Acson Fancoils alla modeller - Ahlsell
Acson Fancoils alla modeller - Ahlsell
Acson Fancoils alla modeller - Ahlsell
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Modeller:<br />
AWM-GW<br />
RCM-DW<br />
ACK-CW/AW<br />
ACC-CW<br />
Fläktkonvektorer<br />
ahlsell kyl<br />
DS108:0806
INNEHÅLLSFÖRTECKNING<br />
1. Egenskaper.............................................................3,6,9,13<br />
2. Tekniska data...............................................................4-17<br />
3. Elektrisk data...............................................................18-21<br />
4. Komponentdata...........................................................22-27<br />
5. Dimensioner................................................................28-39<br />
6. Elschema.....................................................................40-44<br />
7. Inst<strong>alla</strong>tion...................................................................45-60<br />
8. Fjärrkontroll.................................................................61-73<br />
2
1. AWM - EGENSKAPER<br />
• ENKEL INSTALLATION<br />
- Beroende på det smala och kompakta utförandet samt enheternas låga vikt är inomhusdelen lätt<br />
att placera och installera i olika miljöer.<br />
• PLATSBESPARANDE<br />
- Inomhusdelarna monteras på vägg och tar inte upp någon golv- eller takyta. Väggmontaget är en<br />
fördel speciellt vid låga takhöjder.<br />
• LÅG LJUDNIVÅ<br />
- Inomhusdelen har en radialfläkt, och det sköna klimatet förstärks av fläktens låga ljudnivå.<br />
• FÖRNÄMLIG LUFTDISTRIBUTION<br />
- Enheterna har ett bra luftflöde och en förnämlig distribution i fyra riktningar av den kylda luften.<br />
Luftdistributionen kan antingen ställas in manuellt eller med automatik via fjärrkontrollen.<br />
• SERVICEVÄNLIGT UTFÖRANDE<br />
- Inomhusdelens luftfilter har en ny design som gör det enkelt att vid rengöring dra ut filtret från enhetens<br />
intagsgaller.<br />
- Frontpanelen kan enkelt tas bort varvid elektriska komponenter, kablage och rörledningar sedan<br />
blir lätt tillgängliga för service och underhåll.<br />
• TRÅDLÖS FJÄRRKONTROLL<br />
- Med den trådlösa fjärrkontrollen är det möjligt att att var som helst i rummet styra och ställa in aggregatets<br />
drift. Fjärrkontrollens räckvidd är nio meter, och den har bland annat följande funktioner:<br />
- Fläkten i inomhusdelen kan ställas in på hög/medium/låg eller automatik.<br />
- Nattfunktion med högre rumstemperatur under natten, vilket betyder att ett rum inte kyls ner i onödan<br />
om det inte används nattetid.<br />
- Luftdistributionen kan ställas in för automatisk funktion.<br />
- Rumstemperaturen regleras av en elektronisk termostat.<br />
- En timerfunktion som kan ställas in att starta/stoppa aggregatet med upp till 15 timmars fördröjning.<br />
3
AWM-GW<br />
2. TEKNISK DATA<br />
AWM07GW AWM10GW AWM15GW<br />
Btu/h 8000 9500 11000<br />
W 2340 2780 3220<br />
Btu/h 5920 6935 8030<br />
W 1732 2029 2351<br />
Btu/h 18000 21600 24200<br />
W 5280 6330 7090<br />
HIGH l/s / CFM 130 / 275 142 / 300 163 / 345<br />
MEDIUM l/s / CFM 106 / 225 118 / 250 135 / 285<br />
LOW l/s / CFM 83 / 175 94 / 200 104 / 220<br />
HEIGHT mm/in 260 / 10.2<br />
WIDTH mm/in 799 / 31.5<br />
DEPTH mm/in 198 / 7.8<br />
HEIGHT mm/in 337 / 13.3<br />
WIDTH mm/in 857 / 33.7<br />
DEPTH mm/in 270 / 10.6<br />
kg/lb 10 / 22.1<br />
dBA 40 / 35 / 29 39 / 34 / 28 42 / 36 / 29<br />
USGPM<br />
LITRES/M<br />
1.85<br />
7.00<br />
2.11<br />
8.00<br />
2.38<br />
9.00<br />
kPa / psi 41 / 5.9 54 / 7.8 67 / 9.7<br />
kPa / psi 37 / 5.4 44 / 6.4 59 / 8.6<br />
kPa / psi<br />
m/s<br />
ft/min<br />
0.65<br />
127.3<br />
0.61<br />
119.2<br />
0.70<br />
137.1<br />
cm 3 MODEL<br />
NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
260 / 10.2<br />
UNIT DIMENSION<br />
899 / 35.4<br />
198 / 7.8<br />
337 / 13.3<br />
PACKING DIMENSION<br />
957 / 37.7<br />
270 / 10.6<br />
UNIT WEIGHT<br />
12 / 26.5<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 653 / 6.5 737 / 7.4 737 / 7.4<br />
CONNECTION 1/2" BSP FEMALE ADAPTOR<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
AIR DISCHARGE<br />
OPERATION<br />
mm/in<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MWMFW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE<br />
UNIT. MWM301W : 1m IN FRONT AND 1 m BELOW THE DISCHARGE OPENING OF THE UNIT (JIS B 8615)<br />
4<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AUTOMATIC LOUVER (UP& DOWN)<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
16 / 0.63
AWM-GW<br />
AWM20GW AWM25GW<br />
Btu/h<br />
W<br />
16500<br />
4840<br />
18000<br />
5270<br />
Btu/h<br />
W<br />
13120<br />
3848<br />
14760<br />
4326<br />
Btu/h 35000 40500<br />
W 10260 11870<br />
HIGH l/s / CFM 297 / 630 312 / 660<br />
MEDIUM l/s / CFM 231 / 490 274 / 580<br />
LOW l/s / CFM 208 / 440 222 / 470<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
kg/lb 16 / 35.3 16 / 35.3<br />
dBA 49 / 43 / 40 50 / 48 / 44<br />
USGPM<br />
LITRES/M<br />
3.52<br />
13.33<br />
3.65<br />
13.83<br />
kPa / psi 37 / 5.4 41 / 5.9<br />
kPa / psi 31 / 4.5 33 / 4.8<br />
kPa / psi<br />
m/s 1.10 1.16<br />
ft/min 217.2 228.0<br />
cm 3 MODEL<br />
NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
304 / 12.0<br />
UNIT DIMENSION<br />
1062 / 41.8<br />
222 / 8.7<br />
378 / 14.9<br />
PACKING DIMENSION<br />
1130 / 44.5<br />
292 / 11.5<br />
UNIT WEIGHT<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 1023 / 10.2 1023 / 10.2<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
AIR DISCHARGE<br />
OPERATION<br />
mm/in<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MWMFW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE<br />
UNIT. MWM301W : 1m IN FRONT AND 1 m BELOW THE DISCHARGE OPENING OF THE UNIT (JIS B 8615)<br />
5<br />
1/2" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AUTOMATIC LOUVER (UP& DOWN)<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
20 / 0.79
1. RCM - EGENSKAPER<br />
EXTRA SMAL OCH STILFULL DESIGN<br />
Enheterna är konstruerade med tanke på stor flexibilitet och att de ska passa in i olika miljöer<br />
Den smala, kompakta och rundade utformningen av enheterna ger ett mycket elegant intryck.<br />
Inga röranslutningar eller upphängningsdetaljer blir synliga efter monteringen.<br />
CENTRIFUGALFLÄKT MED LÅG LJUDNIVÅ<br />
Enheterna har en låg ljudnivå och är försedda med en fläkt som har tre hastigheter.<br />
INDIVIDUELL REGLERING<br />
Enheterna kan installeras i olika zoner, och varje enhet kan ha sin egen reglerutrustning.<br />
Individuell reglering är energibesparande och det ger bättre komfort och luftdistribution i de<br />
kylda och/eller värmda utrymmena.<br />
