13.11.2014 Views

VOLTA 100 / VOLTA 133 Notice de montage - Sammode

VOLTA 100 / VOLTA 133 Notice de montage - Sammode

VOLTA 100 / VOLTA 133 Notice de montage - Sammode

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>VOLTA</strong> <strong>100</strong> / <strong>VOLTA</strong> <strong>133</strong><br />

<strong>Notice</strong> <strong>de</strong> <strong>montage</strong><br />

Mounting instruction<br />

<strong>VOLTA</strong> <strong>100</strong> <strong>VOLTA</strong> <strong>133</strong><br />

1 lampe<br />

1 lamp<br />

2 lampes<br />

dont 1 lampe secourue (douille marquée d’un point vert)<br />

2 lamps<br />

1 lamp supplied by batteries (green point on lamp hol<strong>de</strong>r)<br />

T8 (Ø26mm) Secouru 1h Secouru 3h<br />

Type<br />

D max L Flux mini Flux mini<br />

(mm) (mm) (lm) (lm)<br />

1x36 W 1275 1318 542 217<br />

1x58 W 1575 1618 558 186<br />

T5 (Ø16mm) Secouru 1h Secouru 3h<br />

Type<br />

D max L Flux mini Flux mini<br />

(mm) (mm) (lm) (lm)<br />

1x35 W 1515 1618 925 252<br />

1x54 W 1215 1318 756 160<br />

T8 (Ø26mm) Secouru 1h Secouru 3h<br />

Type<br />

D max L Flux mini Flux mini<br />

(mm) (mm) (lm) (lm)<br />

2x36 W 1275 1355 500 200<br />

2x58 W 1575 1655 510 170<br />

T5 (Ø16mm) Secouru 1h Secouru 3h<br />

Type<br />

D max L Flux mini Flux mini<br />

(mm) (mm) (lm) (lm)<br />

2x35 W 1515 1595 870 237<br />

2x54 W 1215 1295 712 150<br />

Température d’utilisation : <strong>de</strong> 0°C à 30°C<br />

Operating temperature: from 0°C to 30°C<br />

Sammo<strong>de</strong> SA<br />

<strong>Notice</strong> <strong>VOLTA</strong><br />

24 rue <strong>de</strong>s Amandiers, F-75020 Paris 1/4 Octobre 2011


1.<br />

2.<br />

3.<br />

CONNECTER LES BATTERIES<br />

CONNECT BATTERIES<br />

4.<br />

5.<br />

Sammo<strong>de</strong> SA<br />

<strong>Notice</strong> <strong>VOLTA</strong><br />

24 rue <strong>de</strong>s Amandiers, F-75020 Paris 2/4 Octobre 2011


6.<br />

7.<br />

4G1,5/2,5 or 5G1,5/2,5<br />

8.<br />

9.<br />

LANCER UN TEST FONCTIONNEL EN PRESSANT LE BOUTON TEST<br />

PUSH THE BUTTON TO LAUNCH A FUNCTIONAL TEST<br />

Clignotement LED 30 sec, puis LED verte.<br />

LED blinking 30 sec, then permanent green.<br />

10.<br />

Sammo<strong>de</strong> SA<br />

<strong>Notice</strong> <strong>VOLTA</strong><br />

24 rue <strong>de</strong>s Amandiers, F-75020 Paris 3/4 Octobre 2011


1. Position & Câble / Position & cable / Position & Kabel<br />

Horizontal<br />

Vertical<br />

2. Flasques / End caps / Endkappen<br />

α ≠ 0°<br />

α = 0°<br />

3. Vis centrale / Central screw / Zentrale Schraube<br />

Sammo<strong>de</strong> SA<br />

<strong>Notice</strong> <strong>VOLTA</strong><br />

24 rue <strong>de</strong>s Amandiers, F-75020 Paris 4/4 Octobre 2011


<strong>VOLTA</strong> <strong>100</strong> / <strong>VOLTA</strong> <strong>133</strong><br />

