MONOBLOCCO 400 PIANO - 500 ANGOLO – 800 ANGOLO / Dx - Sx
MONOBLOCCO 400 PIANO - 500 ANGOLO – 800 ANGOLO / Dx - Sx
MONOBLOCCO 400 PIANO - 500 ANGOLO – 800 ANGOLO / Dx - Sx
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
7. CONNECTION TO THE FLUE / AIR FOR COMBUSTION (air intake)<br />
Monoblocco <strong>400</strong> Piano <strong>–</strong> <strong>500</strong> / <strong>800</strong> Angolo<br />
Stiff aluminized steel pipes a minimum of 2 mm in thickness or 316 stainless steel pipes a minimum of 1 mm in<br />
thickness must be connected to the stack.<br />
It is FORBIDDEN to use flexible metal or asbestos cement pipes as they are not entirely safe, being liable to<br />
tear or break and thereby cause smoke to leak out.<br />
The smoke exhaust pipe must be hermetically sealed onto the stack and<br />
can be at a maximum inclination of 45° to avoid exc essive build-up of<br />
condensate produced during the initial start-up phases and/or excessive<br />
build-up of soot, and moreover it avoids slowing down smoke out-flow.<br />
A non-hermetic connection could compromise the device’s working order.<br />
The connection pipe’s internal diameter must be the same as the external<br />
diameter of the device’s smoke stub pipe. This is ensured by using pipes<br />
compliant with DIN 1298.<br />
1000 cm 2<br />
Depression in the stack should be 14 Pa (mod.<strong>400</strong> <strong>–</strong> 1,4 mm column of<br />
water) - 12 Pa (mod.<strong>500</strong>/<strong>800</strong> - 1,2 mm column of water).<br />
The measurement must always be carried out when the device is hot (rated<br />
thermal performance).<br />
You need to reduce depression when it exceeds 17 Pa (1.7 mm column of<br />
water) by installing an additional draught regulator.<br />
IMPORTANT: Only use metal pipes insulated with proper materials<br />
(fibre insulation coating resistant to temperatures up to 600°C) to<br />
avoid deterioration of the walls or counter-hood.<br />
The space between the upper part, the sides of the device and the hood’s<br />
fireproof deflector (at the base of the flue) must be constantly ventilated.<br />
There must therefore be an intake of air from the bottom (intake of fresh air)<br />
and a raised outlet (outlet for hot air).<br />
The air circulation spaces indicated in Picture 16 are the minimum<br />
requirements.<br />
Top: minimum opening 1000 cm 2<br />
Base: minimum opening 750 cm 2<br />
This ensures:<br />
• Improved safety<br />
• Increase in heat created by circulation of air around the device.<br />
ATTENTION: The fireproof plasterboard counter-hood should preferably be<br />
fitted with a self-supporting metal frame to prevent it from weighing too<br />
heavily on the aesthetic coating (marble).<br />
The heat vent grating (Picture 18 pos. 6) has to be installed on the upper<br />
part of the hood at about 20 cm from the ceiling. This must always be<br />
installed as its function is to release heat collected within the hood<br />
(overpressure) out into the room.<br />
7.1. EXTERNAL AIR INTAKE<br />
There must be sufficient quantity of air for combustion and re-oxygenation<br />
of the room to ensure the device will work properly. There should therefore<br />
be vents letting air in from outside the building and enabling circulation of<br />
air for combustion even when the doors and windows are closed.<br />
• The air intake must be in a position where it cannot be<br />
obstructed.<br />
• The air intake should communicate with the room in which the device is installed and be protected with a<br />
grille.<br />
• Vents may communicate with adjacent rooms but not with garages, kitchens, bathrooms or boiler rooms.<br />
• Any extractor hoods in the room where the device is installed must not operate at the same time as this<br />
could cause smoke to enter the room, even with the fireplace’s door closed.<br />
Minimum dimensions:<br />
A <strong>–</strong> natural convection: 300 cm 2<br />
B <strong>–</strong> forced convection: (Picture 13):<br />
150 cm 2 external air intake for the stack;<br />
150 cm 2 external air intake for the fan;<br />
150 cm 2 internal air intake for the fan<br />
Picture 16<br />
750 cm 2<br />
10 cm min post. e laterale Mod 600<br />
min 6 cm gap at back and<br />
sides<br />
Picture 17<br />
24 6098401 Rev.09 <strong>–</strong> EN