PLATSBESPARANDE ENHETER FÖR GOLV- ELLER TAKMONTERING<br />
Enheterna är konstruerade för synligt montage på vägg eller i tak på ett mycket utrymmesbesparande<br />
sätt. Inget behov av att reparera väggar och tak ska normalt uppstå efter monteringen.<br />
Något fundament krävs inte heller för de golvplacerade enheterna. Den enkla<br />
inst<strong>alla</strong>tionen ger ett snabbt montage till en låg kostnad.<br />
STADIG OCH ROBUST KONSTRUKTION<br />
Enheterna är uppbyggda med chassi av ett kraftigt material och med robusta komponenter.<br />
Droppfatet är tillverkat av polystyrenplast och försett med en ytbeläggning som förhindrar att<br />
läckage eller kondens uppstår.<br />
SERVICEVÄNLIGT UTFÖRANDE<br />
Luftfilter, elektriska komponenter, fläkt och fläktmotor kan <strong>alla</strong> enkelt nås för service och<br />
underhåll genom att returluftgallren tas bort. Kyl-/värmebatteriet och droppfatet blir åtkomliga<br />
för rengöring genom att den undre panelen demonteras.<br />
MICROPROCESSORSTYRD REGLERING<br />
Den inbyggda styrutrustningen med fjärrkontroll ger en noggrann reglering, och den har<br />
bland annat följande funktioner:<br />
• Fläktens hastighet kan ställas in på hög/medium/låg eller automatik.<br />
• Timerinställning till/från. Enheterna kan ställas in att automatiskt starta/stoppa vissa tider.<br />
• Elektronisk termostat. Rumstemperaturen får en noggrann reglering vilket leder till bättre<br />
komfort och en energisnålare drift.<br />
• Nattfunktion med högre resp lägre rumstemperatur under natten, vilket betyder att ett rum<br />
inte kyls ner resp värms upp i onödan om det inte används nattetid.<br />
TRÅDLÖS FJÄRRKONTROLL<br />
Med den kompakta trådlösa fjärrkontrollen är det möjligt att var som helst i rummet styra och<br />
ställa in enheternas drift.<br />
AUTOMATISK ELLER MANUELL KONTROLL AV LUFTUTBLÅSNINGEN<br />
Med automatisk kontroll kommer den rörliga luftriktaren att svänga upp och ner, vilket ger en<br />
mycket bra spridning av luften i vertikal riktning. Den horisontella spridningen regleras genom<br />
att justera de vertikala luftriktarna.<br />
6
Teknisk data - RCM-DW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. RCM20/25DW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW<br />
THE UNIT. RCM30/40/50DW : 1 m IN FRONT OF THE UNIT AND 1m BELOW THE AIR DISCHARGE OPENING. (JIS B 8615)<br />
7<br />
RCM20DW RCM25DW RCM30DW<br />
Btu/h<br />
W<br />
20000<br />
5856<br />
22000<br />
6442<br />
25000<br />
7320<br />
Btu/h<br />
W<br />
15140<br />
4433<br />
16786<br />
4915<br />
18875<br />
5527<br />
Btu/h 35000 40000 46000<br />
W 10248 11712 13469<br />
HIGH l/s / CFM 264 / 560 297 / 630 329 / 700<br />
MEDIUM l/s / CFM 239 / 510 293 / 620 325 / 690<br />
LOW l/s / CFM 193 / 410 262 / 550 306 / 650<br />
HEIGHT mm/in 249 / 9.8<br />
WIDTH mm/in 1214 / 47.8<br />
DEPTH mm/in 670 / 26.4<br />
HEIGHT mm/in 345 / 13.6<br />
WIDTH mm/in 1361 / 53.6<br />
DEPTH mm/in 760 / 29.9<br />
kg/lb 45 / 99.2<br />
dBA 50 / 47 / 40 54 / 53 / 50 51 / 50 / 48<br />
USGPM<br />
LITRES/M<br />
3.90<br />
16.75<br />
4.20<br />
18.42<br />
4.90<br />
21.77<br />
kPa / psi 16.75 / 2.43 19.10 / 2.77 16.96 / 2.46<br />
kPa / psi 13.03 / 1.89 14.89 / 2.16 13.10 / 1.90<br />
kPa / psi<br />
m/s<br />
ft/min<br />
1.38<br />
272.0<br />
1.55<br />
306.0<br />
1.38<br />
272.0<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
214 / 8.4<br />
UNIT DIMENSION<br />
1214 / 47.8<br />
670 / 26.4<br />
301 / 11.9<br />
PACKING DIMENSION<br />
1311 / 51.6<br />
760 / 29.9<br />
UNIT WEIGHT<br />
43 / 94.8<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 1890 / 18.9 1890 / 18.9 2342 / 23.4<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
AIR DISCHARGE<br />
OPERATION<br />
mm/in<br />
3/4" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AUTOMATIC LOUVER (UP& DOWN)<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
19.05 / 3/4
Teknisk data - RCM-DW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. RCM20/25DW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW<br />
THE UNIT. RCM30/40/50DW : 1 m IN FRONT OF THE UNIT AND 1m BELOW THE AIR DISCHARGE OPENING. (JIS B 8615)<br />
8<br />
RCM40DW RCM50DW<br />
Btu/h<br />
W<br />
40000<br />
11712<br />
45000<br />
13176<br />
Btu/h<br />
W<br />
29200<br />
8550<br />
32535<br />
9526<br />
Btu/h 75000 85000<br />
W 21960 24888<br />
HIGH l/s / CFM 450 / 950 500 / 1060<br />
MEDIUM l/s / CFM 428 / 910 483 / 1020<br />
LOW l/s / CFM 420 / 890 450 / 950<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
kg/lb<br />
dBA 54 / 53 / 52 54 / 53 / 52<br />
USGPM<br />
LITRES/M<br />
8.60<br />
31.82<br />
9.30<br />
40.19<br />
kPa / psi 11.86 / 1.72 13.58 / 1.97<br />
kPa / psi 9.10 / 1.32 10.48 / 1.52<br />
kPa / psi<br />
m/s<br />
ft/min<br />
1.22<br />
241.0<br />
1.36<br />
267.0<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
249 / 9.8<br />
UNIT DIMENSION<br />
1714 / 67.5<br />
670 / 26.4<br />
345 / 13.6<br />
PACKING DIMENSION<br />
1361 / 53.6<br />
760 / 29.9<br />
UNIT WEIGHT<br />
70 / 154.3<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 4578 / 45.8 4578 / 45.8<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
AIR DISCHARGE<br />
OPERATION<br />
mm/in<br />
3/4" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AUTOMATIC LOUVER (UP& DOWN)<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
19.05 / 3/4
1. ACK - EGENSKAPER<br />
EXTRA SMAL OCH STILFULL DESIGN<br />
Enheterna är konstruerade med tanke på stor flexibilitet samt att de ska passa in i olika miljöer. Den<br />
låga (endast 28 mm) och rundade profilen på frontpanelen ger ett mycket elegant intryck.<br />
CENTRIFUGALFLÄKT MED LÅG LJUDNIVÅ<br />
Fläkten har tre varvtal och låg ljudnivå. Den är utformad för att ge jämn luftdistribution i <strong>alla</strong> riktningar.<br />
INBYGGD KONDENSVATTENPUMP<br />
Enheterna har en inbyggd kondensvattenpump med 500 mm pumphöjd. Detta förenklar arbetet med<br />
dragning av kondensvattenavloppet.<br />
STADIG OCH ROBUST KONSTRUKTION<br />
Enheterna är uppbyggda med chassi av ett kraftigt material och med robusta komponenter. Droppfatet<br />
är tillverkat av polystyrenplast och försett med en ytbeläggning som förhindrar att läckage eller kondens<br />
uppstår.<br />
SERVICEVÄNLIGT UTFÖRANDE<br />
Luftfilter, elektriska komponenter, fläkt, fläktmotor och kondensvattenpump kan <strong>alla</strong> enkelt nås för<br />
service och underhåll genom att returluftgallret tas bort. Om frontpanelen tas bort kan droppfatet och<br />
kyl-/värmebatteriet demonteras.<br />
MICROPROCESSOR MED FJÄRRKONTROLL<br />
Den inbyggda styrutrustningen med fjärrkontroll ger en noggrann reglering, och den har bl a följande<br />
