fan coil units actively direct the air to be treated through the<br />
heat exchanger, with especially effective heating or cooling. They<br />
bring room air to the desired temperature faster and operate<br />
with smaller heating or cooling surfaces. Their enhanced heat<br />
transfer enables lower feed temperatures during heating, and<br />
higher feed temperatures during cooling. This minimises losses<br />
and saves energy between the boiler or the chiller and the final<br />
unit.<br />
<strong>GEA</strong> <strong>Flex</strong> Fan Coil Units<br />
Heating, cooling, and ventilating –<br />
fast and efficiently<br />
A choice of fan speeds, as well as valves to regulate the flow vol-<br />
ume, enable flexible control of unit output. Adjustable air-outlet<br />
grills, in addition, assure uniform distribution of temperature-<br />
controlled air in the room. Comfortable climate-control solution:<br />
VDI 6022 (D)<br />
Tested room-air hygiene<br />
Seal of hygiene<br />
SWKI VA<br />
104-01 (CH)<br />
Tested by ILH BERLIN<br />
Heating and cooling in one unit<br />
Assuring desired room temperature with smaller<br />
units<br />
Energy saving with lower feed temperatures<br />
during heating, and with higher temperatures for<br />
cooling<br />
<strong>Flex</strong>ible control<br />
Recirculated-air units in accordance with VDI<br />
6022<br />
2 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Our models in the Basic and Comfort Editions<br />
The right version for<br />
every requirement<br />
The <strong>GEA</strong> <strong>Flex</strong> fan coil units are available in the Basic and Comfort<br />
Editions. Both of these variations are based on the same<br />
equipment platform, and employ this platform with various system<br />
components. This enables numerous equipment configurations.<br />
Purity and timeless design – the Basic variation<br />
The Basic Edition model, with modest grey-white enclosure, contains<br />
high-quality technology and offers (according to version)<br />
connections for hot and/or cold water, a three-speed fan, and an<br />
air filter. Various valve types allow coordinated and precise heating<br />
and cooling. With its extremely user-friendly control system,<br />
the <strong>GEA</strong> <strong>Flex</strong> fan coil unit is therefore the perfect starter model<br />
for comfortable, decentral climate control of your rooms.<br />
Greater expectations in many variations –<br />
the Comfort Edition<br />
The Comfort Edition of the <strong>GEA</strong> <strong>Flex</strong> offers additional functions<br />
and more features. It enables climate control of rooms in mixedair<br />
operation, and treatment of the air with finer filters. According<br />
to the requirements, Comfort units offer hot and/or cold water connections.<br />
They can be equipped with additional electrical heating,<br />
and with an integrated direct evaporator – which allows a combination<br />
with outdoor split-climate units. The enclosure is designed<br />
for various air-intake and -outlet variations, and a light-grey band<br />
makes the unit optically even slimmer.<br />
Installation sizes and diversity of performance<br />
Both <strong>GEA</strong> <strong>Flex</strong> variants, Basic and Comfort, are available in 8 installation<br />
sizes with a height beginning at 504 mm, and a uniform<br />
depth of 240 mm. The width will vary according to output,<br />
between 840 and 1,890 mm. The 8 unit sizes allow a selection<br />
that optimally matches the required output. The heating and<br />
cooling output ratings lie between 1 and 20 kW*. The circulating<br />
air volume coordinated to these output ratings varies between<br />
150 and 1,800 m³/h.<br />
* Heating: pumped hot water, 70/50°C, tL1 +20°C<br />
* Cooling: pumped cold water, 6/12°C, tL1 +27°C, 46% relative humidity<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
The basic edition of the <strong>GEA</strong> <strong>Flex</strong> fan coil unit offers<br />
reliable technology for many applications. This starter unit<br />
is well suited for user-friendly heating and/or cooling, and<br />
can be combined with various accessory components.<br />
The Comfort Edition, with its distinctive light-grey band,<br />
can climate-control rooms in mixed-air operation as well. It<br />
can be equipped with an additional electrical heater if<br />
required. Its various air-intake and -outlet directions<br />
guarantee flow-optimised airflow routing for all applications.<br />
3
Satisfies virtually all requirements:<br />
<strong>Flex</strong>ible setup and installation variations<br />
