Photometrics<br />

I5-454T5-UNV-EBT2-UPL<br />

(2) Electronic Ballasts<br />

(4) 54W T5 lamps 4400 lumens<br />

Spacing criterion: (II) 1 2 x mounting<br />

height, (⊥) 0 8 x mounting height<br />

Efficiency 92 8%<br />

Test Report: 236P118<br />

I5-354T5-UNV-EBT2-UPL<br />

(2) Electronic Ballasts<br />

(3) F54T5/HO/830K lamps 4400 lumens<br />

Spacing criterion: (II) 1 2 x mounting<br />

height, (⊥) 0 7 x mounting height<br />

Efficiency 98 2%<br />

Test Report: 236P108<br />

Coefficients of Utilization<br />

Effective floor cavity reflectance 20%<br />

rc 80% 50% 30%<br />

rw 70 50 30 10 50 30 10 50 30 10<br />

RCR<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

109 109 109 109 100 100 100 94 94 94<br />

101 97 94 91 90 87 85 85 83 81<br />

93 87 81 77 80 76 73 76 73 70<br />

86 78 71 66 72 67 63 69 65 61<br />

80 70 63 57 65 60 55 63 58 54<br />

73 63 55 50 59 53 48 56 51 47<br />

68 57 49 44 54 47 43 51 46 42<br />

63 52 44 39 49 43 38 47 41 37<br />

59 47 40 34 44 38 34 43 37 33<br />

54 43 35 30 40 34 30 39 33 29<br />

51 39 32 27 37 31 27 36 30 26<br />

Zonal Lumen Summary<br />

Zone Lumens %Lamp %Fixture<br />

0-30 5508 31 3 33 7<br />

0-40 8329 47 3 51 0<br />

0-60 12731 72 3 78 0<br />

0-90 15217 86 5 93 2<br />

0-180 16330 92 8 100 0<br />

Coefficients of Utilization<br />

Effective floor cavity reflectance 20%<br />

rc 80% 50% 30%<br />

rw<br />

RCR<br />

70 50 30 10 50 30 10 50 30 10<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