funktioner.<br />
• Fläktens hastighet kan ställas in på hög/medium/låg eller automatik.<br />
• Timerinställning till/från. Enheterna kan förinställas att automatiskt starta och stoppa vissa tider.<br />
• Elektronisk termostat. Rumstemperaturen får en noggrann reglering vilket leder till bättre komfort<br />
och en energisnålare drift.<br />
TRÅDLÖS FJÄRRKONTROLL<br />
Med den kompakta trådlösa fjärrkontrollen är det möjligt att var som helst i rummet styra och ställa in<br />
enheternas drift.<br />
9
Teknisk data - ACK-CW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.<br />
10<br />
ACK10CW ACK15CW ACK20CW<br />
Btu/h<br />
W<br />
9000<br />
2635<br />
15000<br />
4392<br />
16900<br />
4948<br />
Btu/h<br />
W<br />
7000<br />
2050<br />
11000<br />
3221<br />
12000<br />
3514<br />
Btu/h 20000 31000 33500<br />
W 5856 9077 9809<br />
HIGH l/s / CFM 203 / 430<br />
MEDIUM l/s / CFM 193 / 410<br />
LOW l/s / CFM 184 / 390<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
kg/lb ( 22+2 ) / ( 0.9+0.1 )<br />
dBA 44 / 43 / 42 44 / 42 / 41 47 / 46 / 44<br />
USGPM<br />
LITRES/M<br />
1.90<br />
7.19<br />
3.35<br />
12.68<br />
3.60<br />
13.63<br />
kPa / psi 57.42 / 8.33 30.83 / 4.47 35.83 / 5.20<br />
kPa / psi 44.37 / 6.44 24.00 / 3.48 27.30 / 3.96<br />
kPa / psi<br />
m/s<br />
ft/min<br />
0.77<br />
151.8<br />
0.60<br />
118.0<br />
0.66<br />
129.4<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
184 / 390<br />
NOMINAL AIR FLOW<br />
175 / 370<br />
165 / 350<br />
250 / 9.8 ( 295 / 11.6 )<br />
UNIT DIMENSION - ( ) WITH PANEL<br />
570 / 22.4 ( 640 / 25.2 )<br />
570 / 22.4 ( 640 / 25.2 )<br />
317 / 12.5 ( 127 / 5.0 )<br />
PACKING DIMENSION<br />
( ) - PANEL<br />
630 / 24.8 ( 700 / 27.6 )<br />
630 / 24.8 ( 700 / 27.6 )<br />
UNIT WEIGHT ( UNIT + PANEL ) ( 23+2 ) / ( 0.9+0.1 )<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE 1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 435 / 4.4 845 / 8.5 845 / 8.5<br />
CONNECTION 3/4" BSP FEMALE UNION<br />
CONTROL<br />
ROOM TEMPERATURE MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AIR DISCHARGE AUTOMATIC LOUVER (UP& DOWN)<br />
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
CONDENSATE DRAIN SIZE mm/in<br />
19.05 / 3/4
Teknisk data - ACK-AW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. ACK20/25AW/AWH : POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.<br />
ACK30/40/50AW/AWH : 1.5m BELOW THE FACIA (JIS B 8615).<br />
11<br />
ACK20AW ACK25AW ACK30AW<br />
Btu/h<br />
W<br />
24000<br />
7027<br />
25600<br />
7496<br />
29500<br />
8638<br />
Btu/h<br />
W<br />
17800<br />
5212<br />
18800<br />
5505<br />
21600<br />
6324<br />
Btu/h 50900 53000 60900<br />
W 14917 15533 17848<br />
HIGH l/s / CFM 349 / 740 368 / 780 415 / 880<br />
MEDIUM l/s / CFM 297 / 630 312 / 660 349 / 740<br />
LOW l/s / CFM 283 / 600 283 / 600 321 / 680<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
kg/lb ( 31+4 ) / ( 1.2+0.2 ) ( 32+4 ) / ( 1.3+0.2 ) ( 35+4 ) / ( 1.4+0.2 )<br />
dBA 42 / 39 / 37 45 / 42 / 40 49 / 45 / 43<br />
USGPM<br />
LITRES/M<br />
5.50<br />
20.82<br />
5.80<br />
21.96<br />
6.70<br />
25.36<br />
kPa / psi 19.44 / 2.82 23.58 / 3.42 30.47 / 4.42<br />
kPa / psi 16.74 / 2.43 18.48 / 2.68 24.27 / 3.52<br />
kPa / psi<br />
m/s<br />
ft/min<br />
0.71<br />
139.8<br />
0.75<br />
147.9<br />
0.85<br />
166.5<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
335 / 13.2 ( 363 / 14.3 )<br />
UNIT DIMENSION - ( ) WITH PANEL<br />
820 / 32.3 ( 930 / 36.6 )<br />
821 / 32.3 ( 930 / 36.6 )<br />
380 / 15.0 ( 130 / 5.1 )<br />
PACKING DIMENSION<br />
( ) - PANEL<br />
920 / 36.2 ( 1020 / 40.2 )<br />
920 / 36.2 (1000 / 39.4 )<br />
UNIT WEIGHT ( UNIT + PANEL )<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE 1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 2963 / 29.6 2963 / 29.6 2963 / 29.6<br />
CONNECTION 3/4" BSP FEMALE UNION<br />
CONTROL<br />
ROOM TEMPERATURE MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AIR DISCHARGE AUTOMATIC LOUVER (UP& DOWN)<br />
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
CONDENSATE DRAIN SIZE mm/in<br />
19.05 / 3/4
Teknisk data - ACK-AW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. ACK20/25AW/AWH : POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.<br />
ACK30/40/50AW/AWH : 1.5m BELOW THE FACIA (JIS B 8615).<br />
12<br />
ACK40AW ACK50AW<br />
Btu/h<br />
W<br />
35000<br />
10248<br />
40000<br />
11712<br />
Btu/h<br />
W<br />
25500<br />
7466<br />
29600<br />
8667<br />
Btu/h 66600 69100<br />
W 19519 20251<br />
HIGH l/s / CFM 467 / 990 491 / 1040<br />
MEDIUM l/s / CFM 406 / 860 448 / 950<br />
LOW l/s / CFM 359 / 760 411 / 870<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
HEIGHT mm/in<br />
WIDTH mm/in<br />
DEPTH mm/in<br />
kg/lb ( 38+4 ) / ( 1.5+0.2 ) ( 40+4 ) / ( 1.6+0.2 )<br />
dBA 51 / 48 / 46 53 / 52 / 50<br />
USGPM<br />
LITRES/M<br />
7.30<br />
27.63<br />
7.50<br />
28.39<br />
kPa / psi 35.44 / 5.14 37.16 / 5.39<br />
kPa / psi 28.41 / 4.12 29.85 / 4.33<br />
kPa / psi<br />
m/s<br />
ft/min<br />
0.95<br />
187.6<br />
1.00<br />
197.3<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
335 / 13.2 ( 363 / 14.3 )<br />
UNIT DIMENSION - ( ) WITH PANEL<br />
820 / 32.3 ( 930 / 36.6 )<br />
821 / 32.3 ( 930 / 36.6 )<br />
380 / 15.0 ( 130 / 5.1 )<br />
PACKING DIMENSION<br />
( ) - PANEL<br />
920 / 36.2 ( 1020 / 40.2 )<br />
920 / 36.2 (1000 / 39.4 )<br />
UNIT WEIGHT ( UNIT + PANEL )<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE 1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 2963 / 29.6 2963 / 29.6<br />
CONNECTION 3/4" BSP FEMALE UNION<br />
CONTROL<br />
ROOM TEMPERATURE MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
AIR DISCHARGE AUTOMATIC LOUVER (UP& DOWN)<br />
OPERATION LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
CONDENSATE DRAIN SIZE mm/in<br />
19.05 / 3/4
1. ACC - EGENSKAPER<br />
DISKRET AGGREGAT<br />
Eftersom aggregatet är inbyggt i undertaket så är endast luftdon synliga i rummet. Detta<br />
gör att aggregatet inte på verkar inredningen nämnvärt.<br />
Inga röranslutningar eller upphängningsdetaljer blir synliga efter monteringen.<br />
CENTRIFUGALFLÄKT MED LÅG LJUDNIVÅ<br />
Enheterna har en låg ljudnivå och är försedda med en fläkt som har tre hastigheter.<br />
INDIVIDUELL REGLERING<br />
Enheterna kan installeras i olika zoner, och varje enhet kan ha sin egen reglerutrustning.<br />
Individuell reglering är energibesparande och det ger bättre komfort och luftdistribution i de<br />
kylda utrymmena.<br />
TRÅDBUNDEN FJÄRRKONTROLL<br />
Aggregatet utrustas med trådbunden fjärrkontroll, därifrån man enkelt kan styra aggregatets<br />