Integration possible behind walls or above<br />
suspended ceilings<br />
The <strong>GEA</strong> MATRIX control system, adapted to<br />
the required functionalities<br />
Integration into the building-services management<br />
system via various interfaces<br />
Combination with other fan coil units or <strong>GEA</strong><br />
products<br />
Equipped for virtually every use<br />
With <strong>GEA</strong> <strong>Flex</strong> fan coil units, you can<br />
flexibly plan for every application<br />
As a result of their modular concept, <strong>GEA</strong> <strong>Flex</strong> fan coil units<br />
can be employed for many and various applications. These<br />
models are effective with wall or ceiling installation. They<br />
function highly satisfactorily on a stand-alone basis with en-<br />
closure, or can be mounted virtually invisibly as base units,<br />
with the required air outlets, behind a wall or above a sus-<br />
pended ceiling. The <strong>GEA</strong> MATRIX control system, integrated<br />
as desired, adapts to each and every functionality. The opera-<br />
tor control units – with or without integrated timer switches<br />
– provide the interface to the user. The control units can be in-<br />
stalled in the units themselves, or externally.<br />
<strong>Flex</strong> units with primary-air connection can be easily combined<br />
with a central ventilation system. The control interfaces likewise<br />
allow uncomplicated integration into the building-services man-<br />
agement system.<br />
<strong>GEA</strong> <strong>Flex</strong> fan coil units heat, cool, and ventilate offices, sales<br />
rooms, and public facilities. Prominent hotel chains use them<br />
gladly owing to their quiet and reliable operation. With their<br />
cost-effective operation and flexible application possibilities,<br />
<strong>GEA</strong> <strong>Flex</strong> fan coil units set standards for advanced climate-con-<br />
trol solutions.<br />
4 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Wall and ceiling models<br />
Basic Edition<br />
Only recirculated-air operation<br />
Basic model shown here:<br />
– without enclosure<br />
– ceiling version<br />
– four-pipe system<br />
– valves mounted<br />
Wall and ceiling models<br />
Comfort Edition<br />
Recirculated- or mixed-air operation<br />
Basic mixed-air model shown here:<br />
– without enclosure<br />
– wall version<br />
– four-pipe system<br />
– valves mounted<br />
Already with the Basic Edition of <strong>GEA</strong><br />
<strong>Flex</strong> fan coil units, the most common re-<br />
quirements for climate control of rooms<br />
can be quietly and reliably satisfied.<br />
These robust units are highly effective<br />
for typical flush-mounted applications.<br />
The Basic Edition has been designed for<br />
heating or cooling in recirculated-air<br />
mode. It is effective for all applications for<br />
which a standard flush-mounted situation<br />
exists: for example, under windows. The<br />
horizontal ceiling installation is ideally<br />
suited, for example, for shops, workshops,<br />
and other rooms where floor space is at a<br />
premium.<br />
The Comfort Edition of <strong>GEA</strong> <strong>Flex</strong> fan coil<br />
units satisfies requirements, for example,<br />
in which mixed-air options are desired –<br />
or where quiet heating and cooling are ex-<br />
pected. They are also ideally suited for<br />
cases in which exceptional installation sit-<br />
uations prevail.<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
The many possible intake- and outlet-air<br />
combinations, and the extremely quiet<br />
fans, mean that Comfort Edition models<br />
are something special. The possibility of<br />
ordering these models with mixed-air op-<br />
eration, and/or with electrical heating, ex-<br />
pands their application spectrum. In ad-<br />
dition, the great diversity of accessories<br />
and the availability of various control<br />
modules all mean that the Comfort Edi-<br />
tion satisfies practically all situations.<br />
5
Whether at home, at work, or in a hotel: <strong>GEA</strong> fan coil units<br />
reliably assure feel-good room climate. High-performance fans<br />
take the room quickly to the desired temperature, and quietly<br />
maintain it at the required level.<br />
Basic or Comfort > the requirement decides<br />
[One equipment platform] [8 installation<br />
sizes] [2- and 4-pipe systems]<br />
[150 – 1,800 m³/h] [1 – 20 kW]<br />
[Heating, cooling, and ventilation]<br />
With high-performance functions for feel-good climate<br />
6 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
