Teknisk Datablad Hilti Brannstopp hylse CFS-SL Europeisk ... - Motek
Teknisk Datablad Hilti Brannstopp hylse CFS-SL Europeisk ... - Motek Teknisk Datablad Hilti Brannstopp hylse CFS-SL Europeisk ... - Motek
Teknisk Datablad Hilti Firestop Sleeve CFS-SL Hilti Brannstopp hylse CFS-SL Europeisk Teknisk Godkjenning Utgave 2012 Hilti Firestop Sleeve CFS-SL | Issue 04/2011 page 1
- Page 2: Hilti Firestop Sleeve CFS-SL Hilti
- Page 6: Hilti Firestop Sleeve CFS-SL Hilti
<strong>Teknisk</strong><br />
<strong>Datablad</strong><br />
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
<strong>Hilti</strong> <strong>Brannstopp</strong><br />
<strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong><br />
<strong>Europeisk</strong><br />
<strong>Teknisk</strong> Godkjenning<br />
Utgave 2012<br />
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 1
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
<strong>Brannstopp</strong> <strong>hylse</strong><br />
<strong>CFS</strong>-<strong>SL</strong><br />
Monteringsanvisning<br />
Enkel og rask branntetting av kabler<br />
Ideel ved etterinstallering av kabler<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
Bruksområder<br />
■ Tetting av gjennomføringer med enkeltstående kabler og kabelbunter<br />
■ Velegnet for små og mellomstore sirkulære utsparinger i vegg og<br />
dekke<br />
■ Kan brukes i betong, mur og gips<br />
Fordeler<br />
■ Lett å montere - rask og enkel<br />
■ Funksjonell umiddelbart etter installasjon<br />
■ Enkelt å etterinstallere kabler: enkel åpne- og lukkefunksjon<br />
■ Røyktett uten å ha fugemasse mellom kablene<br />
■ Robust<br />
■ ETA dokumentert brannmotstand opp til 120 minutter<br />
<strong>Teknisk</strong> data<br />
<strong>CFS</strong>-<strong>SL</strong><br />
Ekspanderende<br />
Ja<br />
Maks bredde, fugen rundt<br />
7 mm<br />
Minimum tykkelse vegg<br />
100 mm<br />
Minimum tykkelse dekke<br />
150mm<br />
Andre komponent<br />
<strong>Brannstopp</strong> akryl fugemas. <strong>CFS</strong>-S ACR<br />
Brannklasse E (i henhold til EN 13501-1:2007)<br />
<strong>Europeisk</strong> teknisk godkjenning (ETA) kan du få ved henvende deg til<br />
<strong>Motek</strong><br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
Bestillingsbetegnelse<br />
Anbefalt utsparing<br />
Art. nr.<br />
<strong>Brannstopp</strong> <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> S Ø 63-73 mm 72019717<br />
<strong>Brannstopp</strong> <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> M Ø 113-122 mm 72019718<br />
page 2 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 3
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
Kabelgjennomføringer<br />
Gips- og betong/murvegg<br />
Kabelgjennomføringer<br />
Betong- og murdekke<br />
<strong>Hilti</strong> <strong>Brannstopp</strong> <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> kan benyttes til å opprettholde ønsket brannklasse i:<br />
Gipsvegger (E), minimum 100 mm tykkelse (t E<br />
) og maks tykkelse 200 mm med tre- eller stålstendere, kledd med gips på begge<br />
sider og plater med en total tykkelse på minimum 25 mm. Mellom trestenderne må det være en minimum avstand på 100 mm<br />
mellom tettingen og stender, og hulrommet må fylles med minimum 100 mm isolasjon klasse A1 eller A2 i henhold til EN<br />
13501-1.<br />
Betong- og murvegger (E), minimum densitet/tetthet 650 kg/m 3 , minimum tykkelse 100 mm og maks 200 mm (t E<br />
).<br />
<strong>Hilti</strong> brannstopp <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> kan benyttes til gjennomføringstettinger (A) i betong- og murgulv (E) med minimum densitet/<br />
tetthet 550 kg/m 3 og minimum tykkelse 150 mm og maks tykkelse 200 mm (t E<br />
).<br />
Gjennomføringstetting (A) /<br />
Kabler(C)<br />
Dekke type (E) and tykkelse (t E<br />
)<br />
Klassifisering<br />
E = integritet<br />
I = isolasjon<br />
Andre kriterier<br />
Beskrivelse<br />
Gjennomføringstetting (A) /<br />
Kabler(C)<br />
Alle typer mantlet kabler 1) ≤<br />
diameter 21 mm<br />
Alle typer mantlet kabler 1) ≤<br />
diameter 50 mm<br />
Alle typer mantlet kabler 1) ≤<br />
diameter 80 mm<br />
Bundet kabelbunter maks<br />
diameter 36 mm, maks diameter<br />
enkeltstående kabler 21 mm<br />
Bundet kabelbunter maks<br />
diameter 86 mm, maks diameter<br />
enkeltstående kabler 21 mm<br />
Tom utsparing 2) (ingen kabler<br />
trukket gjennom)<br />
Vegg type (E) and tykkelse (t E<br />
)<br />
Gips- og betongvegg<br />
≥ 100 mm – ≤ 200 mm<br />
Klassifisering<br />
E = integritet<br />
I = isolasjon<br />
EI 60 (<strong>CFS</strong>-<strong>SL</strong> S)<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 90 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 60 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 60 (<strong>CFS</strong>-<strong>SL</strong> S)<br />