funktioner.<br />
Inställning av fläktens hastighet låg, medium, hög eller automatik, timer med till- och frånslag,<br />
rumstemperaturen mellan 16-30 grader, nattsänkning m.m.<br />
STADIG OCH ROBUST KONSTRUKTION<br />
Enheterna är uppbyggda med chassi av ett kraftigt material och med robusta komponenter.<br />
Dubbla droppfat och dräneringar för att säkerställa att inga ovälkommna läckage av<br />
kondensvatten uppstår.<br />
SERVICEVÄNLIGT UTFÖRANDE<br />
Luftfilter, elektriska komponenter, fläkt och fläktmotor kan <strong>alla</strong> enkelt nås för service och<br />
underhåll.<br />
MICROPROCESSORSTYRD REGLERING<br />
Den inbyggda styrutrustningen med fjärrkontroll ger en noggrann reglering, och den har<br />
bland annat följande funktioner:<br />
• Fläktens hastighet kan ställas in på hög/medium/låg eller automatik.<br />
• Timerinställning till/från. Enheterna kan ställas in att automatiskt starta/stoppa vissa tider.<br />
• Elektronisk termostat. Rumstemperaturen får en noggrann reglering vilket leder till bättre<br />
komfort och en energisnålare drift.<br />
• Nattfunktion med högre resp lägre rumstemperatur under natten, vilket betyder att ett rum<br />
inte kyls ner resp värms upp i onödan om det inte används nattetid.<br />
13
Teknisk data - ACC-CW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB STD - GB/D17758. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.<br />
TESTED WITH 2m LENGTH DUCT AT THE AIR DISCHARGE OUTLET ANS AIR RETURN INLET.<br />
14<br />
ACC10CW ACC15CW ACC20CW<br />
Btu/h<br />
W<br />
9900<br />
2902<br />
15000<br />
4396<br />
18000<br />
5275<br />
Btu/h<br />
W<br />
7000<br />
2052<br />
10000<br />
2931<br />
13600<br />
3986<br />
Btu/h 19000 25500 38000<br />
W 5569 7474 11137<br />
HIGH l/s / CFM 142 / 300 241 / 510 330 / 700<br />
MEDIUM l/s / CFM 123 / 260 208 / 440 321 / 680<br />
LOW l/s / CFM 104 / 220 170 / 360 293 / 620<br />
mmAq 5 / 4 / 3 5 / 4 / 3 5 / 4 / 3<br />
HEIGHT mm/in 261 / 10.3 262 / 10.3 263 / 10.3<br />
WIDTH mm/in 765 / 30.1 905 / 35.6 1065 / 41.9<br />
DEPTH mm/in 411 / 16.2 412 / 16.2 413 / 16.2<br />
HEIGHT mm/in 410 / 16.1 411 / 16.1 412 / 16.1<br />
WIDTH mm/in 951 / 37.4 1091 / 43.0 1251 / 49.3<br />
DEPTH mm/in 535 / 21.1 536 / 21.1 537 / 21.1<br />
kg/lb 17 / 37.5 21 / 46.3 22 / 48.5<br />
dBA 33 / 30 / 26 37 / 34 / 29 38 / 36 / 34<br />
USGPM<br />
LITRES/M<br />
2.00<br />
7.57<br />
2.58<br />
9.77<br />
4.20<br />
15.90<br />
kPa / psi 8.83 / 1.28 13.97 / 2.03 18.28 / 2.65<br />
kPa / psi 6.69 / 0.97 10.76 / 1.56 14.20 / 2.06<br />
kPa / psi<br />
m/s<br />
ft/min<br />
109.00<br />
232.0<br />
153.00<br />
324.0<br />
312.00<br />
147.0<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
EXTERNAL STATIC ( H/M/L )<br />
UNIT DIMENSION<br />
PACKING DIMENSION<br />
UNIT WEIGHT<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 1108 / 11.1 1356 / 13.6 1678 / 16.8<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
OPERATION<br />
mm/in<br />
3/4" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
19.05 / 3/4
Teknisk data - ACC-CW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB STD - GB/D17758. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.<br />
TESTED WITH 2m LENGTH DUCT AT THE AIR DISCHARGE OUTLET ANS AIR RETURN INLET.<br />
15<br />
ACC25CW ACC28CW<br />
Btu/h<br />
W<br />
22500<br />
6594<br />
26000<br />
7620<br />
Btu/h<br />
W<br />
17900<br />
5246<br />
19500<br />
5715<br />
Btu/h 48000 55000<br />
W 14068 16120<br />
SUPER HIGH l/s / CFM NA 401 / 850<br />
HIGH<br />
MEDIUM<br />
l/s / CFM<br />
l/s / CFM<br />
345 / 730<br />
340 / 720<br />
382 / 810<br />
363 / 770<br />
LOW l/s / CFM 274 / 580 335 / 710<br />
mmAq 5 / 4 / 3 10 / 8 / 7 / 6<br />
HEIGHT mm/in 261 / 10.3 290 / 11.4<br />
WIDTH mm/in 1200 / 47.2 942 / 37.1<br />
DEPTH mm/in 411 / 16.2 600 / 23.6<br />
HEIGHT mm/in 410 / 16.1 327 / 12.9<br />
WIDTH mm/in 1386 / 54.6 1122 / 44.2<br />
DEPTH mm/in 535 / 21.1 674 / 26.5<br />
kg/lb 25 / 55.1 38 / 83.8<br />
dBA 40 / 39 / 36 44 / 41 / 38 / 34<br />
USGPM<br />
LITRES/M<br />
4.70<br />
17.79<br />
5.70<br />
21.58<br />
kPa / psi 24.12 / 3.50 14.69 / 2.13<br />
kPa / psi 18.96 / 2.75 11.38 / 1.65<br />
kPa / psi<br />
m/s<br />
ft/min<br />
173.0<br />
366.0<br />
146.0<br />
309.0<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
EXTERNAL STATIC ( H/M/L )<br />
UNIT DIMENSION<br />
PACKING DIMENSION<br />
UNIT WEIGHT<br />
SOUND PRESSURE LEVEL ( H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 1920 / 19.2 2321 / 23.2<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
OPERATION<br />
mm/in<br />
3/4" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
19.05 / 3/4
Teknisk data - ACC-CW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB STD - GB/D17758. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.<br />
TESTED WITH 2m LENGTH DUCT AT THE AIR DISCHARGE OUTLET ANS AIR RETURN INLET.<br />
16<br />
ACC30CW ACC30CW ACC40CW<br />
Btu/h<br />
W<br />
28000<br />
8206<br />
35000<br />
10258<br />
38000<br />
11137<br />
Btu/h<br />
W<br />
21800<br />
6389<br />
27600<br />
8089<br />
34000<br />
9965<br />
Btu/h 60000 65000 75000<br />
W 17585 19050 21981<br />
SUPER HIGH l/s / CFM 425 / 900 727 / 1540 519 / 1100<br />
HIGH<br />
MEDIUM<br />
l/s / CFM<br />
l/s / CFM<br />
392 / 830<br />
359 / 760<br />
694 / 1470<br />
670 / 1420<br />
500 / 1060<br />
467 / 990<br />
LOW l/s / CFM 335 / 710 637 / 1350 425 / 900<br />
mmAq 21 / 17 / 13 / 9 14 / 12 / 11 / 9 21/ 18 / 13 / 9<br />
HEIGHT mm/in 378 / 14.9 310 / 12.2 378 / 14.9<br />
WIDTH mm/in 929 / 36.6 1247 / 49.1 1045 / 41.1<br />
DEPTH mm/in 541 / 21.3 638 / 25.1 541 / 21.3<br />
HEIGHT mm/in 399 / 15.7 339 / 13.4 399 / 15.7<br />
WIDTH mm/in 1110 / 43.7 1445 / 56.9 1229 / 48.4<br />
DEPTH mm/in 615 / 24.2 711 / 28.0 615 / 24.2<br />
kg/lb 39 / 86.0 41 / 90.4 42 / 92.6<br />
dBA 49 / 46 / 42 / 38 55 / 51 / 48 / 45 51 / 49 / 45 / 41<br />
USGPM<br />
LITRES/M<br />
6.20<br />
23.47<br />
9.60<br />
36.34<br />
7.40<br />
28.01<br />
kPa / psi 12.82 / 1.89 44.24 / 6.42 18.86 / 2.74<br />
kPa / psi 9.86 / 1.43 35.78 / 5.19 14.69 / 2.13<br />
kPa / psi<br />
m/s<br />
ft/min<br />
151.0<br />
320.0<br />
192.0<br />
406.0<br />
170.0<br />
360.0<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
EXTERNAL STATIC ( SH/H/M/L )<br />
UNIT DIMENSION<br />
PACKING DIMENSION<br />
UNIT WEIGHT<br />
SOUND PRESSURE LEVEL ( SH/H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 2714 / 27.1 3123 / 31.2 3093 / 30.9<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
OPERATION<br />
mm/in<br />
3/4" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
19.05 / 3/4
Teknisk data - ACC-CW<br />
