Searching for connected

SLS-500 PLCs

The SLS-500-Configurator has an integrated

automatic search function for connected PLCs. For

this the SLS-500-Configurator scans all available free

ports from COM1 to COM8 for a connected SLS-500-

PLC.

The following baud rates are used:

� 115200 Baud, 8, No Parity, 1 Stop bit

� 57600 Baud, 8, No Parity, 1 Stop bit

� 38400 Baud, 8, No Parity, 1 Stop bit

� 19200 Baud, 8, No Parity, 1 Stop bit

� 9600 Baud, 8, No Parity, 1 Stop bit

� 4800 Baud, 8, No Parity, 1 Stop bit

� 2400 Baud, 8, No Parity, 1 Stop bit

� 1200 Baud, 8, No Parity, 1 Stop bit

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

If no PLC is found, a failure message will occur and

the process has to be repeated.

Otherwise SLS-500-Configurator saves the detected

configuration!


Tech Note: Searching for connected PLC

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

If a program is loaded from SLS-500-Configurator to

the Controller and if the baud rate on the Controller

changes, SLS-500-Configurator will put out a failure

message the next time the download is started:

The function of SLS-500-Configurator is to adapt the

changed adjustments to the Controller and to

download the program without errors.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

„Search PLC“ opens every COM port and scans step

by step with every supported baud rate. This search

runs once.


Tech Note: Adjust baud rate of the SLS-500 PLCs

Products:

Revision: R100

Adjust baud rate

You can adjust the SLS-500 Controller to the

following baud rates:

� 9600 Baud

� No parity

� 8 Data bits

� 1 Stop bit

or

� 19200 Baud

� No parity

� 8 Data bits

� 1 Stop bit

or

� 38400 Baud

� No parity

� 8 Data bits

� 1 Stop bit

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

The adjustment of the baud rate is required for:

�Communication between module and PC

�Communication between module and

external devices, which provides different

baud rates

�Copy program from internal memory

to the MemoryCard

�Copy program from MemoryCard

to internal memory


Tech Note: Adjust baud rate of the SLS-500 PLCs

Products:

Revision: R100

System analogue memory

SIO_RJ11_BAUDRATE

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

The system analogue memory is required for the

baud rate configuration. It is a fixed component of the

system and contains the so-called System Variables.

Example for 9600 Baud

Programming

Title: Initialisierung mit 9600 Baud

9600 SIO_RJ11_BAUDRATE

Example for 19200 Baud

Programming

Title: Initialisierung mit 19200 Baud

19200 SIO_RJ11_BAUDRATE

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

In this case the system variable

SIO_RJ11_BAUDRATE is responsible to initialise the

baud rate.

The name can not be chosen individually since it is

fixed in the system analogue memory. If a false name

or baud rate is chosen the port can not be initialised.

1.

1. initialisation

1.

1. initialisation


Tech Note: Adjust baud rate of the SLS-500 PLCs

Products:

Revision: R100

Example for 38400 Baud

Description

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Programming

Title: Initialisierung mit 38400 Baud

38400 SIO_RJ11_BAUDRATE

The baud rate configuration should only be carried out

on the initialisation page, but it is not absolute

necessary.

The desired value of the baud rate will be registered

in the analogue constant. The system variable loads

the value of the analogue constant. Consequently the

system variable is initialised.

If a non acceptable value is registered – all values

except 9600, 19200 and 38400 – the system variable

will not be initialised and keeps the last saved value.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Save baud rate

1.

1. initialisation

The real-time-clock saves the last used baud rate.

The value can be stored up to 100 days, even in the

case off voltage breakdown.


Tech Note: Cycle time control of SLS-500 PLCs

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

SLS-500-Configurator

Cycle time control

of SLS-500 PLCs

The system software of SLS-500 PLCs executes

programs cyclically. The program cycle splits up in two

parts. The SYSTEM-part and the SLS-500-

Configurator-Program-part. Both parts can be

monitored by their execution time. For this purpose

there are the variables SYS_CYCLEMAX and

SYS_SYSMAX. You can also determine the current

runtime of both parts simultaneously in the software.