115 115 115 115 105 105 105 99 99 99<br />

107 103 100 97 95 92 90 90 88 86<br />

99 92 86 81 85 81 77 81 77 74<br />

91 83 76 70 77 71 67 73 69 65<br />

85 74 67 61 69 63 59 66 61 57<br />

78 67 59 53 63 56 51 60 55 50<br />

73 61 53 47 57 51 46 55 49 45<br />

68 55 48 42 52 46 41 50 45 40<br />

63 50 43 37 48 41 37 46 40 36<br />

58 46 38 33 44 37 33 42 36 32<br />

54 42 35 30 40 34 29 39 33 29<br />

Zonal Lumen Summary<br />

Zone Lumens %Lamp %Fixture<br />

0-30 4637 35 1 35 8<br />

0-40 6733 51 0 51 9<br />

0-60 10058 76 2 77 6<br />

0-90 12070 91 4 93 1<br />

0-180 12966 98 2 100 0<br />

Coefficients of Utilization<br />

Effective floor cavity reflectance 20%<br />

rc 80% 50% 30%<br />

rw 70 50 30 10 50 30 10 50 30 10<br />

RCR<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

I8-332-UNV-EB81-UPL<br />

Electronic Ballast<br />

F32T8/TL835 Lamps 3000 lumens<br />

Spacing criterion: (II) 1 2 x mounting<br />

height, (⊥) 1 1 x mounting height<br />

Efficiency 94 1%<br />

Test Report: 236P188C<br />

Illuminance Estimator<br />

110 110 110 110 100 100 100 95 95 95<br />

101 97 93 90 89 86 83 84 82 80<br />

92 85 79 74 78 74 70 74 70 67<br />

85 75 68 62 69 64 59 66 61 57<br />

78 67 59 53 62 56 51 59 54 49<br />

72 60 52 46 56 49 44 53 48 43<br />

66 54 46 41 51 44 39 48 43 38<br />

62 50 42 36 46 40 35 44 39 34<br />

58 45 38 32 43 36 32 42 35 31<br />

54 42 34 29 39 33 29 38 32 28<br />

51 39 32 27 37 30 26 35 30 26<br />

Zonal Lumen Summary<br />

Zone Lumens %Lamp %Fixture<br />

0-30 2530 28 1 29 9<br />

0-40 3885 43 2 45 9<br />

0-60 6299 70 0 74 4<br />

0-90 7803 86 7 92 1<br />

0-180 8468 94 1 100 0<br />

Illuminance Levels (FC) & Watts Per Sq. Ft. (LPD)<br />

Based on 100 ft. x 100 ft. Open Manufacturing Area Multiplier<br />

I5 4L 54W T5HO 6L 54W T5HO 1.5<br />

Mounting<br />

Height<br />

Spacing 15 ft 20 ft 25 ft 30 ft 35 ft<br />

on Center FC LPD FC LPD FC LPD FC LPD FC LPD<br />

15 ft 45 0.75 42 0.75 39 0.75 36 0.75 34 0.75<br />

20 ft 31 0.52 29 0.52 27 0.52 25 0.52 24 0.52<br />

25 ft 20 0.33 19 0.33 17 0.33 16 0.33 15 0.33<br />

I5-454T5-TBW-UNV-EBT2-UPL<br />

(2) Electronic Ballasts<br />

(4) 54W T5 4400 lumens<br />

Spacing criterion: (II) 1 1 x mounting<br />

height, (⊥) 0 9 x mounting height<br />

Efficiency 81 2%<br />

Test Report: 236P112<br />

I5-354T5-TBW-UNV-EBT2-UPL<br />

(2) Electronic Ballasts<br />

(3) F54T5/HO lamps 4400 lumens<br />

Spacing criterion: (II) 1 0 x mounting<br />

height, (⊥) 0 7 x mounting height<br />

Efficiency 94 2%<br />

Test Report: 236P107<br />

Coefficients of Utilization<br />

Effective floor cavity reflectance 20%<br />

rc 80% 50% 30%<br />

rw 70 50 30 10 50 30 10 50 30 10<br />

RCR<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

95 95 95 95 87 87 87 82 82 82<br />

88 85 82 80 78 76 74 74 72 71<br />

82 76 71 67 70 67 63 66 64 61<br />

75 68 63 58 63 59 55 60 57 54<br />

70 61 55 50 57 52 48 55 51 47<br />

64 55 49 44 52 46 42 49 45 41<br />

60 50 44 39 47 42 38 45 40 37<br />

56 46 39 35 43 38 34 41 37 33<br />

52 41 35 31 39 34 30 38 33 29<br />

48 38 31 27 36 30 26 34 29 26<br />

45 35 28 24 33 27 24 32 27 23<br />

Zonal Lumen Summary<br />

Zone Lumens %Lamp %Fixture<br />

0-30 4945 28 1 34 6<br />

0-40 7390 42 0 51 7<br />

0-60 11071 62 9 77 5<br />

0-90 13159 74 8 92 1<br />

0-180 14293 81 2 100 0<br />

Coefficients of Utilization<br />

Effective floor cavity reflectance 20%<br />

rc 80% 50% 30%<br />

rw<br />

RCR<br />

70 50 30 10 50 30 10 50 30 10<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

110 110 110 110 100 100 100 94 94 94<br />

102 99 95 92 90 88 86 85 83 82<br />

95 88 83 78 81 77 74 77 74 71<br />

88 79 73 68 73 68 64 70 66 62<br />

81 71 64 59 66 61 57 63 59 55<br />

75 64 57 51 60 54 50 58 52 48<br />

70 59 51 46 55 49 44 53 47 43<br />

65 54 46 41 50 44 40 48 43 39<br />

60 49 42 37 46 40 36 44 39 35<br />

56 45 37 33 42 36 32 41 35 31<br />

53 41 34 29 39 33 29 37 32 28<br />

Zonal Lumen Summary<br />

Zone Lumens %Lamp %Fixture<br />

0-30 4535 34 4 36 5<br />

0-40 6495 49 2 52 3<br />

0-60 9563 72 4 76 9<br />

0-90 11373 86 2 91 5<br />

0-180 12428 94 2 100 0<br />

Coefficients of Utilization<br />

Effective floor cavity reflectance 20%<br />

rc 80% 50% 30%<br />

rw 70 50 30 10 50 30 10 50 30 10<br />

RCR<br />

0<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

I8-432-UNV-EB81-UPL<br />

Electronic Ballast<br />

F32T8-TL835 lamps 3000 lumens<br />

Spacing criterion: (II) 1 2 x mounting<br />

height, (⊥) 1 3 x mounting height<br />

Efficiency 91 2%<br />

Test Report: 236P197C<br />

107 107 107 107 98 98 98 92 92 92<br />

98 94 90 87 86 83 81 81 79 77<br />

89 82 76 71 75 71 67 71 68 64<br />

81 72 65 59 66 61 56 63 58 54<br />

74 64 56 50 59 53 48 56 51 46<br />

68 57 49 43 53 46 41 50 45 40<br />

63 51 43 37 48 41 36 46 40 35<br />

59 46 39 33 43 37 32 42 36 31<br />

54 42 35 29 40 33 29 38 32 28<br />

51 39 31 26 37 30 26 35 29 25<br />

48 36 29 24 34 28 23 33 27 23<br />

Zonal Lumen Summary<br />

Zone Lumens %Lamp %Fixture<br />

0-30 2861 23 8 26 1<br />

0-40 4657 38 8 42 6<br />

0-60 8121 67 7 74 2<br />

0-90 10169 84 7 92 9<br />

0-180 10943 91 2 100 0<br />

Multiplier<br />

I8 4L 32W T8 w/Uplight 6L 32W T8 1.5<br />

Mounting<br />

Height<br />

Spacing 15 ft 20 ft 25 ft 30 ft 35 ft<br />

on Center FC LPD FC LPD FC LPD FC LPD FC LPD<br />

15 ft 36 0.4 33 0.4 30 0.4 28 0.4 26 0.4<br />

20 ft 25 0.28 23 0.28 21 0.28 20 0.52 18 0.28<br />

25 ft 16 0.18 15 0.18 14 0.18 13 0.33 12 0.18<br />

Choose the spacing and mounting height to determine the average footcandle and watts per square foot values. Use the multipliers to factor other available<br />