MODEL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.<br />
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :<br />
a) COOLING - ENTERING AIR TEMP. : 27°C (80.6°F) DB / 19°C (66.2°F) WB, ENTERING WATER TEMP. : 7°C (44.6°F), LEAVING WATER TEMP. : 12°C (53.6°F)<br />
b) HEATING - ENTERING AIR TEMP.: 20°C (68°F) DB, ENTERING WATER TEMP. : 70°C (158°F), LEAVING WATER TEMP. : 65°C (149°F)<br />
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB STD - GB/D17758. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.<br />
TESTED WITH 2m LENGTH DUCT AT THE AIR DISCHARGE OUTLET ANS AIR RETURN INLET.<br />
17<br />
ACC50CW ACC60CW<br />
Btu/h<br />
W<br />
47000<br />
13775<br />
54000<br />
15826<br />
Btu/h<br />
W<br />
34700<br />
10170<br />
39900<br />
11694<br />
Btu/h 95000 110000<br />
W 27843 32239<br />
SUPER HIGH l/s / CFM 750 / 1590 779 / 1650<br />
HIGH<br />
MEDIUM<br />
l/s / CFM<br />
l/s / CFM<br />
651 / 1380<br />
604 / 1280<br />
722 / 1530<br />
675 / 1430<br />
LOW l/s / CFM 571 / 1210 609 / 1290<br />
mmAq 18 / 16 / 14 / 11 18 / 16 / 14 / 10<br />
HEIGHT mm/in 378 / 14.9 379 / 14.9<br />
WIDTH mm/in 1299 / 51.1 1499 / 59.0<br />
DEPTH mm/in 541 / 21.3 542 / 21.3<br />
HEIGHT mm/in 399 / 15.7 399 / 15.7<br />
WIDTH mm/in 1481 / 58.3 1685 / 66.3<br />
DEPTH mm/in 615 / 24.2 615 / 24.2<br />
kg/lb 54 / 119.0 62 / 136.7<br />
dBA 53 / 52 / 50 / 47 55 / 53 / 50 / 47<br />
USGPM<br />
LITRES/M<br />
10.00<br />
37.85<br />
10.80<br />
40.88<br />
kPa / psi 37.08 / 5.38 7.01 / 1.02<br />
kPa / psi 29.65 / 4.30 5.38 / 0.78<br />
kPa / psi<br />
m/s<br />
ft/min<br />
159.0<br />
336.0<br />
157.0<br />
333.0<br />
cm 3 NOMINAL TOTAL COOLING CAPACITY<br />
NOMINAL SENSIBLE COOLING CAPACITY<br />
NOMINAL TOTAL HEATING CAPACITY (ENTERING<br />
WATER TEMP. = 70°C)<br />
NOMINAL AIR FLOW<br />
EXTERNAL STATIC ( SH/H/M/L )<br />
UNIT DIMENSION<br />
PACKING DIMENSION<br />
UNIT WEIGHT<br />
SOUND PRESSURE LEVEL ( SH/H/M/L )<br />
NOMINAL WATER FLOW RATE<br />
HEAD LOSS (COOLING)<br />
HEAD LOSS (HEATING) : 70°C<br />
MAX. WORKING PRESSURE<br />
1608 / 233<br />
SURFACE AIR VELOCITY<br />
FAN COIL WATER VOLUME & MASS<br />
/ kg 3893 / 38.9 4512 / 45.1<br />
CONNECTION<br />
CONTROL<br />
CONDENSATE DRAIN SIZE<br />
ROOM TEMPERATURE<br />
OPERATION<br />
mm/in<br />
7/8" BSP FEMALE ADAPTOR<br />
MICRO-COMPUTER CONTROLLED THERMOSTAT<br />
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL<br />
19.05 / 3/4
AWM-GW<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
AWM 301W<br />
MODEL<br />
FAN MOTOR<br />
3. ELEKTRISK DATA<br />
AWM07GW AWM10GW AWM15GW<br />
INSULATION GRADE<br />
B B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 24 26 29<br />
RATED RUNNING CURRENT A 0.11 0.11 0.13<br />
MOTOR OUTPUT W 8 9 13<br />
POLES<br />
4 4 4<br />
AWM20GW AWM25GW<br />
INSULATION GRADE<br />
B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 69 70<br />
RATED RUNNING CURRENT A 0.29 0.29<br />
MOTOR OUTPUT W 25 55<br />
POLES<br />
4 4<br />
INSULATION GRADE<br />
AWM301W<br />
F<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 68<br />
RATED RUNNING CURRENT A 0.30<br />
MOTOR OUTPUT W 40<br />
POLES<br />
4<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.<br />
18
Elektriska data - RCM-DW<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
RCM-CBW<br />
MODEL<br />
FAN MOTOR<br />
ACM-EW<br />
MODEL<br />
FAN MOTOR<br />
RCM20DW RCM25DW RCM30DW<br />
INSULATION GRADE<br />
B B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 88 118 120<br />
RATED RUNNING CURRENT A 0.40 0.58 0.58<br />
MOTOR OUTPUT W 40 65 65<br />
POLES<br />
4 4 4<br />
RCM40DW RCM50DW<br />
INSULATION GRADE<br />
B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 217 217<br />
RATED RUNNING CURRENT A 1.04 1.04<br />
MOTOR OUTPUT W 100 100<br />
POLES<br />
4 4<br />
RCM07CBW RCM10CBW RCM15CBW<br />
INSULATION GRADE<br />
B B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 47 52 75<br />
RATED RUNNING CURRENT A 0.22 0.24 0.34<br />
MOTOR OUTPUT W 20 20 30<br />
POLES<br />
4 4 4<br />
ACM15EW ACM20EW ACM25EW<br />
INSULATION GRADE<br />
B B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 101 109 113<br />
RATED RUNNING CURRENT A 0.46 0.49 0.51<br />
MOTOR OUTPUT W 50 65 70<br />
POLES<br />
4 4 4<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.<br />
19
Elektriska data - ACK-AW<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
ACK-BW<br />
MODEL<br />
FAN MOTOR<br />
ACK-CW<br />
MODEL<br />
FAN MOTOR<br />
ACK-AWH<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
ACK20AW ACK25AW ACK30AW<br />
INSULATION GRADE<br />
E E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 121 144 156<br />
RATED RUNNING CURRENT A 0.53 0.65 0.69<br />
MOTOR OUTPUT W 35 45 60<br />
POLES<br />
6 6 6<br />
ACK40AW ACK50AW<br />
INSULATION GRADE<br />
E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 183 241<br />
RATED RUNNING CURRENT A 0.80 1.08<br />
MOTOR OUTPUT W 83 120<br />
POLES<br />
6 6<br />
ACK15BW ACK20BW ACK25BW<br />
INSULATION GRADE<br />
E E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 69 69 75<br />
RATED RUNNING CURRENT A 0.30 0.30 0.31<br />
MOTOR OUTPUT W 22 22 30<br />
POLES<br />
6 6 6<br />
ACK10CW ACK15CW ACK20CW<br />
INSULATION GRADE<br />
E E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 56 63 74<br />
RATED RUNNING CURRENT A 0.24 0.28 0.31<br />
MOTOR OUTPUT W 16 18 22<br />
POLES<br />
6 6 6<br />
ACK20AWH ACK25AWH ACK30AWH<br />
INSULATION GRADE<br />
E E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 121 144 156<br />
RATED RUNNING CURRENT A 0.53 0.65 0.69<br />
MOTOR OUTPUT W 35 45 60<br />
POLES<br />
6 6 6<br />
ACK40AWH ACK50AWH<br />
INSULATION GRADE<br />
E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 183 241<br />
RATED RUNNING CURRENT A 0.80 1.08<br />
MOTOR OUTPUT W 83 120<br />
POLES<br />
6 6<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.<br />
20
Elektriska data - ACC-CW<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
MODEL<br />
FAN MOTOR<br />
ACC10CW ACC15CW ACC20CW<br />
INSULATION GRADE<br />
E E E<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 68 97 141<br />
RATED RUNNING CURRENT A 0.30 0.43 0.65<br />
MOTOR OUTPUT W 30 50 80<br />
POLES<br />
4 4 4<br />
ACC25CW ACC28CW ACC30CW<br />
INSULATION GRADE<br />
E B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 172 286 401<br />
RATED RUNNING CURRENT A 0.74 1.30 1.90<br />
MOTOR OUTPUT W 100 320 320<br />
POLES<br />
4 4 4<br />
ACC38CW ACC40CW ACC50CW<br />
INSULATION GRADE<br />
B B B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 536 524 638<br />
RATED RUNNING CURRENT A 2.40 2.60 2.90<br />
MOTOR OUTPUT W 470 400 480<br />
POLES<br />