SYS_CYCLETIME and SYS_SYSTIME are used as

variables.

Cycle time control

The digital inputs of all modules as well as the digital

outputs, the digital analogue inputs and analogue

outputs will be updated during the SYSTEM-part.

Afterwards corresponding timer and counter will be

processed and safety checks will be carried out etc.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

SYS_SYSTIME

in ms

SYS_CYCLETIME

in ms

SLS-500

SYSTEM

SLS-500

Program

The execution of SLS-500-Configurator program is

determined to completely process the saved SLS-

500-Configurator program. The In/Outputs are taken

from the process image. The process image is an

internal image within the SLS-500-PLCs, which will be

sent to the physical In/Outputs during the SYSTEMpart.


Tech Note: Cycle time control of SLS-500 PLCs

Products:

Revision: R100

Programming the cycle time control with SLS-

500-Configurator

10

3

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

SYS_CYCLEMAX

SYS_SYSMAX

The two variables SYS_CYCLEMAX and

SYS_SYSMAX determine the maximum values. If

maximum values are exceeded, the PLC will give out

ERROR and will switch off all extensions (extension

modules). In this way the maximum cycle time of the

PLC can be limited.

SYS_CYCLETIME

SYS_SYSTIME

ZyklusZeit

SystemZeit

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

The two parameters SYS_CYCLEMAX and

SYS_SYSMAX can be transferred to the analog

memory. In this way you have internal access to the

current cycle time of the program. All time indications

are in ms.


Tech Note: Memory-Card usage with SLS-500 PLCs

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

MemoryCard usage with SLS-500

Main Controller

The MemoryCard for a SLS-500 Main Controller can

be used for 3 different things: The MemoryCard

allows the transport of programs from one main

controller to another. More over the MemoryCard

enables the upgrading of the program of a main

controller and third the MemoryCard can save

remanent data.

Allocation of memory space on

MemoryCard

The MemoryCard has a capacity of 64 kB. 32 kB are

acquired for SLS-500-Configurator programs.

16 kB are used to save remanent analog values (that

makes a capacity of 4096 analog values) and 16 kB

are used to save texts of SLS-500-Configurator (that

makes 512 remanent text values).

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

64kB

SIGRAPH SLS-500

Program

32kB

Remanent

analogue values

4096

Remanent

text strings

512


Tech Note: Memory-Card usage with SLS-500 PLCs

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Installation of the MemoryCard in

SLS-500 Main Controller

The MemoryCard first has to be put into the provided

card holder. Then it has to be inserted into the

Controller as shown in the figure. If the MemoryCard

has no contact the reading operation will give out a

ZERO-value. If the MemoryCard is inserted correctly,

everything will work similar to the description.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Copying programs

Having loaded a correct SLS-500-Configurator

program to the MemoryCard, you can start the known

PLC-manager with „Start->Dialog“. You will have the

following options with the PLC-manager: First you can

copy the current loaded SLS-500-Configurator

program from the Main Controller to the MemoryCard

by clicking the button „CC->MC“. You can also

remove the MemoryCard from the Controller and

insert it into another Controller, which will load the

program automatically as soon as it gets voltage.


Tech Note: Memory-Card usage with SLS-500 PLCs

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Updating programs

2nd occasion: Insert a MemoryCard with a program

into the controller and click the button MC->CC. The

MemoryCard-program will be loaded automatically in

the main controller. Now you could take out the

MemoryCard, because the program is saved to the

controller.

Important: The program can only be copied once.

That means that by clicking the button „CC->MC“, the

program is available on the MemoryCard. If you press

the button „MC->CC“ again, the function will also be

executed just once, so that the program is copied just

once.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

MemoryCard usage with SLS-500-

Configurator

Access the functions of the MemoryCard with

“objects->MemoryCard“ from the menu bar.