<strong>GEA</strong> <strong>Flex</strong> Fan Coil Units<br />
Enclosures<br />
1<br />
5 6<br />
7 8<br />
4<br />
1<br />
4<br />
5<br />
6<br />
7<br />
8<br />
Air intake on the narrow side; air outlet on the narrow<br />
side. For recirculated-air operation with wall or ceiling<br />
installation. Free air suction required approx. 10 cm<br />
from the building. Without feet.<br />
Air intake on the narrow side; air outlet on the front<br />
side. For recirculated-air operation with wall or ceiling<br />
installation. Free air suction required approx. 10 cm<br />
from the building. Without feet.<br />
Air intake on the front side; air outlet on the narrow<br />
side. For recirculated-air operations with wall, ceiling,<br />
or floor installation. For setup open in the room: with<br />
optional back wall or narrow-side cover panel.<br />
Intake-air opening with grill integrated into the<br />
enclosure. Without feet.<br />
Air intake on the front side; air outlet on the front side.<br />
For recirculated-air operations with wall, ceiling, or<br />
floor installation. Intake-air opening with grill<br />
integrated into the enclosure. Without feet.<br />
Air intake on the front side; air outlet on the narrow<br />
side. For recirculated-air operations with wall, ceiling,<br />
or floor installation. With feet – intake-air opening<br />
without grill.<br />
Air intake on the front side – air outlet on the front<br />
side. For recirculated-air operations with wall, ceiling,<br />
or floor installation. With feet. Intake-air opening<br />
without grill.<br />
Air intake on the front side – air outlet on the narrow<br />
side. For recirculated- or mixed-air operations with<br />
wall, ceiling, or floor installation. With feet. Mixed-air<br />
intake opening integrated with grill. Intake of outside<br />
air on the rear side, without grill.<br />
Air intake on the front side – air outlet on the front<br />
side. For recirculated- or mixed-air operations with<br />
wall, ceiling, or floor installation. With feet. Mixed-air<br />
intake opening integrated with grill. Intake of outside<br />
air on the rear side, without grill.<br />
1 4<br />
5 6 7 8<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
7
Comprehensive control possibilities:<br />
Control functions in various expansion stages<br />
Bus interfaces to other equipment units<br />
Plug-and-play functionality<br />
Energy-optimised equipment operation<br />
Equipment ready to operate<br />
Highly competent service<br />
Global add-on modules<br />
LON interface<br />
Service tool<br />
<strong>GEA</strong> MATRIX – intelligent control technology<br />
Just the right turn for<br />
the right room climate<br />
If requested as option, the proven <strong>GEA</strong> MATRIX control unit will<br />
be integrated into the <strong>GEA</strong> <strong>Flex</strong> fan coil units at the factory. Your<br />
benefit: only completely tested equipment will be supplied to<br />
your construction site.<br />
<strong>GEA</strong> MATRIX is available in configuration levels 500, 2000, 3000,<br />
or 4000, with adaptation to the various possible applications. A version<br />
can be supplied for hotel applications, for example: as well as<br />
a Basic version for cost-optimised budgets.<br />
Most of the versions are provided as default with the two-cable <strong>GEA</strong><br />
MATRIX dual-cable bus system, through which all <strong>GEA</strong> MATRIX<br />
units can communicate with each other. As a result, it is simple to<br />
implement daytime and nighttime switching actions, or to control<br />
pumps and collect error messages at a single point. <strong>GEA</strong> MATRIX<br />
can also be connected to higher-level bus systems.<br />
In addition, <strong>GEA</strong> MATRIX assures energy-optimized operation of<br />
<strong>GEA</strong> <strong>Flex</strong> fan coil units. A coordinated switch-over function, for<br />
example, prevents heating and cooling circulation systems from<br />
working against each other. By means of the summer compensation<br />
function, <strong>GEA</strong> MATRIX takes outside-temperature influences<br />
into account and prevents energy-intensive climate control.<br />
Hardware and software are developed entirely at <strong>GEA</strong>. As a result<br />
of close collaboration in the company, <strong>GEA</strong> engineers can systematically<br />
adjust the control system to match every component – and<br />
in turn optimally exploit the possibilities of the fan coil units. <strong>GEA</strong><br />
support staff also profit from this arrangement by being able to<br />