4 4 4<br />
INSULATION GRADE<br />
ACC60CW<br />
B<br />
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50<br />
RATED INPUT POWER W 713<br />
RATED RUNNING CURRENT A 3.20<br />
MOTOR OUTPUT W 600<br />
POLES<br />
4<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.<br />
21
4. Komponentdata AWM-GW<br />
MODEL<br />
COIL<br />
AIR FILTER<br />
TYPE<br />
Q'TY<br />
FAN MATERIAL<br />
FAN MOTOR<br />
CASING<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
DRIVE<br />
LENGTH x DIAMETER<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
COLOUR<br />
TYPE<br />
MATERIAL<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
MATERIAL<br />
Q'TY<br />
MATERIAL<br />
DRIVE<br />
LENGTH x DIAMETER<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
AWM07GW AWM10GW<br />
AWM15GW<br />
mm/in 617.5 x 97 ( 24.3 x 3.8 )<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.20 / 2.16<br />
ROW<br />
2<br />
FIN PER INCH<br />
18<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
MATERIAL<br />
COLOUR<br />
MATERIAL<br />
mm/in<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
MATERIAL<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2<br />
ROW<br />
SIZE ( L x W x t )<br />
FIN PER INCH<br />
22<br />
1 1<br />
1<br />
1 1<br />
1<br />
IP24 IP24<br />
IP24<br />
CROSS FLOW FAN<br />
1 1<br />
1<br />
IP20<br />
ANTI FUNGUS SKEW FAN<br />
ACRYLO NITRILE STYRENE<br />
DIRECT<br />
INDUCTION<br />
CROSS FINNED TUBES<br />
PLAIN COPPER<br />
7.00 / 0.28<br />
0.32 / 0.013<br />
ALUMINIUM<br />
0.11 / 0.004<br />
ACRYLO NITRILE STYRENE<br />
DIRECT<br />
810 x 108 ( 31.9 x 4.3 )<br />
INDUCTION<br />
CROSS FINNED TUBES<br />
PLAIN COPPER<br />
7.00 / 0.28<br />
0.32 / 0.013<br />
ALUMINIUM<br />
0.11 / 0.004<br />
717.5 x 97 ( 28.2 x 3.8 )<br />
0.23 / 2.52<br />
2<br />
18<br />
WASHABLE SARANNET (NANO FILTER)<br />
AWM20GW<br />
304 x 298 x 1.5 ( 11.9 x 11.7 x 0.1 )<br />
HIGH IMPACT POLYSTYRENE<br />
LIGHT GREY<br />
0.27 / 2.90<br />
2<br />
18<br />
WASHABLE SARANNET (NANO FILTER)<br />
mm/in 351 x 386 x 105 ( 13.8 x 15.2 x 0.1 )<br />
HIGH IMPACT POLYSTYRENE<br />
LIGHT GREY<br />
AWM25GW<br />
1<br />
IP20
Komponentdata - RCM-DW<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
TYPE<br />
Q'TY<br />
MATERIAL<br />
DRIVE<br />
DIAMETER x LENGTH<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
Q'TY<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
COLOUR<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
23<br />
RCM20DW RCM25DW RCM30DW<br />
2 2 3<br />
1 1 1<br />
NA NA NA<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.11 / 0.004<br />
0.19 / 2.06 0.19 / 2.06 0.24 / 2.57<br />
ROW<br />
3 3 3<br />
FIN PER INCH<br />
12 12 12<br />
PC/S 2 2 2<br />
mm<br />
544 x 270 x 3<br />
in<br />
21.4 x 10.6 x 0.1<br />
ELECTRO-GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
RCM40DW RCM50DW<br />
4 4<br />
mm/in<br />
1 1<br />
NA NA<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 TYPE<br />
CROSS FLOW FAN<br />
Q'TY<br />
MATERIAL<br />
ABS<br />
DRIVE<br />
DIRECT<br />
DIAMETER x LENGTH<br />
146 x 200 / 5.8 x 7.9<br />
TYPE<br />
INDUCTION<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
CROSS FINNED TUBES<br />
MATERIAL<br />
INNER GROOVED COPPER<br />
TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
MATERIAL<br />
CORRUGATED ALUMINIUM<br />
0.11 / 0.004<br />
FIN<br />
0.37 / 3.96 0.37 / 3.96<br />
ROW<br />
4 4<br />
FIN PER INCH<br />
12 14<br />
MATERIAL<br />
WASHABLE SARANNET<br />
Q'TY<br />
PC/S 2 + 1 2 + 3<br />
mm 514 x 270 x 3 (2 pcs) 500 x 285 x 3 (2 pcs)<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
COLOUR<br />
MATERIAL<br />
MATERIAL<br />
mm 494 x 270 x 3 (1 pc) 400 x 285 x 3 (3 pcs)<br />
in 21.4 x 10.6 x 0.1 (2 pcs) 19.6 x 11.2 x 0.1 (2 pcs)<br />
in 19.4 x 10.6 x 0.1 (1 pc) 15.7 x 11.2 x 0.1 (3 pcs)<br />
ELECTRO-GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
CROSS FLOW FAN<br />
ABS<br />
DIRECT<br />
146 x 200 / 5.8 x 7.9<br />
INDUCTION<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
CORRUGATED ALUMINIUM<br />
WASHABLE SARANNET
Komponent data - ACK-AW<br />
MODEL<br />
FAN MATERIAL<br />
DRIVE<br />
DIAMETER<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
TYPE<br />
Q'TY<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
24<br />
ACK20AW ACK25AW ACK30AW<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.11 / 0.004<br />
0.47 / 5.02 0.47 / 5.03 0.47 / 5.04<br />
ROW<br />
2 2 2<br />
FIN PER INCH<br />
14 14 16<br />
SIZE ( L x W x t ) mm/in<br />
TYPE<br />
Q'TY<br />
MATERIAL<br />
DRIVE<br />
DIAMETER<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2<br />
SIZE ( L x W x t ) mm/in<br />
MATERIAL (PANEL)<br />
PANEL COLOUR<br />
MATERIAL<br />
MATERIAL<br />
MATERIAL (PANEL)<br />
PANEL COLOUR<br />
MATERIAL<br />
MATERIAL<br />
ROW<br />
FIN PER INCH<br />
576 x 556 x 22 / 22.7 x 21.9 x 0.9<br />
ELECTRO-GALVANIZED MILD STEEL (ABS )<br />
LIGHT GREY<br />
ACK40AW ACK50AW<br />
TURBO FAN<br />
1<br />
ASG20<br />
DIRECT<br />
450 / 17.7<br />
INDUCTION<br />
1<br />
IP22<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
ALUMINIUM SLIT FIN<br />
0.11 / 0.004<br />
0.47 / 5.02<br />
2 2<br />
16 16<br />
WASHABLE SARANNET<br />
576 x 556 x 22 / 22.7 x 21.9 x 0.9<br />
ELECTRO-GALVANIZED MILD STEEL (ABS )<br />
LIGHT GREY<br />
TURBO FAN<br />
1<br />
ASG20<br />
DIRECT<br />
450 / 17.7<br />
INDUCTION<br />
1<br />
IP22<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
ALUMINIUM SLIT FIN<br />
WASHABLE SARANNET
Komponent data - ACK-CW<br />
ACK10CW ACK15CW<br />
1 1<br />
mm/in<br />
1 1<br />
NA NA<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 MODEL<br />
TYPE<br />
TURBO FAN<br />
Q'TY<br />
FAN MATERIAL<br />
ASG20<br />
DRIVE<br />
DIRECT<br />
DIAMETER<br />
330 / 13.0<br />
TYPE<br />
INDUCTION<br />
FAN MOTOR Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
CROSS FINNED TUBES<br />
MATERIAL<br />
INNER GROOVE COPPER TUBE<br />
TUBE<br />
7.00 / 0.276<br />
0.28 / 0.011<br />
COIL<br />
MATERIAL<br />
ALUMINIUM SLIT FIN<br />
0.11 / 0.004<br />
FIN<br />
0.24 / 2.583 0.309 / 3.323<br />
ROW<br />
1 2<br />
FIN PER INCH<br />
16 20<br />
AIR FILTER MATERIAL<br />
WASHABLE SARANNET<br />
SIZE ( L x W x t ) mm/in<br />
368 x 381 x 21 / 14.5 x 15 x 0.8<br />
CASING<br />
MATERIAL (PANEL)<br />
PANEL COLOUR<br />
ELECTRO-GALVANIZED MILD STEEL ( ABS )<br />
LIGHT GREY<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2<br />
TYPE<br />
Q'TY<br />
MATERIAL<br />
DRIVE<br />
DIAMETER<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
MATERIAL<br />
TUBE<br />
MATERIAL<br />
FIN<br />
MATERIAL<br />
ROW<br />
FIN PER INCH<br />