Writing analogue values

L1.DI1

0

12345

Write� Write� Write� Write�

Index

Index

Value

Value

Example: If the digital input gets a rising edge, the

value 12345 will be allocated to the Index 0.

Reading analogue values

MEMORY MEMORY CARD

CARD

MEMORY MEMORY CARD

CARD

WRITE

WRITE

VALUE

VALUE

00 Index Index READ

READ

VALUE

VALUE

Out Out

test test

The analogue value of Index 0 will be read out and

saved to the analogue memory „test“.


Tech Note: Memory-Card usage with SLS-500 PLCs

Products:

Revision: R100

Writing text values

00

HIQUEL RESI

L1.DI1

If digital input 1 gets a rising edge, the text „HIQUEL“

will be saved to the MemoryCard with Index 0.

Reading text values

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Write� Write� Write ��

Index

Index

Text

Text

MEMORY MEMORY CARD

CARD

MEMORY MEMORY CARD

CARD

WRITE

WRITE

TEXT

TEXT

0 Index

Index READ

READ

TEXT

TEXT

Out Out

test

The text value on the MemoryCard at Index 0 will be

read out and saved to the text memory „test“.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com


Tech Note: Incremental-Encoder with SLS-500-CAN PLCs

Products:

Revision: R100

SLS-500-CAN-R and SLS-500-CAN-S Main Controller

SLS-500 and Incremental Encoder

The main modules SLS-500-R 24V and SLS-500-S

24V use the last digital inputs (Di5-Di8) to receive the

track of the incremental encoder. Therefore you can

only wire max. 2 incremental encoders with a SLS-

500-R 24V and/or SLS-500-S 24V.

An incremental encoder delivers values on 2 lines,

called track A and track B. The speed at which

impulses are sent by the incremental encoder are

called „line“.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

To process this data with SLS-500, a procedure is

needed that converts the impulses into a position.

This procedure is called „4-times evaluation“.

B

A

24 V

0

24 V

0

A and B in the graph describe the two tracks of the

encoder. The „4-times evaluation“ shows the direction

of rotation and the current position of the encoder.

Example: If the encoder has got a line resolution of

1000, it will deliver 1000 impulses per second. SLS-

500 would internally generate 4000 impulses out of

the 1000 impulses. In this way the PLC splits up one

encoder turn into 4000 parts.

t


Tech Note: Incremental-Encoder with SLS-500-CAN PLCs

Products:

Revision: R100

For SLS-500-CAN-R and SLS-500-CAN-S Main Controller

Wiring with SLS-500-CAN

As shown in the figure, you can wire the incremental

encoder with the CAN Main Controller:

The encoder is connected with digital inputs Di7 and

Di8.

IMPORTANT: The SLS-500 Main Controller can‘t

evaluate more than 5000 edges per second! This is a

total of the encoder and the HS-Counter inputs

together!

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

+24V

GND Di1Ai1 Di2Ai2 Di3Ai3 Di4Ai4

+24V Do1 Do2 Do3 C1-4

GND

A

B

Di5 Di6 Di7 Di8

SLS-500-CAN-R (S) main controller

Do1 Do2 Do3 C1-4


Tech Note: Incremental-Encoder with SLS-500-CAN PLCs

Products:

Revision: R100

For SLS-500-CAN-R and SLS-500-CAN-S Main Controller

Programming incremental encoders

with SLS-500-Configurator

The incremental encoder is initialized by a binary

system-variable, which is set to 1 by a binary

constant. The binary system-variable must have the

name „ENCODER“, otherwise it will not work.

const 1 ENCODER_XY

ENCODER

If the binary system-variable is initialized, the

analogue system-variable Encoder still has to be

initialized and/or set to 0. Nevertheless the name has

s to be correct. (ENCODER)