EI 90 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 60 (<strong>CFS</strong>-<strong>SL</strong> S)<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
Andre kriterier<br />
Beskrivelse<br />
Fugen rundt <strong>hylse</strong>n må forsegels med <strong>Hilti</strong><br />
<strong>Brannstopp</strong> akryl fugemasse <strong>CFS</strong>-S ACR<br />
på begge sider av veggen (A 2<br />
).<br />
Alle typer mantlet kabler 1) ≤<br />
diameter 21 mm<br />
Alle typer mantlet kabler 1) ≤<br />
diameter 50 mm<br />
Alle typer mantlet kabler 1) ≤<br />
diameter 80 mm<br />
Bundet kabelbunter maks<br />
diameter 36 mm, maks diameter<br />
enkeltstående kabler 21 mm<br />
Bundet kabelbunter maks<br />
diameter 86 mm, maks diameter<br />
enkeltstående kabler 21 mm<br />
Tom utsparing 2) (ingen kabler<br />
trukket gjennom)<br />
Betong- og murdekke<br />
≥150 mm – ≤ 200 mm<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> S og<br />
<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 60 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> S)<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> M)<br />
EI 120 (<strong>CFS</strong>-<strong>SL</strong> S og<br />
<strong>CFS</strong>-<strong>SL</strong> M)<br />
1)<br />
Alle typer mantlet kabler som i dag er vanlig å bruke i Europa (f.eks. kraft, kontrol, signal, telekommunikasjon, data, optiske fiber kabler).<br />
2) Om kabler skal trekkes gjennom på et senerer tidspunkt, for påkrevd klassifisering se detaljer i ETA..<br />
Fugen rundt <strong>hylse</strong>n må forsegels med <strong>Hilti</strong><br />
<strong>Brannstopp</strong> akryl fugemasse <strong>CFS</strong>-S ACR<br />
på begge sider av veggen (A 2<br />
).<br />
1)<br />
Alle typer mantlet kabler som i dag er vanlig å bruke i Europa (f.eks. kraft, kontrol, signal, telekommunikasjon, data, optiske fiber kabler).<br />
2) Om kabler skal trekkes gjennom på et senerer tidspunkt, for påkrevd klassifisering se detaljer i ETA.<br />
page 4 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 5
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
<strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong><br />
Egenskapene til <strong>CFS</strong>-<strong>SL</strong><br />
Tester og dokumentasjon<br />
<strong>Hilti</strong> brannstopp produkter er omfattende testet og indivduelt tilpasser de tekniske krav til et byggs tekniske<br />
krav til elektiske installasjoner. Bedømmelsen av brukervennlighet er gjort i henhold til EOTA ETAG N o 026 del 2.<br />
Egenskaper Tester av egenskapene Norm, standard, test<br />
Helse og miljø<br />
Farlige substanser<br />
I henhold til produsentens deklarasjon, har<br />
produktets innhold blitt sammenlignet med<br />
listen over farlige substanser hos den<br />
<strong>Europeisk</strong>e kommisjon for å verifisere at det<br />
ikke innholder slike substanser over lovlige<br />
grenser. <strong>CFS</strong>-<strong>SL</strong> overholder registering, evaluering,<br />
autorisering og begrensninger av<br />
kjemikaler (REACH).<br />
HMS datablad<br />
Bestandighet<br />
<strong>Hilti</strong> brannstopp <strong>hylse</strong> <strong>CFS</strong>-<strong>SL</strong> har blitt vurdert<br />
ETAG 026-2<br />
til Z 2<br />
kategorien, og resultatet av testene<br />
viser at den er egnet for gjennomføringerstettinger<br />
til bruk i innemiljø, men ikke i fuktighetsklasse<br />
Z 1<br />
, det utelukker temperaturer under<br />
0°C<br />
Brannklassifisering Klasse E EN 13501-1<br />
Service<br />
Med mer enn 20 års erfaring fra hele verden innen passiv brannsikring, er <strong>Hilti</strong> en av de<br />
ledende leverandørene av brannstopp produkter. Vi vil gjerne hjelpe deg aktivt i ditt prosjekt<br />
med branntetting ved å tilby:<br />
• Veileding i produktvalg<br />
• Omfattende teknisk dokumentasjon<br />
• Våre selgere i <strong>Motek</strong> kommer dit du jobber og gir demonstrasjon og opplæring<br />
• Rask og effektiv levering av varer<br />
• Sikkerhet i forhold til offentlige krav til kvaliteten av produktene<br />
• Internationalt nettverk med <strong>Hilti</strong> brannstopp spesialister<br />
page 6 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 <strong>Hilti</strong> Firestop Sleeve <strong>CFS</strong>-<strong>SL</strong> | Issue 04/2011 page 7
<strong>Hilti</strong> = registered trademark of <strong>Hilti</strong> Corp., Schaan I W 4088 0411 0-en I 2 Printed in Liechtenstein I © 2010 I Right of technical and programme changes reserved S. E. & O.<br />
<strong>Hilti</strong>. Outperform. Outlast.<br />
<strong>Hilti</strong> Corporation | 9494 Schaan | Liechtenstein | P +423-234 2111 | F +423-234 2965 | www.hilti.com