SIZE ( L x W x t ) mm/in<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
25<br />
ACK20CW<br />
TURBO FAN<br />
1<br />
ASG20<br />
DIRECT<br />
330 / 13.0<br />
INDUCTION<br />
1<br />
NA<br />
CROSS FINNED TUBES<br />
BARE COPPER TUBE<br />
7.00 / 0.276<br />
0.28 / 0.011<br />
ALUMINIUM SLIT FIN<br />
0.11 / 0.004<br />
0.309 / 3.323<br />
2<br />
20<br />
WASHABLE SARANNET<br />
368 x 381 x 21 / 14.5 x 15 x 0.8<br />
MATERIAL (PANEL) ELECTRO-GALVANIZED MILD STEEL ( ABS )<br />
PANEL COLOUR<br />
LIGHT GREY
Komponentdata - ACC-CW<br />
MODEL<br />
FAN MATERIAL<br />
DRIVE<br />
DIAMETER x LENGTH<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
TYPE<br />
Q'TY<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
Q'TY<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
COLOUR<br />
TYPE<br />
Q'TY<br />
MATERIAL<br />
DRIVE<br />
DIAMETER x LENGTH<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
MATERIAL<br />
COLOUR<br />
MATERIAL<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
MATERIAL<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
26<br />
ACC10CW ACC15CW ACC20CW<br />
1 2 2<br />
NA NA NA<br />
1 1 1<br />
NA NA NA<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.11 / 0.004<br />
0.12 / 1.24 0.12 / 1.26 0.18 / 1.89<br />
ROW<br />
3 3 3<br />
FIN PER INCH<br />
12 14 12<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
Q'TY<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
MATERIAL<br />
CENTRIFUGAL<br />
DIRECT<br />
160 x 202 / 6.3 x 8.0<br />
INDUCTION<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
CORRUGATED ALUMINIUM<br />
WASHABLE SARANNET<br />
PC/S 1 1 1<br />
mm 560 x 195 x 5 700 x 195 x 5 860 x 195 x 5<br />
in 22.1 x 7.7 x 0.2 27.6 x 7.7 x 0.2 33.9 x 7.7 x 0.2<br />
ELECTRO-GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
ACC25CW ACC28CW ACC30CW<br />
CENTRIFUGAL<br />
2 2 2<br />
NA NA NA<br />
DIRECT<br />
mm/in 160 x 202 / 6.3 x 8.0 185 x 203 / 7.3 x 8.0 210 x 203 / 8.4 x 8.0<br />
INDUCTION<br />
1 1 1<br />
NA NA NA<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
CORRUGATED ALUMINIUM<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.11 / 0.004<br />
0.20 / 2.19 0.24 / 2.62 0.28 / 2.98<br />
ROW<br />
3 3 3<br />
FIN PER INCH<br />
12 14 12<br />
WASHABLE SARANNET<br />
PC/S 1 2 2<br />
mm 995 x 195 x 5 456 x 210 x 5 449 x 305 x 5<br />
in 39.2 x 7.7 x 0.2 18.0 x 8.3 x 0.2 17.7 x 12.0 x 0.2<br />
ELECTRO-GALVANIZED MILD STEEL<br />
LIGHT GREY
Komponentdata - ACC-CW<br />
MODEL<br />
COIL<br />
CASING<br />
TYPE<br />
Q'TY<br />
FAN MATERIAL<br />
FAN MOTOR<br />
AIR FILTER<br />
MODEL<br />
FAN<br />
FAN MOTOR<br />
COIL<br />
AIR FILTER<br />
CASING<br />
DRIVE<br />
DIAMETER x LENGTH<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
Q'TY<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
COLOUR<br />
TYPE<br />
Q'TY<br />
MATERIAL<br />
DRIVE<br />
MATERIAL<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
MATERIAL<br />
DIAMETER x LENGTH<br />
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.<br />
27<br />
ACC38CW ACC40CW<br />
2 2<br />
NA NA<br />
1 1<br />
NA NA<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.11 / 0.004<br />
0.34 / 3.63 0.32 / 3.44<br />
ROW<br />
3 3<br />
FIN PER INCH<br />
14 12<br />
TYPE<br />
Q'TY<br />
INDEX OF PROTECTION (IP)<br />
TYPE<br />
TUBE<br />
FIN<br />
MATERIAL<br />
Q'TY<br />
SIZE ( L x W x t )<br />
MATERIAL<br />
COLOUR<br />
MATERIAL<br />
PC/S 2 2<br />
mm 608 x 230 x 5 507 x 305 x 5<br />
in 23.9 x 9.1 x 0.2 20.0 x 12.0 x 0.2<br />
mm/in<br />
DIAMETER mm/in<br />
THICKNESS mm/in<br />
MATERIAL<br />
CENTRIFUGAL FAN<br />
DIRECT<br />
214 x 203 / 8.4 x 8.0<br />
INDUCTION<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
CORRUGATED ALUMINIUM<br />
WASHABLE SARANNET<br />
ELECTRO-GALVANIZED MILD STEEL<br />
LIGHT GREY<br />
ACC50CW ACC60CW<br />
CENTRIFUGAL FAN<br />
2 2<br />
NA NA<br />
DIRECT<br />
214 x 203 / 8.4 x 8.0<br />
INDUCTION<br />
1 1<br />
NA NA<br />
CROSS FINNED TUBES<br />
PLAIN COPPER TUBE<br />
9.52 / 3/8<br />
0.33 / 0.013<br />
CORRUGATED ALUMINIUM<br />
THICKNESS mm/in<br />
FACE AREA m 2 / ft 2 0.11 / 0.004<br />
0.41 / 4.40 0.48 / 5.17<br />
ROW<br />
3 3<br />
FIN PER INCH<br />
12 12<br />
WASHABLE SARANNET<br />
PC/S 2 2<br />
mm 634 x 305 x 5 734 x 305 x 5<br />
in 25.0 x 12.0 x 0.2 29.0 x 12.0 x 0.2<br />
ELECTRO-GALVANIZED MILD STEEL<br />
LIGHT GREY
Inomhusdel<br />
Modell : AWM 07GW<br />
Inomhusdel<br />
Modell : AWM 10 / 15 GW<br />
5. DIMENSIONER<br />
28<br />
Dimension in mm<br />
Dimension in mm
Inomhusdel<br />
Modell : AWM 20 / 25GW<br />
Inomhusdel<br />
Modell : AWM 301W<br />
Dimension A B C D E<br />
AWM301W 1120.0 (44.1) 360.0 (14.2) 200.0 (7.9) 730.0 (28.7) 347.0 (13.7)<br />
All dimensions are in mm/ (in)<br />
29
Inomhusdel<br />
Modell : RCM 20 / 25 DW<br />
Inomhusdel<br />
Modell : RCM 30 / 40 / 50 DW<br />
30<br />
Dimension in mm<br />
MODEL A B C D E F G H I J K L M N O P Q<br />
RCM30DW 1174 75 1082 68 93 156 1214 57 670 216 319 879 517 100 47 100 53<br />
RCM40DW 1674 75 1582 68 93 156 1714 57 670 216 319 1379 517 95 40 100 45<br />
RCM50DW 1674 75 1582 68 93 156 1714 57 670 216 319 1379 517 95 40 100 45<br />
Dimension in mm
Inomhusdel<br />
Modell : ACK 20 / 25 / 30 / 40 / 50 AW<br />
Inomhusdel<br />
Modell : ACK 15 / 20 / 25 BW<br />
31<br />
Dimension in mm<br />
Dimension in mm
Inomhusdel<br />
Modell : ACK 10 / 15 / 20 CW<br />
Inomhusdel<br />
Modell : ACK 20 / 25 / 30 / 40 / 50 AWH<br />
32<br />
Dimension in mm<br />
Water Inlet/Outlet 1 = connection to chiller<br />
Water Inlet/Outlet 2 = connection to boiler<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 10 / 15CW<br />
MODEL A B C D E F G H I J K L M N O<br />
ACC10CW 31 741 702 662 10 765 72 261 411 349 225 261 171 118 77<br />
ACC15CW 31 881 841 802 10 905 72 261 411 349 225 261 171 118 77<br />
Inomhusdel<br />
Modell : ACC 20 / 25 CW<br />
33<br />
Dimension in mm<br />
MODEL A B C D E F G H I J K L M N O P<br />
ACC20CW 31 1041 1002 962 10 1065 72 261 411 349 225 261 174 128 55 55<br />
ACC25CW 31 1176 1137 1097 10 1200 72 261 411 349 225 261 171 118 77 54<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 28CW<br />
34<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 30CW<br />
35<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 38CW<br />
36<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 40CW<br />
37<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 50CW<br />
38<br />
Dimension in mm
Inomhusdel<br />
Modell : ACC 60CW<br />
39<br />
Dimension in mm
Modell : AWM 07 / 10 / 15GW<br />
Modell : AWM 20 / 25 GW<br />
6. ELSCHEMA<br />
40
Modell : RCM 20 / 25 / 30 / 40 / 50DW<br />
Modell : RCM 07 / 15 CBW<br />
41