Here it is set to 0:

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

00 ENCODER_X

ENCODER

The value of the incremental encoder can be easily

saved to a analogue memory:

ENCODER_X

ENCODER MyVar1

That way the incremental encoder can be set to a

desired value:

MyVar1

ENCODER_X

ENCODER


Tech Note: High-Speed-Counter with SLS-500-CAN PLCs

Products:

Revision: R100

SLS-500-CAN-R and SLS-500-CAN-S Main Controller

SLS-500-CAN and High-Speed-Counter

The main modules SLS-500-CAN-R 24V and SLS-

500-CAN-S 24V use the last digital inputs (Di7-Di8) to

count impulses with high frequencies up to 500 kHz .

Therefore you can only wire max. 2 impulse

generators to a SLS-500-CAN-R 24V and/or SLS-

500-CAN-S 24V.

An impulse generator delivers a value on a line, that

refers to the ground of the module.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

To process this data with SLS-500 a procedure is

needed that counts the impulses.

The procedure is called „2-times evaluation“.

All rising and falling edges are noticed.

The system-analogue-memory will be increased by

0,001 after every edge.

A

B

24 V

0

24 V

0

t

Example: If the impulse generator has a line

resolution of 1000, it will deliver 1000 impulses per

turn. SLS-500-CAN would generate internally 2000

impulses out of the 1000 impulses. In this way the

PLC splits up one impulse generator turn into 2000

parts.


Tech Note: High-Speed-Counter with SLS-500-CAN PLCs

Products:

Revision: R100

For SLS-500-CAN-R and SLS-500-CAN-S Main Controller

Wiring with SLS-500

As shown in the figure, you can wire up to two

impulse generators with the main controller:

The first impulse generator is wired with digital input

Di7 and the second impulse generator is wired with

digital input Di8.

IMPORTANT: The SLS-500 Main Controller can‘t

evaluate more than 5000 edges per second! This is a

total of both impulse generators!

GND Di1Ai1 Di2Ai2 Di3Ai3 Di4Ai4

+24V Do1 Do2 Do3 C1-4

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

GND GND

+24V +24V

Di5 Di6 Di7 Di8

SLS-500-CAN-R (S) main controller

A B

Do1 Do2 Do3 C1-4


Tech Note: High-Speed-Counter with SLS-500-CAN PLCs

Products:

Revision: R100

Programming the HSC-Impulse

Generator with SLS-500-Configurator

The impulse generator is initialized by a binary

system-variable, which is set to 1 by a binary

constant. This binary system-variable must have the

name „ENCODER“, otherwise it will not work.

If the binary system-variable is initialized, still both of

the counters (A and B) have to be set to 0. Here the

system-analogue-memory is used. The name has to

be correct. (COUNTER_A, COUNTER_B)

Here they are set to 0:

00

00

For SLS-500-CAN-R and SLS-500-CAN-S Main Controller

const 1 ENCODER_XY

ENCODER

COUNTER_A

ENCODER_X

COUNTER_B

ENCODER_Y

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

The value of an impulse generator can be easily

saved to an analogue memory:

COUNTER_A ENCODER_X

MyVar1

That way the impulse generator can be set to a

desired value to continue counting from there:

MyVar1

COUNTER_A

ENCODER_X


Tech Note: High-Speed-Counter with SLS-500-CAN PLCs

Products:

Revision: R100

SLS-500-CAN-R and SLS-500-CAN-S Main Controller

Programming a Speed-Impulse

Generator with SLS-500-Configurator

Here the system-analogue-memory is used too. Also

the name has to be correct. (SPEED_A, SPEED_B)

This system-analogue-memory must not be reset to

0, because just the impulses per second are

indicated.