quickly and expertly react in case of any questions.<br />
Numerous additional global modules are available as function expansions<br />
of the standard local connections. Examples here are: intra-group<br />
<strong>GEA</strong> MATRIX control units and clock modules, modules<br />
for activation control of exhaust-air fans and chillers, expansion of<br />
analogue or digital input and output signals, 0 … 10-V outputs for<br />
valves, and integration into a LON bus system in accordance with<br />
the LonWorks standard.<br />
Starting with MATRIX 2000, all modules can be simply integrated<br />
via the MATRIX.Net bus system. In addition, the service tools<br />
MATRIX.PDA and MATRIX.PC can be used for parameterisation,<br />
facility commissioning, maintenance, and data recording from the<br />
MATRIX control system.<br />
8 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Control unit for MATRIX 500 Control unit for MATRIX 2000<br />
MATRIX OP5<br />
– Enclosure without display, pure white<br />
– Recirculated-air mode,<br />
IP 20 protection class<br />
– Desired-temperature setting<br />
– Fan-speed selection for permanent duty<br />
– Button for temperature-reduction mode<br />
– LED for operation/malfunction/ext. influence<br />
– Integrated room-temperature sensor<br />
Control units for MATRIX 3000 and MATRIX 4000<br />
MATRIX OP30 without buttons<br />
MATRIX OP31 with temp.-reduction button<br />
– Enclosure without display, pure white<br />
– Recirculated-air, IP 20 protection class<br />
– Desired-temperature setting<br />
– Fan-speed selection switch for permanent /<br />
automatic operation<br />
– LED for operation/malfunction/ext. influence<br />
– Integrated room-temperature sensor<br />
MATRIX OP50 without clock<br />
MATRIX OP51 with clock<br />
– Enclosure without display, pure white<br />
– Recirculated-air / mixed-air modes of operation<br />
– IP 20 enclosure protection class<br />
– Operation by rotary navigator<br />
– LCD display with plain text<br />
– Status report by pictograms<br />
– Integrated room-temperature sensor<br />
<strong>GEA</strong> thermostat / compact switch units<br />
MATRIX OP21<br />
Same as the OP5 control unit, but with:<br />
– Fan-speed selection switch for<br />
permanent / automatic operation<br />
– MATRIX.Net data bus<br />
Network connection for MATRIX<br />
add-on modules via OP21 control unit<br />
MATRIX OP44<br />
Same as the OP31 control unit, but with:<br />
– Selection switching for heating / cooling /<br />
automatic operation<br />
– Selection switching for recirculated-air /<br />
mixed-air modes of operation<br />
All units without display. Protective hood as<br />
option.<br />
MATRIX.IR infrared remote control unit<br />
– Functions as for the OP44 control unit, but:<br />
Without operational/malfunction reports<br />
Without report of external influence<br />
Without integrated room sensor<br />
– Black enclosure, similar to RAL 9004<br />
– LCD display, 45 x 30 mm<br />
– Effective range = approx. 20 m<br />
CMS / CMT / CET series: extremely simple control units are also available for minimal control-function requirements<br />
(for systems based on pumped hot water and pumped cold water).<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
9
Overview of systems and performance ratings <strong>GEA</strong> <strong>Flex</strong>-Geko<br />
Air Heating Cooling<br />
Basic Edition Installed sizes flow rating rating<br />
Fan speeds 1 - 2 - 3 1 ... 8 in m 3 / h in kW in kW<br />
Recirculated air Typ Performance rating min | max min | max min | max<br />
Pumped hot water / pumped cold water<br />
Heating with pumped hot water U0W 1<br />
180 | 1800 2.0 | 19.5<br />
Cooling with pumped cold water UW0 1<br />
180 | 1800 1.1 | 10.7<br />
Cooling with pumped cold water or heating<br />
with pumped hot water (change over) UWC<br />
Cooling with pumped cold water and heating<br />
with pumped hot water (4-pipe system) UWW<br />
See pages 12 and 13 for the output ratings in the individual fan-speed levels.<br />
Heating with pumped hot water: 70/50°C, tL1 +20°C;<br />
cooling with pumped cold water: 6/12°C, tL1 +27°C, 46% relative humidity; refrigerant: R410A, to +10°C ·<br />
See page 11 for data on the sound emission<br />
*The “U”s in the “Type” column above stand for recirculated air. “M” stands for mixed air<br />
1<br />
1<br />
180 | 1800 2.0 | 19.5 1.1 | 10.7<br />
175 | 1780 0.7 | 7.0 1.1 | 9.1<br />
Air Heating Cooling<br />
Comfort-Edition Installed sizes flow rating rating<br />
Fan speeds 1 - 2 - 3 1 ... 8 in m 3 / h in kW in kW<br />
