INSTRUCTIONS FOR USE AND MAINTENANCE<br />
4.6.7 Automatic vacuuming & charging completed<br />
Once the charge has been completed, the message<br />
“vacuuming & charging completed” will appear, and the<br />
green LED will cease to flash.<br />
Pressing any key will cause the system to go into scales<br />
mode.<br />
4.7. Gas recovery function<br />
Before selecting the gas recovery option, tare the scales.<br />
Connect the recovery unit to the plug (fig 13).<br />
Plug in the recovery unit.<br />
Place the bottle on the scales.<br />
Disconnect the vacuum pump (fig 12).<br />
Select the gas recovery option on the menu.<br />
Select the amount to be controlled.<br />
Confirm.<br />
4.8. Reset<br />
Once the automatic reset working option has been<br />
confirmed (see 2.2)<br />
4.8.1 Resetting the parameters.<br />
Clearing the tare of the scales.<br />
Programmed charge set to minimum.<br />
Time to create vacuum programmed equal to default<br />
value.<br />
4.8.2 Reset completed.<br />
Message “reset" and green LED lit without flashing.<br />
Pressing any key will cause the system to go into scales<br />
mode.<br />
5. Ordinary Maintenance<br />
Ordinary Maintenance<br />
5.1 Replacing the vacuum pump oil.<br />
The oil must be replaced at least after every 20 hours<br />
of use and at least once every six months, even if the<br />
equipment has not seen continuous use.<br />
Replacing the oil is also essential if it has any residues or<br />
is cloudy in appearance; Contaminated oil, apart from<br />
preventing the pump from achieving acceptable vacuum<br />
levels, can cause irreparable damage to the mechanical<br />
parts of the pump itself.<br />
All the tasks relating to the removal and replacement of the<br />
oil are carried out with the vacuum pump switched off.<br />
- Before removing the oil, leave the pump running for at<br />
least 10 minutes.<br />
- Turn the equipment off by setting the switch no. 3<br />
to position 0 and removing the cable from the power<br />
supply, strictly in that order.<br />
- Remove the drainage plug from the pump situated on<br />
the lower part of the pump.<br />
- Allow all the oil to drain completely<br />
- Replace the drainage plug of the pump tightly<br />
- Remove the filler cap no. 6 located on the upper part<br />
of the pump<br />
- Fill slowly with oil until the level reaches the halfway<br />
position on the visor located at the rear of the pump.<br />
- Replace filler cap no. 6.<br />
6. Removal / Recycling<br />
!<br />
Some parts of the appliance are recyclable. There are<br />
centres which are recognised and certified for the collection<br />
of these recyclable materials. For environmentally friendly<br />
disposal of non/recyclable parts (eg. scrap from the<br />
electronic system), please contact your local waste disposal<br />
department.<br />
GENERAL SAFETY INSTRUCTIONS<br />
!<br />
WARNING<br />
The lubricant must not be disposed of into the<br />
environment; it is a special residue and, as such, it<br />
must be disposed of in compliance with the legislation<br />
in force.<br />
WARNING<br />
Read these instructions thoroughly.<br />
Failure to abide by the following safety instructions may<br />
result in electric shock, fire or serious injury. The term<br />
'power tools' used in the<br />
following instructions refers to portable electrical devices,<br />
whether connected to a power cable or, when powered<br />
by a battery, without a cable.<br />
STORE THIS INSTRUCTIONS MANUAL IN A<br />
SAFE PLACE.<br />
18