This system-analogue-memory will be reset after

every system cycle automatically and will display the

frequency of the impulse generator.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

The value of an impulse generator can be easily

saved to the analogue memory:

ENCODER_X

SPEED_A MyVar2 MyVar1

ENCODER_X

SPEED_B MyVar3 MyVar1


Tech Note: Incremental-Encoder withSLS-500 PLCs

Products:

Revision: R100

For SLS-500-R and SLS-500-S Main Controller

SLS-500 and Incremental Encoder

The main modules SLS-500-R 24V and SLS-500-S

24V use the last digital inputs (Di5-Di8) to receive the

tracks of the incremental encoder. Therefore you can

only wire max. 2 incremental encoders with a SLS-

500-R 24V and/or SLS-500-S 24V.

An incremental encoder delivers values on 2 lines,

called track A and track B. The speed at which

impulses are sent by the incremental encoder are

called „line“.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

To process this data with SLS-500, a procedure is

needed that converts the impulses into a position.

This procedure is called „4-times evaluation“.

B

A

24 V

0

24 V

0

A and B in the graph describe the two tracks of the

encoder. The „4-times evaluation“ shows the direction

of rotation and the current position of the encoder.

Example: If the encoder has got a line resolution of

1000, it will deliver 1000 impulses per second. SLS-

500 would internally generate 4000 impulses out of

the 1000 impulses. In this way the PLC splits up one

encoder turn into 4000 parts.

t


Tech Note: Incremental-Encoder with SLS-500 PLCs

Products:

Revision: R100

For SLS-500-R and SLS-500-S Main Controller

Wiring with SLS-500

As shown in the figure, you can wire up to two

incremental encoders with the main controller.

The first encoder is wired with digital inputs Di5 and

Di6 and the second encoder is wired with digital

inputs Di7 and Di8.

IMPORTANT: The SLS-500 Main Controller can‘t

evaluate more than 5000 edges per second! This is a

total of both encoders!

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

+24V +24V

GND Di1Ai1 Di2Ai2 Di3Ai3 Di4Ai4

+24V Do1 Do2 Do3 C1-4

GND GND

A

B

A

Di5 Di6 Di7 Di8

SLS-500-R (S) main controller

Do1 Do2 Do3 C1-4

B


Tech Note: Incremental-Encoder with SLS-500 PLCs

Products:

Revision: R100

For SLS-500-R and SLS-500-S Main Controller

Programming an Incremental-

Encoder with SLS-500-Configurator

The incremental encoder is initialized by a binary

system-variable, which is set to 1 by an binary

constant. This binary system-variable must have the

name „ENCODER_XY“, otherwise it will not work.

const 1 ENCODER_XY

If the binary system-variable is initialized, still both of

the encoders (X and Y) have to be initialized and/or

set to 0. In the contrast to „ENCODER_XY“, it is not a

binary system-variable but a system-analoguememory.

Nevertheless the name has to be correct.

(ENCODER_X, ENCODER_Y)

Here they are set to 0:

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

00

00

ENCODER_X

ENCODER_Y

The value of an incremental encoder can be easily

saved to an analogue memory:

ENCODER_X MyVar1

That way the incremental encoder can be set to a

desired value:

MyVar1

ENCODER_X


Tech Note: Connection cable for SLS-500 PLCs

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

SLS-510-PC-RS232

(Programming cable)

This cable is required in order to load a SLS-500-

Configurator-Project to a SLS-510 main module. (group

A)

SLS-520-PC-RS232

(Programming cable)

Same cable: SLS-500, SLS-520, SLS-86, HI-86

This cable is required to load a program from SLS-500-

Configurator to SLS-520 Main Controller. (group B)

SLS-500-PC-RS232

(Programming cable)

Same cable: SLS-500, SLS-520, SLS-86, HI-86

This cable is required to load a program from SLS-500-

Configurator to SLS-500 Main Controller. (group C and

D)

SLS-XXX-TERM4

(Connection cable)

Required to connect a HIQUEL-TERM4 terminal to a

SLS-500 Main Controller. (group C and D)

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

SLS-500-CAT5-RS232

This cable provides a free RS232 interface on the

CAT5 hub of the SLS-500 (group C and D).