Eclairage <strong>de</strong> remplacement<br />

Système automatique <strong>de</strong> test :<br />

<strong>de</strong>scriptif et comportement<br />

Les luminaires <strong>de</strong> la gamme <strong>VOLTA</strong> sont équipés d’une unité <strong>de</strong> secours qui gère automatiquement <strong>de</strong>s<br />

tests pour vérifier le bon fonctionnement du système <strong>de</strong> sécurité :<br />

- Test <strong>de</strong> fonctionnement <strong>de</strong> 30 secon<strong>de</strong>s : chaque semaine, il s’assure du bon fonctionnement <strong>de</strong>s<br />

composants.<br />

- Test d’autonomie <strong>de</strong> 1h ou 3h : annuel, il vérifie également l’autonomie <strong>de</strong>s batteries.<br />

Dans la mesure du possible, ces tests seront lancés en l’absence <strong>de</strong>s utilisateurs, <strong>de</strong> façon à limiter les<br />

nuisances. Le résultat <strong>de</strong> ces tests est indiqué par l’état d’un témoin LED dans le luminaire, dont la<br />

signification est expliquée dans le tableau ci-<strong>de</strong>ssous :<br />

Couleur du témoin LED Signification Que faut-il faire ?<br />

Vert fixe Fonctionnement normal RAS<br />

Vert clignotement rapi<strong>de</strong><br />

(0,1s on / 0,1s off)<br />

Vert clignotement lent<br />

(1s on / 1s off)<br />

Rouge fixe<br />

Rouge clignotement lent<br />

(1s on / 1s off)<br />

Rouge clignotement rapi<strong>de</strong><br />

(0,1s on / 0,1s off)<br />

Test fonctionnel en cours<br />

Test d’autonomie en cours<br />

Défaut lampe<br />

Circuit ouvert ou lampe HS<br />

Défaut batterie<br />

La batterie a échoué au test<br />

d’autonomie ou au test fonctionnel<br />

Défaut <strong>de</strong> charge<br />

La batterie ne se charge pas<br />

RAS<br />

RAS<br />

Changer la lampe, ou vérifier que la lampe<br />

est bien positionnée<br />

Si la batterie vient d’être changée, vérifiez<br />

que les pôles ne sont pas inversés.<br />

Sinon, batterie défectueuse, à changer.<br />

Batterie défectueuse, à changer.<br />

N.B. : Après installation, le luminaire est conçu pour lancer un test <strong>de</strong> mise en service visant à s’assurer<br />

du bon fonctionnement <strong>de</strong>s composants et <strong>de</strong> l’autonomie <strong>de</strong>s batteries. Ce test se lancera entre 5 et 30<br />

jours après mise en service <strong>de</strong>s luminaires.<br />

• LORS DE L’INSTALLATION DU LUMINAIRE, NE PAS OUBLIER DE RECONNECTER LA BATTERIE.<br />

• APRES CHAQUE RELAMPING, BRANCHER LE CONNECTEUR PUIS LANCER UN TEST DE 30<br />

SECONDES PAR APPUI BREF SUR LE BOUTON ROUGE. LE TEMOIN LED DOIT REPASSER AU VERT.<br />

Sammo<strong>de</strong> SA<br />

SAT Gamme <strong>VOLTA</strong><br />

24 rue <strong>de</strong>s Amandiers, F-75020 Paris 1/4 Octobre 2011


<strong>VOLTA</strong> <strong>100</strong> / <strong>VOLTA</strong> <strong>133</strong><br />

Replacement lighting<br />

Automatic Testing System:<br />

<strong>de</strong>scription and instruction notes<br />

<strong>VOLTA</strong> light fittings are provi<strong>de</strong>d with an emergency unit able to run tests automatically, in or<strong>de</strong>r to check the<br />

working or<strong>de</strong>r of the emergency system:<br />

- Function test (30 seconds): Once a week, it checks the good working or<strong>de</strong>r of components, including lamps.<br />