Recirculated air / mixed air Typ Performance rating min | max min | max min | max<br />
Pumped hot water / pumped cold water<br />
Heating with pumped hot water U0W / M0W 1<br />
150 | 1820 1.7 | 19.6<br />
Cooling with pumped cold water UW0 / MW0 1<br />
150 | 1820 1.0 | 10.8<br />
Cooling with pumped cold water or heating<br />
with pumped hot water (change over)<br />
UWC / MWC<br />
Cooling with pumped cold water and heating<br />
UWW / MWW<br />
with pumped hot water (4-pipe system)<br />
Pumped hot water / pumped cold water / electrical heating<br />
150 | 1820 1.7 | 19.6 1.0 | 10.8<br />
145 | 1800 0.6 | 7.2 1.0 | 9.1<br />
Electrical heating U0E / M0E 1<br />
270 | 1820 2.1 | 12.4<br />
Heating with pumped hot water + 2.3 | 18.1<br />
U0F / M0F 1<br />
220 | 1820<br />
electrical booster heating<br />
0.9 | 4.1<br />
Cooling with pumped cold water or heating 2.3 | 18.1<br />
UWB / MWB 1<br />
220 | 1820<br />
with pumped hot water + electrical heating<br />
0.9 | 4.1<br />
Cooling with pumped cold water and<br />
heating with electrical heating<br />
1.2 | 9.6<br />
UWE / MWE 1<br />
220 | 1820 0.9 | 4.1 1.2 | 9.6<br />
Cooling and heating with cold and hot water UWF 0.9 | 7.2<br />
1<br />
215 | 1800<br />
(4-pipe system) + electrical heating (only recirculated air)<br />
0.9 | 4.1<br />
Refrigerant: R410A / pumped hot water<br />
1.2 | 7.6<br />
Cooling with R410A refrigerant UD0 / MD0 1<br />
270 | 1820 1.2 | 7.1<br />
Cooling with R410A refrigerant and<br />
heating with pumped hot water<br />
1<br />
1<br />
UDW / MDW 1<br />
270 | 1800 1.0 | 7.2 1.0 | 4.9<br />
10 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
<strong>GEA</strong> <strong>Flex</strong>-Geko Noise emission in dB(A)<br />
Basic Edition – installed sizes 1 2 3 4 5 6 7 8<br />
Fan speeds 1 - 2 - 3<br />
At air flow of: Fan speed 1 m 3 / h 180 190 330 380 400 520 570 590<br />
Acoustic power level Lw 33 33 33 35 35 36 36 36<br />
Acoustic pressure level* Lp * 24 24 24 26 26 27 28 27<br />
At air flow of: Fan speed 2 m 3 / h 260 290 490 540 560 740 790 940<br />
Acoustic power level Lw 41 43 44 44 44 44 45 45<br />
Acoustic pressure level* Lp * 33 34 35 35 35 35 36 37<br />
At air flow of: Fan speed 3 m 3 / h 490 520 860 960 990 1310 1410 1800<br />
Acoustic power level Lw 57 57 59 60 60 62 62 63<br />
Acoustic pressure level* Lp * 48 49 51 51 51 54 53 54<br />
Comfort Edition – installed sizes 1 2 3 4 5 6 7 8<br />
Fan speeds 1 - 2 - 3 - 4 - 5<br />
At air flow of: Fan speed 1 m 3 / h 150 160 280 290 300 430 460 590<br />
Acoustic power level Lw < 30 < 30 30 < 30 < 30 33 33 34<br />
Acoustic pressure level* Lp * 21 < 20 21 20 < 20 24 24 25<br />
At air flow of: Fan speed 3 m 3 / h 270 280 470 490 520 750 770 970<br />
Acoustic power level Lw 42 42 43 41 42 46 46 46<br />
Acoustic pressure level* Lp * 33 33 34 32 34 38 38 37<br />
At air flow of: Fan speed 5 m 3 / h 530 540 890 990 1010 1310 1420 1820<br />
Acoustic power level Lw 58 58 59 58 59 62 62 61<br />
Acoustic pressure level* Lp * 50 49 51 50 51 54 53 53<br />
* Conditions for measurement of acoustic pressure level Lp:<br />
Measuring interval = 5 m. Room volume = 100 m³. Reverberation period = 0.5 s. Directional factor = 4 (quarter-sphere sound emission)<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
11
Performance ratings Basic Edition<br />
Basic Edition Installed size 1 2 3 4 5 6 7 8<br />
Capacity stage 1 Min. fan-speed level = 1<br />
2 pipes Air flow m 3 / h 180 190 330 380 400 520 570 590<br />
Heating U0W / UWC kW 2.0 2.3 3.6 4.3 4.7 5.6 6.3 6.8<br />
Cooling UW0 / UWC kW 1.1 1.2 1.9 2.4 2.7 3.0 3.4 3.7<br />
4 pipes Air flow m 3 / h 175 185 325 370 390 515 565 585<br />
Heating UWW kW 0.7 1.1 1.8 2.3 2.5 3.2 3.7 3.9<br />
Cooling UWW kW 1.1 1.2 2.0 2.4 2.5 3.3 3.7 3.8<br />
Max. fan-speed level = 3<br />
2 pipes Air flow m 3 / h 490 520 860 960 990 1310 1410 1800<br />
Heating U0W / UWC kW 3.8 4.6 6.7 7.9 8.8 10.5 11.6 14.3<br />
Cooling UW0 / UWC kW 1.9 2.3 3.4 4.1 4.6 5.2 5.9 7.2<br />
4 pipes Air flow m 3 / h 485 515 850 945 975 1300 1395 1780<br />
Heating UWW kW 1.4 1.9 3.0 3.7 4.2 5.3 5.9 7.1<br />
Cooling UWW kW 1.9 2.2 3.5 4.2 4.4 5.7 6.3 7.2<br />
Basic Edition Installed size 1 2 3 4 5 6 7 8<br />
Capacity stage 2 Min. fan-speed level = 1<br />
2 pipes Air flow m 3 / h 175 185 325 370 390 515 565 585<br />
Heating U0W / UWC kW 2.2 2.6 4.2 5.0 5.4 6.7 7.4 7.9<br />
Cooling UW0 / UWC kW 1.2 1.5 2.3 2.8 3.2 3.5 4.1 4.5<br />
4 pipes Air flow m 3 / h 170 185 310 345 370 500 545 570<br />
Heating UWW kW 0.9 1.2 1.9 2.2 2.5 3.0 3.4 3.7<br />
Cooling UWW kW 1.1 1.4 2.1 2.6 2.9 3.3 3.7 4.1<br />
Max. fan-speed level = 3<br />