SLS-500-CAT5*

*0M1, 0M5, 3M0, SPEC

Connects SLS-500 Main Controller with SLS-500

Extension Modules. Different lengths.

SLS-500-BUS

RS485 bus termination for products of groups C and

D.


Tech Note: Connection cable for SLS-F2 PLCs

Products:

Revision: R100

SLS-F2-PC-RS232 (Programming cable)

Required to load a SLS-500-Configurator-Project to a

SLS-F2 Main Module. (group F)

SLS-F2-CAT5

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Required to connect SLS-F2 Main Controllers via CAN-

Bus. (group F)

SLS-F2-CAN-BUS

CAN-bus-termination for SLS-F2. (group F)

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com


Tech Note: Internal Supply Voltage Control

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Internal +24V control for SLS-500 Main-

Controllers

All modules have an internal voltage control, to

guarantee that the extension modules and the main

controller are switched off correctly in the case of a

voltage drop.

The internal power fail-logic monitors the 24-V-voltage

permanently. If the voltage drops below a certain

threshold, the internal CPU program will be informed

and the communication with the extension modules

and the running SLS-500-Configurator program will

be stopped. After that the control will continue to

monitor whether the voltage stays below this crucial

threshold. If this is the case, no SLS-500-Configurator

program will be executed. If the voltage returns to a

normal level, a pause of 2 seconds will be made. After

this break the SLS-500 module and the SLS-500-

Configurator program will be reactivated and all

extension modules will be restarted.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Because of the internal voltage control of the SLS-500

PLCs it is guaranteed that the connected extension

module and the bus-system do only work if the supply

voltage is correct. If there is a short-term voltage drop

in an application, the main controller will shutdown the

running program and will restart it if the voltage

returns to a normal level.

This provides a secure operation of the modules, also

with large spread facilities.


Tech Note: Excel linking to SLS-500 PLCs

Products:

Revision: R100

SIVIEWServer

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

The SIVIEWServer is the link between SLS-500 and

Excel-database. It can pre-process data of up to 16

PLCs for one database.

For every PC-connected PLC you can configure a

own symbol table, as well as name, interface and

baud rate. These configurations will be saved to a file

(for example HIQUEL-SLS-500.ssc).

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Configuration of the symbol table

The symbol table is a file created by the Compiler (for

example RESI.sym). This file has to be opened with

the text editor in order to make changes. This file is

necessary to allocate the names to the right Index.

The file will be saved to the directory ..\local

settings\Temp of the user. The name and the index of

every memory will be displayed during the simulation

of the program.


Tech Note: Real-time clock with SLS-500-Configurator

Products:

Revision: R100

Real-time clock with SLS-500-

Configurator

SLS-500-Controller provide the functions of a RTC

(Real-time clock). This real-time clock will keep

running even in the case of complete voltage

breakdown. The backup-batteries will supply the RTC

for approximately 100 days after voltage breakdown.

SLS-500-Configurator enables the user to read out

the RTC and provides the update to the current date

by using the PC.

Requirements

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

The SLS-500-Controller must be connected to the PC

correctly. After that start the DIALOG from „Start“ and

„Dialog“. The connection to the module will be set up.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Read-out the time

If the connection is set up click the button „Get actual

PLC time“. SLS-500-Configurator will display the

current values of the RTC.

The displayed values can of course differ from the

PC-time.


Tech Note: Real-time clock with SLS-500-Configurator

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Set time to PC-time

SLS-500-Configurator is also able to set the RTC to

the current PC-time.

Set the time by clicking „Set Clock to PC time“. The

current time of the PLC will be loaded to the PLC.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Set time in a running program

SLS-500-Configurator can also change the time with

a program running on a controller.