- Duration test (1 or 3 hours): Once a year, it <strong>de</strong>termines whether the batteries are able to fulfill the<br />

requirements.<br />

When possible, these tests are <strong>de</strong>signed to happen during a period of non-occupancy, in or<strong>de</strong>r to avoid<br />

annoyance. The test result is indicated by the colour of the LED insi<strong>de</strong> the luminaire:<br />

LED colour Status What must be done ?<br />

permanent green Everything is OK Nothing<br />

fast blinking green<br />

(0,1s on / 0,1s off)<br />

Function test in progress<br />

Nothing<br />

slow blinking green<br />

(1s on / 1s off)<br />

Duration test in progress<br />

Nothing<br />

permanent red<br />

slow blinking red<br />

(1s on / 1s off)<br />

fast blinking red<br />

(0,1s on / 0,1s off)<br />

Lamp failure<br />

Open circuit, or lamp <strong>de</strong>fault<br />

Battery failure<br />

Battery failed the duration test or the<br />

function test<br />

Incorrect charging current<br />

Batteries cannot charge<br />

Change the lamp if nee<strong>de</strong>d, or check the<br />

position of the lamp<br />

If batteries are new, the connection<br />

poles may have been inverted.<br />

If not, batteries need to be changed.<br />

Batteries need to be changed.<br />

N.B.: After commissioning, the luminaire is <strong>de</strong>signed to launch a commissioning test in or<strong>de</strong>r to check the<br />

good working or<strong>de</strong>r of components and the emergency duration. This test will run from 5 to 30 days after the<br />

commissioning of luminaires.<br />

- WARNING: AFTER COMMISSIONING, DO NOT FORGET TO RECONNECT THE BATTERY.<br />

- AFTER EACH RELAMPING, RECONNECT THE CONNECTOR AND PUSH THE RED BUTTON TO<br />

LAUNCH A 30 SECONDS AUTO-TEST. THE LED LIGHT MUST THEN GO PERMANENT GREEN.<br />

Sammo<strong>de</strong> Sammo<strong>de</strong> SA SA<br />

SAT SAT Gamme Gamme <strong>VOLTA</strong> <strong>VOLTA</strong><br />

24 24 rue rue <strong>de</strong>s <strong>de</strong>s Amandiers, Amandiers, F-75020 F-75020 Paris Paris 3/4 4/4 Octobre Octobre 2011 2011


SCHEMA DE CABLAGE / WIRING SCHEME<br />

EMERGENCY UNIT<br />

TEST BUTTON<br />

LA PHASE Lswitch PERMET DE COMMANDER L’EXTINCTION DES LUMINAIRES SANS COUPER L’ALIMENTATION DE L’UNITE DE SECOURS.<br />

LA COMMANDE D’EXTINCTION PAR COUPURE TOTALE DE L’ALIMENTATION ENTRAINERAIT LE PASSAGE EN MODE SECOURU, ET A TERME<br />

LA DECHARGE DES BATTERIES.<br />

WARNING: Lswitch LINE ENABLES TO SWITCH THE LIGHT OFF WITHOUT STOPPING THE SUPPLY OF THE EMERGENCY SYSTEM.<br />

SWICHTING OFF BY STOPPING THE PERMANENT SUPPLY WOULD COMMUTE THE LUMINAIRE TO EMERGENCY MODE, AND WOULD<br />

EVENTUALLY DISCHARGE THE BATTERIES.<br />

Sammo<strong>de</strong> SA<br />

SAT Gamme VOTA<br />

24 rue <strong>de</strong>s Amandiers, F-75020 Paris 2/4 Octobre 2011


FAQ<br />

Si vous constatez un dysfonctionnement dans la comman<strong>de</strong> d’allumage et d’extinction <strong>de</strong>s luminaires,<br />

vérifiez que le câblage a été réalisé conformément au schéma <strong>de</strong> câblage.<br />