2 pipes Air flow m 3 / h 485 515 850 945 975 1300 1395 1780<br />
Heating U0W / UWC kW 4.7 5.6 8.5 9.9 10.8 13.1 14.6 17.9<br />
Cooling UW0 / UWC kW 2.4 3.1 4.4 5.4 6.0 6.8 7.7 9.6<br />
4 pipes Air flow m 3 / h 470 505 815 890 920 1255 1350 1700<br />
Heizen UWW kW 1.6 2.2 3.3 3.9 4.4 5.1 5.8 7.0<br />
Cooling UWW kW 2.2 2.9 4.2 5.0 5.6 6.4 7.3 9.1<br />
Basic Edition Installed size 1 2 3 4 5 6 7 8<br />
Capacity stage 3 Min. fan-speed level = 1<br />
2 pipes Air flow m 3 / h 170 185 310 345 370 500 545 570<br />
Heating U0W / UWC kW 2.4 2.6 4.4 5.0 5.4 6.8 7.6 8.1<br />
Cooling UW0 / UWC kW 1.3 1.5 2.5 2.9 3.3 3.5 4.1 4.6<br />
Max. fan-speed level = 3<br />
2 pipes Air flow m 3 / h 470 505 815 890 920 1255 1350 1700<br />
Heating U0W / UWC kW 5.2 6.0 9.4 10.6 11.6 14.3 15.8 19.5<br />
Cooling UW0 / UWC kW 2.9 3.3 5.2 6.0 6.5 7.6 8.6 10.7<br />
Heating with pumped hot water: 70/50°C, tL1 +20°C; cooling with pumped cold water: 6/12°C, tL1 +27°C, 46% relative humidity<br />
12 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008
Comfort Edition Performance ratings<br />
Comfort Edition Installed size 1 2 3 4 5 6 7 8<br />
Capacity stage 1 Min. fan-speed level = 1<br />
2 pipes Air flow m 3 / h 150 160 280 290 300 430 460 590<br />
Heating U0W / UWC kW 1.7 2.0 3.2 3.5 3.7 4.9 5.4 6.8<br />
Cooling UW0 / UWC kW 1.0 1.1 1.7 2.0 2.1 2.6 2.9 3.7<br />
4 pipes Air flow m 3 / h 145 155 275 285 295 425 455 575<br />
Heizen UWW kW 0.6 1.0 1.7 1.9 2.1 2.9 3.2 3.9<br />
Cooling UWW kW 0.9 1.0 1.8 2.0 2.0 2.8 3.2 3.7<br />
Max. fan-speed level = 5<br />
2 pipes Air flow m 3 / h 530 540 890 990 1010 1310 1420 1820<br />
Heating U0W / UWC kW 3.9 4.7 6.8 8.1 8.8 10.5 11.7 14.4<br />
Cooling UW0 / UWC kW 2.0 2.4 3.4 4.1 4.7 5.2 5.9 7.3<br />
4 pipes Air flow m 3 / h 525 535 880 980 1000 1295 1405 1800<br />
Heating UWW kW 1.4 2.0 3.1 3.7 4.2 5.3 5.9 7.2<br />
Cooling UWW kW 2.0 2.3 3.5 4.3 4.5 5.7 6.4 7.3<br />
Comfort Edition Installed size 1 2 3 4 5 6 7 8<br />
Capacity stage 2 Min. fan-speed level = 1<br />
2 pipes Air flow m 3 / h 145 155 275 285 295 425 455 575<br />
Heating U0W / UWC kW 1.9 2.2 3.7 4.0 4.3 5.7 6.2 7.8<br />
Cooling UW0 / UWC kW 1.0 1.3 2.1 2.3 2.6 3.0 3.5 4.4<br />
4 pipes Air flow m 3 / h 145 155 265 280 290 415 445 545<br />
Heating UWW kW 0.8 1.0 1.7 2.0 2.1 2.7 3.0 3.6<br />
Cooling UWW kW 1.0 1.2 1.9 2.2 2.4 2.7 3.1 4.0<br />
Max. fan-speed level = 5<br />
2 pipes Air flow m 3 / h 525 535 880 980 1000 1295 1405 1800<br />
Heating U0W / UWC kW 5.0 5.8 8.8 10.1 11.0 13.1 14.6 18.1<br />
Cooling UW0 / UWC kW 2.5 3.1 4.5 5.5 6.1 6.8 7.8 9.6<br />
4 pipes Air flow m 3 / h 510 525 845 950 975 1245 1360 1710<br />
Heating UWW kW 1.7 2.2 3.3 4.0 4.5 5.1 5.8 7.0<br />
Cooling UWW kW 2.3 3.0 4.3 5.2 5.8 6.4 7.4 9.1<br />
Comfort Edition Installed size 1 2 3 4 5 6 7 8<br />
Capacity stage 3 Min. fan-speed level = 1<br />
2 pipes Air flow m 3 / h 145 155 265 280 285 415 445 545<br />
Heating U0W / UWC kW 2.0 2.2 3.8 4.1 4.3 5.7 6.4 7.7<br />
Cooling UW0 / UWC kW 1.2 1.3 2.2 2.4 2.6 3.1 3.4 4.4<br />
Max. fan-speed level = 5<br />
2 pipes Air flow m 3 / h 510 525 845 950 970 1245 1360 1710<br />
Heating U0W / UWC kW 5.5 6.2 9.6 11.1 12.0 14.2 15.9 19.6<br />
Cooling UW0 / UWC kW 3.0 3.4 5.3 6.2 6.7 7.6 8.7 10.8<br />
Heating with pumped hot water: 70/50°C, tL1 +20°C; cooling with pumped cold water: 6/12°C, tL1 +27°C, 46% relative humidity.<br />
Models with different output ratings are available upon request for systems with electrical heating and direct evaporators.<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
13
Base units – dimensions and weights (mass) <strong>GEA</strong> <strong>Flex</strong>-Geko<br />
Comfort Basic Comfort<br />
Installation Recirculated air Mixed air weight weight<br />
sizes mm mm mm mm kg kg<br />
Height Height Width Depth Max Max<br />
1 470 596 761 225 ... 237 13 18<br />
2 470 596 911 225 ... 237 14 22<br />
3 470 596 1061 225 ... 237 18 27<br />
4 470 596 1211 225 ... 237 21 32<br />
5 470 596 1361 225 ... 237 24 36<br />
6 470 596 1511 225 ... 237 28 42<br />
7 470 596 1661 225 ... 237 30 46<br />
8 470 596 1881 225 ... 237 35 52<br />
The dimensions of the recirculated-air unit with 125-mm supporting feet are the same as those of the mixed-air<br />
unit.<br />
Enclosures – dimensions and weights (mass)<br />
Comfort Basic Comfort<br />
Installation Recirculated air Mixed air weight weight<br />
sizes mm mm mm mm kg kg<br />
Height Height Width Depth Max Max<br />
1 504 629 840 240 9 9<br />
2 504 629 990 240 10 10<br />
3 504 629 1140 240 11 11<br />
4 504 629 1290 240 12 12<br />
5 504 629 1440 240 13 13<br />
6 504 629 1590 240 14 14<br />