The text variable which contains the valid date/time

value has the following format:

„WD TT.MM.JJ HH:MM:SS“

TU 14.07.03 15:30:00 CLOCK

This constant has to be connected with a system textmemory

which has to be set to „CLOCK“.

Consequently the internal real-time clock will be set to

the value of the text-constant or text-variable.

IMPORTANT: The integrated real-time clock runs in

24h mode from 00 to 23 o‘clock!


Tech Note: TERM4 – adjustment with SLS-500 PLCs

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Requirements

HIQUEL-TERM4 Terminal, a Interface-cable Term4-

SLS connection cable and a SLS-500 Main Controller

(group C or D).

Setup mode

Assure that your HIQUEL-TERM4 is connected with

the SLS-500 Main Controller and that the voltage

supply is working, but TERM4 must be switched off .

Now press the three marked arrow keys

simultaneously. Keep them pressed and switch on the

terminal. The setup menu will be displayed after

approximately 5 seconds.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Now you are in setup mode of the HIQUEL-TERM4

terminal.

Adjust the parameters of your TERM4 to the

following:

Contrast: 50%

Bus number: 0

Baud rate: 19200 8N1

Communication mode: PROTECTED


Tech Note: TERM4 – adjustment with SLS-500 PLCs

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Cursor up

Cursor down

Edit adjustment

Edit adjustment

Save and exit

Cancel and exit

The active adjustment is flashing. You can edit the

adjustment by using the arrow keys left/right.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Description

Contrast

The lowest value is 0, the highest is 100. Modify the

contrast with keys left/right.

Bus number

If you want to connect more than one terminal to the

BUS during Protected Mode of the terminal, you can

set unique bus numbers from 0 to 255 for the

individual terminals.

Important: Set the bus number to 0.

Baud rate

The different communication types and speeds can

be set. The following adjustment must be made:

19200 8N1.

Communication mode

Controls the different protocols of TERM4.

Adjustment: Choose PROTECTED.


Tech Note: Y-cable for SLS-500 PLCs

Products:

Revision: R100

Components

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Cable components: Two 6-pole RJ11 plugs (SLS-500

Main Controller and HIQUEL-TERM4) and 9-pole D-

Sub plug (PC).

Formation and function

It is constructed in a way that the SLS-500 Main

Controller is able to send data simultaneously to the

terminal and to the PC.

Two diodes enable the TERM4 and the PC to send

data on the same line.

The voltage supply of the terminal runs over the

voltage supply of the SLS-500 Main Controller.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

RS232

and

SLS500

Controller


Tech Note: Y-cable for SLS-500 PLCs

Products:

Revision: R100

T4

1

2

3

4

5

6

1 6

RJ11

1 6

RJ11

6-pole SLS-500 hub

Looking on the front

of the module

+24V

GND

For all SLS-500 Main Controllers and SLS-500-Configurator versions

DI_S

DI_B

RX

TX

6-pole TERM4 hub

Looking on the side

of the module

RJ 11 SLS-500

1 2 3 4 5 6

nc GND BOOT +24V RX TX

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

DCD

RX

TX

DTR

GND

5 4 3 2 1

9 8 7 6

9-pole

D-sub plug,

at PC

DSR

RTS

CTS

RI

1

2

3

4

5

6

7

8

9

PC


Tech Note: RJ45 connector arrangement with SLS-500 PLCs

Products:

Revision: R100

Components

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Cable components: 8-pole RJ45 plug (SLS-500 Main

Controller) and 9-pole D-Sub plug (PC).

Formation and function

It is constructed in a way that the SLS-500 Main

Controller can send data to various periphery.

The voltage supply of a periphery can run over the

voltage supply of the SLS-500 Main Controller up to

500mA.

Use the configuration of the software program to

switch-over from HIQUEL-BUS to the free

programmable RS232. A additional configuration tool

(SLS-500-SIO-CAT5) is required to adjust the

parameters of the serial interface.