Si le témoin LED reste rouge après installation du luminaire, vérifiez que vous avez bien rebranché la<br />

batterie à l’intérieur du luminaire.<br />

FAQ<br />

- J’ai un <strong>VOLTA</strong><strong>100</strong>. Son niveau d’éclairement est très faible :<br />

J’ai un <strong>VOLTA</strong><strong>133</strong>. Seul un <strong>de</strong>s <strong>de</strong>ux tubes est allumé :<br />

> Si la LED clignote vert, c’est qu’un test automatique est en cours. Il vise à vérifier le bon<br />

fonctionnement du système <strong>de</strong> secours. Il faut patienter, l’éclairage reviendra à son niveau habituel<br />

automatiquement en fin <strong>de</strong> test.<br />

> Si la LED est éteinte, alors le luminaire est en mo<strong>de</strong> secouru, alimenté par ses batteries, suite à un<br />

dysfonctionnement du réseau d’alimentation.<br />

- J’ai effectué un relamping, mais le témoin LED reste rouge :<br />

Lancer systématiquement un test fonctionnel après relamping pour que la LED repasse au vert,<br />

confirmant ainsi le bon fonctionnement du système. Appuyer 1 secon<strong>de</strong> sur le bouton rouge <strong>de</strong> test<br />

qui se trouve dans le luminaire au niveau du connecteur, préalablement branché.<br />

- Le clignotement vert du témoin LED ne s’arrête pas après 30 secon<strong>de</strong>s <strong>de</strong> test fonctionnel :<br />

Si le clignotement se prolonge, c’est que le test n’a pas pu se terminer. Les batteries n’étaient peutêtre<br />

pas assez chargées. Il sera relancé automatiquement dans les 24h, et en cas <strong>de</strong> nouvel échec,<br />

l’état <strong>de</strong> la LED vous l’indiquera, selon le co<strong>de</strong> couleur décrit page 1.<br />

- J’ai changé les batteries <strong>de</strong> mon luminaire, mais le témoin LED reste rouge :<br />

Les batteries sont probablement montées à l’envers. Le fil rouge doit être sur le « + ».<br />

In case of switch on-off malfunction, check first your connections according to the wiring instructions.<br />

If the LED indicator keeps permanent red after commissioning, check battery connections insi<strong>de</strong> the<br />

luminaire.<br />

- I have a <strong>VOLTA</strong><strong>100</strong>. Lighting level is low:<br />

I have a <strong>VOLTA</strong><strong>133</strong>. Only one of the tubes is on:<br />

> If the LED indicator blinks green, an automatic duration test is in progress. It is important to ensure<br />

the good working or<strong>de</strong>r of the emergency system. Please wait, lighting will automatically recover its<br />

usual level when the test is finished.<br />

> If the LED indicator is off, the luminaire is in emergency mo<strong>de</strong>, supplied by batteries, consequently to<br />

a permanent supply failure.<br />

- I ma<strong>de</strong> a relamping, but the LED indicator keeps red:<br />

A manual function test must be systematically launched after relamping so that the LED indicator can<br />

go green, confirming the good working or<strong>de</strong>r of the system. Press 1 second on the red button insi<strong>de</strong><br />

the luminaire, next to the connector that must be connected beforehand.<br />

- The green blinking of the LED does not stop after a 30 seconds function test:<br />

This might be caused by a function test that could not go till its end; batteries were probably<br />

discharged. The function test will be <strong>de</strong>layed and run automatically in the next 24 hours. If the unit fails<br />

the second test, a battery fault will be indicated, according to the table page 4.<br />

- I changed the batteries, but the LED indicator insi<strong>de</strong> the luminaire keeps red:<br />

Batteries connection poles may be inverted. Check that the red wire is connected to « + ».<br />