7 504 629 1740 240 15 15<br />
8 504 629 1890 240 16 16<br />
The dimensions of the recirculated-air unit with 125-mm supporting feet are the same as those of the mixed-air<br />
unit.<br />
Enclosures<br />
Comfort Edition<br />
Recirculated-air wall unit<br />
Without feet; with intake-air grill<br />
in the enclosure<br />
Enclosures<br />
Comfort Edition<br />
Mixed-air wall unit<br />
4 6 7 8<br />
504<br />
240<br />
120<br />
92<br />
504<br />
629<br />
125<br />
240<br />
120<br />
504<br />
629<br />
With feet; without intake-air grill With feet; with intake-air grill<br />
Air outlet on narrow side<br />
125<br />
240<br />
104<br />
Wall units<br />
Recirculated air – Basic and<br />
Comfort<br />
225 (228**)<br />
Mixed air – Comfort Edition<br />
Enclosures<br />
Basic and Comfort Editions<br />
Recirculated-air wall unit<br />
1<br />
504<br />
225<br />
471<br />
35<br />
108<br />
471<br />
125<br />
240<br />
Without feet; without intakeair<br />
grill<br />
240<br />
5<br />
504<br />
629<br />
125<br />
With feet; without intake-air<br />
grill<br />
240<br />
7<br />
504<br />
629<br />
125<br />
With feet; with intake-air grill<br />
504<br />
629<br />
125<br />
With feet; with intake-air grill<br />
Air outlet on front side<br />
14 PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
240<br />
120<br />
104<br />
104
<strong>GEA</strong> <strong>Flex</strong>-Geko Enclosures without supporting feet<br />
Intake-air and outlet-air variations Recirculated Outlet-air grill Outlet-air grill<br />
Wall and ceiling models air-units of plastic of aluminium<br />
Comfort • I Basic Δ For views, see page 7 Adjustable Not adjustable<br />
Intake narrow side | Outlet narrow side<br />
Intake narrow side | Outlet front side<br />
Intake front side | Outlet narrow side<br />
Intake front side | Outlet front side<br />
Intake front side | Outlet narrow side | With cover panel<br />
Intake front side | Outlet narrow side | With rear-wall panel<br />
41<br />
2<br />
3<br />
4<br />
3<br />
3<br />
Intake-air and outlet-air variations Mixed-air Recirculated Outlet-air grill Outlet-air grill<br />
Wall and ceiling models units air-units of plastic of aluminium<br />
Comfort • I Basic Δ For views, see page 7 Adjustable Not adjustable<br />
Intake front side | Outlet narrow side | Without intake grill<br />
Intake front side | Outlet front side | Without intake grill<br />
Intake front side | Outlet narrow side | With intake grill<br />
Intake front side | Outlet front side | With intake grill<br />
Accessories Accessories<br />
Air-intake side<br />
Wall and ceiling models<br />
Comfort • I Basic Δ<br />
Intake-air box with primary-air fittings<br />
Intake-air box with round intake fittings D N<br />
200 enclosure cover for round fittings<br />
Intake-air bend<br />
Intake-air sailcloth fittings<br />
Connection piece for intake-air sailcloth fittings<br />
Intake-air telescopic fittings<br />
Intake-air noise suppressor for recirculated-air<br />
Intake-air noise suppressor for mixed-air units Builtin<br />
wall frame for fresh-air fittings<br />
Weather-protection grill, RAL 9002, painted<br />
Built-in wall frame for weather-protection grill<br />
Spare filter, G1<br />
Spare filter, G2, G3<br />
5<br />
6<br />
7<br />
8<br />
Enclosures with supporting feet<br />
Outlet-air side<br />
Wall and ceiling models<br />
Comfort • I Basic Δ<br />
Outlet-air box with primary-air fittings, not insulated<br />
Outlet-air box with primary-air fittings, insulated<br />
Outlet-air box with round outlet-air fittings, not insulated<br />
Outlet-air box with round outlet-air fittings, insulated<br />
DN 200 enclosure cover for round fittings<br />
Air-outlet bend, not insulated<br />
Air-outlet bend, insulated<br />
Outlet-air sailcloth fittings<br />
Telescopic outlet-air fittings<br />
Outlet-air noise-suppressor fittings<br />
You are on this level of our documentation structure. You can order at no charge<br />
from the first 3 levels as printed copies, under: info@gea-airtreatment.com.<br />
You can download all brochures as PDF files from the following Internet site:<br />
www.gea-airtreatment.com.<br />
PR-2008-0305-GB • We reserve the right to make changes without notice • Version: 09/2008<br />
Image brochure<br />
Application brochures<br />
Product brochures<br />
Data & Facts and operation manuals<br />
(available only as PDF)<br />
15
Customer proximity, sales structures<br />
Reachable always and everywhere!<br />
AE<br />
AT<br />
BA<br />
BE<br />
BG<br />
BY<br />
CH<br />
CZ<br />
CZ<br />
DE<br />
<strong>GEA</strong> Air Treatment<br />
Middle East<br />