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

RS232

and

SLS500

Controller


Tech Note: RJ45 connector arrangement with SLS-500 PLCs

Products:

Revision: R100

1 8

RJ45

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

8-pole SLS-500 hub

Looking on the front

of the module

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

RJ 45 SLS-500

1 2 3 4 5 6

RX TX BUSA +24V GND BUSB

7 8

GND INIT

DCD

RX

TX

DTR

GND

5 4 3 2 1

9 8 7 6

9-pole

D-sub plug

hub

DSR

RTS

CTS

RI

1

2

3

4

5

6

7

8

9

PC


Tech Note: RJ45 connector arrangement with SLS-500 PLCs

Products:

Revision: R100

Connector arrangement

HIQUEL-BUS RS485

The connection to the HIQUEL SLS-500 modules is

provided via CAT5 hub. The following signals are on

this hub:

Important:

This module has an integrated bus termination.

Therefore this module has to be the first or the last

element in the SLS-500 Bus!!

1 8

RJ45

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

PIN

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

1

2

3

4

5

6

7

8

Signal

RXD

TXD

BUSA

+24V

GND

BUSB

GND

INIT_OUT

Marking

RS232-Level-> PC 9-Pol DSUB Pin 3

RS232-Level-> PC 9-Pol DSUB Pin 2

RS485-Pegel -> Connection with BUSA

of the next module

24V

0V -> PC 9-Pol DSUB Pin 5 or GND of

the next module

RS485-Pegel -> Connection with BUSB

of the next module

0V -> PC 9-Pol DSUB Pin 5 or GND of

the next module

TTL-Level-> Connection to the next

module INIT_IN


Tech Note: Visualization with Modbus-RTU

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Configuration - RS232

Touch-Panel

RS232

cable2

RS232

cable1

SLS-500-Modbus-Converter

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

SLS-500-System

up to 32 Expansions


Tech Note: Visualization with Modbus-RTU

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Configuration – RS485

SLS-500-

Modbus-

Converter 1

RS485

cable4

RS232

cable1

SLS-500-

Modbus-

Converter 2

RS485

cable3

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

SLS-500-System

up to 32 Expansions

RS232

SLS-500-System

up to 32 Expansions


Tech Note: Visualization with Modbus-RTU

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Cable 1

SLS-500-

Modbus-

Converter

M-

Rx2

Tx2

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

RJ11-Plug

1

2

3

4

5

6

SLS-500-System


Tech Note: Visualization with Modbus-RTU

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Cable 2

Dsub9-Plug,

on Touch-Panel

Touch-Panel-RS232

1

2

3

4

5

6

7

8

9

TX

RX

GND

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

Rx1

Tx1

M-

SLS-500-

Modbus-

Converter


Tech Note: Visualization with Modbus-RTU

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Cable 3

Dsub9-Plug,

on Touch-Panel

Touch-Panel-RS485

1

2

3

4

5

6

7

8

9

Data+

Data-

GND

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

A1

B1

M-

SLS-500-

Modbus-

Converter


Tech Note: Visualization with Modbus-RTU

Products: For all SLS-500 Main Controllers and all SLS-500-Configurator versions

Revision: R100

Cable 4

Dsub9-Plug,

on Touch-Panel

Modbus-

Converter 1

Touch-Panel-RS485

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

1

2

3

4

5

6

7

8

9

Data+

Data-

GND

M-

A1

B1

M-

A1

B1

Modbus-

Converter 2


Tech Note: SLS-500 overview

Products:

Revision: R100

For all SLS-500 Main Controllers and all SLS-500-Configurator versions

HIQUEL ® GmbH Bairisch Kölldorf 266, A - 8344 Bad Gleichenberg

Tel: +43-3159-3001, Fax: +43-3159-30014, e-mail: hiquel@hiquel.com http: www.hiquel.com

More magazines by this user
Similar magazines