UAE-Dubai<br />
Tel. +971 / 4 / 887 3881<br />
<strong>GEA</strong> Klimatechnik<br />
GmbH & Co KG<br />
A-4673 Gaspoltshofen<br />
Tel. +43 / 7735 / 8000-0<br />
<strong>GEA</strong> Klimatechnik<br />
GmbH & Co KG<br />
RS-11070 Novi Beograd<br />
Tel. +381 / 11 / 3193955<br />
<strong>GEA</strong> Happel Belgium N. V.<br />
B-1130 Brussels<br />
Tel. +32 / 2 / 2406161<br />
EVISS Ltd.<br />
BG-7000 Rousse<br />
Tel . +359 / 82 / 81000<br />
<strong>GEA</strong> Klimatechnik UAB<br />
LT-01141 Vilnius<br />
Tel. +370 / 5 / 2106060<br />
ATC Klimatec Schweiz AG<br />
CH-3065 Bolligen<br />
Tel. +41 / 31 / 9171919<br />
<strong>GEA</strong> LVZ, a.s.<br />
CZ-46312 Liberec<br />
Tel. +420 / 48 / 5225-111<br />
<strong>GEA</strong> Klimatizace spol. s r.o.<br />
CZ-46312 Liberec<br />
Tel. +420 / 48 / 5225-303<br />
<strong>GEA</strong> Happel<br />
Klimatechnik GmbH<br />
D-44625 Herne<br />
Tel. +49 / 2325 / 468-00<br />
The complete addresses are available on the<br />
Internet under: www.gea-air-eco2nomy.com.<br />
DE<br />
DE<br />
DE<br />
DE<br />
DK<br />
EE<br />
ES<br />
FI<br />
FR<br />
FR<br />
<strong>GEA</strong> Happel<br />
Wieland GmbH<br />
D-44625 Herne<br />
Tel. +49 / 2325 / 468-754<br />
<strong>GEA</strong> Deichmann<br />
Umwelttechnik GmbH<br />
D-36179 Bebra<br />
Tel. +49 / 6622 / 504-0<br />
<strong>GEA</strong> Delbag<br />
Lufttechnik GmbH<br />
D-44625 Herne<br />
Tel. +49 / 2325 / 468-700<br />
<strong>GEA</strong> Delbag-Luftfilter<br />
Vertriebsgesellschaft mbH<br />
D-10709 Berlin<br />
Tel. +49 / 30 / 43592-3<br />
CS Klimateknik ApS<br />
DK-5450 Otterup<br />
Tel . +45 / 38 / 887070<br />
<strong>GEA</strong> Klimatechnik UAB<br />
LT-01141 Vilnius<br />
Tel. +370 / 5 / 2106060<br />
<strong>GEA</strong> Air Treatment<br />
Marketing Services Int.<br />
GmbH – oficina España<br />
ES-28028 Madrid<br />
Tel. +34 / 91 / 3837701<br />
OY TEKNOCALOR AB<br />
FIN-01300 Vantaa<br />
Tel. +358 / 10 / 8201100<br />
<strong>GEA</strong> Delbag<br />
Filtration de l’air<br />
F-77450 Montry<br />
Tel. +33 / 1 / 60043355<br />
<strong>GEA</strong> Happel France sarl<br />
F-59436 Roncq Cedex<br />
Tel. +33 / 3 / 20689020<br />
GB<br />
HR<br />
HU<br />
IE<br />
IS<br />
LT<br />
LU<br />
LV<br />
ME<br />
NL<br />
NO<br />
<strong>GEA</strong> Denco Ltd.<br />
UK-HR4 8DS Hereford<br />
Tel. +44 / 1432 / 277 277<br />
<strong>GEA</strong> Klima-rashladna<br />
tehnika d.o.o.<br />
HR-10000 Zagreb<br />
Tel. +385 / 1 / 6064900<br />
<strong>GEA</strong> Klimatechnika <strong>Kft</strong><br />
H-1037 Budapest<br />
Tel. +36 / 1 / 4393200<br />
Aspect Environmental Ltd.<br />
Ardee, Co. Louth Ireland<br />
Tel. +353 / 41 / 6858983<br />
Rafn Jensson<br />
IS-110 Reykjavik<br />
Tel. +354 / 56 / 780-30<br />
<strong>GEA</strong> Klimatechnik UAB<br />
LT-01141 Vilnius<br />
Tel. +370 / 5 / 2106060<br />
<strong>GEA</strong> Happel Luxembourg<br />
L-4940 Bascharage<br />
Tel. +352 / 26 / 502970<br />
<strong>GEA</strong> Klimatechnik UAB<br />
LT-01141 Vilnius<br />
Tel. +370 / 5 / 2106060<br />
<strong>GEA</strong> Klimatechnik<br />
GmbH & Co KG<br />
RS-110 70 Novi Beograd<br />
Tel. +381 / 11 / 3193955<br />
<strong>GEA</strong> Happel Nederland B.V.<br />
NL-2909 LL<br />
Capelle a/d Ijssel<br />
Tel. +31 / 10 / 2350606<br />
<strong>GEA</strong> Klimaprodukter AS<br />
N-0484 Oslo<br />
Tel. +47 / 220 / 27990<br />
PL<br />
PT<br />
RO<br />
RU<br />
SE<br />
SI<br />
SK<br />
RS<br />
TR<br />
UA<br />
www.gea-air-eco2nomy.com<br />
<strong>GEA</strong> Klimatyzacja sp.z.o.o<br />
PL-53-609 Wrocław<br />
Tel. +48 / 71 / 3565866<br />
Nónio, Lda.<br />
P-1269-090 Lisboa<br />
Tel. +351 / 21 / 3826160<br />
<strong>GEA</strong> Klimatechnik s.r.l.<br />
RO-300222 Timisoara<br />
Tel. +40 / 356 / 423703<br />
<strong>GEA</strong> Klimatechnik<br />
GmbH & Co KG<br />
RU-105094 Moskva<br />
Tel. +7 / 495 / 9566674<br />
<strong>GEA</strong> EXOS Ventilation AB<br />
S-74528 Enköping<br />
Tel. +46 / 171 / 85530<br />
<strong>GEA</strong> Klimatizacijska<br />
Tehnika d.o.o.<br />
SI-1000 Ljubljana<br />
Tel. +386 / 1 / 2573850<br />
<strong>GEA</strong> Klimatizácia s.r.o.<br />
SK-83104 Bratislava<br />
Tel. +421 / 7 / 44457917<br />
<strong>GEA</strong> Klimatechnik<br />
GmbH & Co KG<br />
RS-11070 Novi Beograd<br />
Tel. +381 / 11 / 3193955<br />
<strong>GEA</strong> ISISAN<br />
TR-80700<br />
Balmumcu Istanbul<br />
Tel. +90 / 212 / 2757171<br />
<strong>GEA</strong> Ukraina t.o.v.<br />
UA-01135 Kyiv<br />
Tel. +38 / 044 / 4619356<br />
09/2008 – PR-2008-0305-GB<br />
Subject to modification • Copyright <strong>GEA</strong>