Modell : ACK 20 / 25 / 30 / 40 / 50AW<br />
Modell : ACK 15 / 20 / 25 BW<br />
42
Modell : ACK 10 / 15 / 20CW<br />
Modell : ACK 20 / 25 / 30 / 40 / 50 AWH<br />
43
Modell : ACC 10 / 15 / 20 / 25CW<br />
Modell : ACC 28 / 30 / 38 / 40 / 50 / 60CW<br />
44
AWM - GW<br />
Innedelen måste installeras så att kortslutning av luftflödet<br />
in och ut ur aggregatet inte kan uppstå. Följ montage<br />
anvisningens minsta avstånd till hinder se bild nedan.<br />
Placera inte innedelen där den kan utsättas för direkt<br />
solljus. Se också till att det är möjligt att förlägga kondens-<br />
avlopp och vattenrör, samt att innedelen inte är ivägen<br />
för dörrar och fönster.<br />
Montage plåt<br />
Se till att väggen är kraftig nog för att klara av innedelens tyngd.<br />
Annars måste väggen förstärkas.<br />
Använd vattenpass och fäst plåten med 4 skruvar.<br />
Om rören skall förläggas genom väggen förborra med65mm<br />
hålsåg, borra så att hålet blir något lägre på utsidan(se bild).<br />
Håltagning<br />
Borra vägggenomföringen med ett lätt fall<br />
från insidan ut.<br />
7. INSTALLATION<br />
Montera innedelen på montageplåten<br />
Häng upp innedelen på de övre hållarna på montageplåten,<br />
se till att innedelen får ordentligt fäste genom att<br />
skjuta innedelen försiktigt i sidled.<br />
Kondensvattenavlopp<br />
Se till att kondensavloppet är förlagt med fall från<br />
innedelen. Se bild.<br />
45
Vattenröranslutning<br />
Fläktkonvektorn är försedd med oislerade anslutningar för in och utgående rörledningar. På batteriets högsta punkt<br />
finns en avluftningsventil monterad. Tryck på ventilen för att avlufta batteriet.<br />
En trevägsventil krävs för att stänga av eller reglera vätskeflödet till fläktkonvektorn.<br />
Svarta stålrör, kopparrör, PVC-rör eller polyetenrör kan användas. Material måste väljas med hänsyn till typ av vätska mm.<br />
Alla köldbärarledningar och anslutningar måste isoleras mot kondens med syntetiskt cellgummi typ armaflex eller liknande.<br />
Använd ej invändigt nedsmutsade rör eller skadade rör och rördelar till inst<strong>alla</strong>tionen.<br />
Vissa huvudkomponenter är nödvändiga att montera i rörsystemet för att öka kapaciteten och förenkla vid service, t ex<br />
avstängningsventiler, injusteringsventiler, filter, silar, 2 eller 3-vägsventiler mm.<br />
ELANSLUTNINGAR<br />
Modell WM07GW / WM10GW / WM15GW WM20GW / WM25GW<br />
Spänningsområde 220V – 240V/1Ph / 50Hz +<br />
Kabelstorlek mm2 1.5 1.5<br />
Antal kardeler 3 3<br />
Rekommenderad avsäkring A 10 10<br />
Chiller<br />
WM07-25GW<br />
46<br />
3 way valve<br />
Relay (220-240V, 10A)
Varning<br />
Skarpa kanter och batteriets flänsar utgör potentiell risk för skärskador. Undvik direktkontakt med dem.<br />
FÖRSTA FÖRBEREDELSER<br />
• Den elektriska matningen samt el- / rörinst<strong>alla</strong>tioner ska följa gällande föreskrifter och bestämmelser.<br />
• Spänningen får inte variera mer än ±10% av nominell spänning. Elmatningen får inte innehålla<br />
några svetstransformatorer, eftersom de orsakar stora störningar och ostabilitet i elnätet.<br />
• Montera enheten på en plats som är lämplig för rördragning och elinst<strong>alla</strong>tion.<br />
• Enheten ska monteras så att luften från enheten kan få fritt flöde ut och spridas i rummet, och inte<br />
hindras av belysningsarmaturer, balkar mm. Inte heller returluften in till enheten får hindras.<br />
STANDARDMONTAGE<br />
Försäkra er om att taket är tillräckligt starkt att bära vikten av enheten. Montera pendlarna för upphängningen<br />
(väggmontagejärn vid golvuppställning) i rätt läge enligt måtten som visas i figur A. Kontrollera<br />
att infästningen av pendlarna är riktigt förankrade och att enheten monteras i våg. Observera att det<br />
för kondensvattnets avrinning dock ska vara en viss lutning enligt vad som rekommenderas i figur B.<br />
odell RCM 20D RCM 25D RCM 30D RCM 40D RCM50D<br />
1214 1214 1214 1714 1714<br />
666 666 666 666 666<br />
273 273 273 273 273<br />
130 130 130 130 130<br />
F 1160 1160 1560 1560 1560<br />
27 27 27 27 27<br />
77 77 77 77 77<br />
745 745 745 1235 1235<br />
25 25 25 25 25<br />
209 209 209 331 331<br />
486 486 486 486 486<br />
108 108 108 108 108<br />
360 360 360 600 600<br />
770 770 770 1270 1270<br />
136 136 136 136 136<br />
Q 373 373 373 373 373<br />
222 222 222 310 310<br />
Observera! Alla mått är angivna i mm.<br />
Figur B<br />
47<br />
- RCM - DW<br />
10 mm<br />
10 mm högre<br />
Figur A
Vid montaget ska man se till att:<br />
• enheten får den i figur B rekommenderade lutningen för avrinning av kondensvattnet.<br />
• enheten runt om får ett fritt utrymme enligt figur C, vilket förenklar service och ger rätt luftflöde.<br />
• enheten monteras så att det inte uppstår någon kortslutning mellan den behandlade utblåsningsluften<br />
och den inkommande returluften.<br />
• enheten inte monteras så att den utsätts för direkt solbestrålning. Vidare ska montageplatsen vara<br />
lämplig för montage av rörledningar. Placera enheten långt ifrån dörren och så att drag inte uppstår.<br />
Figur C<br />
INSTALLATION - DELVIS INFÄLLT TAKMONTAGE<br />
• Kontrollera att enheten riktas in på rätt sätt i förhållande till undertaket.<br />
• Fritt utrymme runt enheten krävs enligt vad som framgår av figur D.<br />
Figur D<br />
TAKMODELL MÖBLER, INBYGGDA BYGGNADS-<br />
TEKNISKA KONSTRUKTIONER MM<br />
FÅR INTE SKJUTA UT MER ÄN 250 MM<br />
Undertakspanel<br />
48<br />
GOLVMODELL<br />
Enhetens överkant
ÖPPET TAKMONTAGE<br />
STEG 1<br />
Ta bort returluftgaller, sidopanel, sidotäckplåt och montagekonsol från enheten (se fig E).<br />
Figur E<br />
STEG 2<br />
Montera montagekonsolerna enligt de mått som anges i fig A (se fig F).<br />
Figur F<br />
STEG 3<br />
Häng upp enheten och spänn fast bultarna. När rör- och elinst<strong>alla</strong>tionerna är färdiga sätts de<br />
borttagna komponenterna - returluftgaller, sidopanel och sidotäckplåt - tillbaks på enheten<br />
(se fig G).<br />
Figur G<br />
49<br />
Returluftgaller<br />
Sidotäckplåt<br />
Montagekonsol<br />
Sidopanel
GOLVMONTAGE<br />
STEG 1<br />
Ta bort returluftgaller, sidopanel, sidotäckplåt och montagekonsol från enheten (se fig E).<br />
STEG 2<br />
Sätt fast vägg*- och uppställningskonsolerna enligt de mått som anges i fig A, och sätt upp<br />
enheten (se fig H).<br />
Figur H<br />
STEG 3<br />
Anslut rörledningarna enligt något av de två olika inkopplingsalternativen i fig J.<br />
Rörledningar<br />
genom bakre plåten<br />
Inst<strong>alla</strong>tion av rörledningar<br />
Figur J<br />
50<br />
* Väggkonsoler levereras<br />
som extra tillbehör mot<br />
särskild beställning.<br />
Vägg<br />
Rörledningar<br />
genom bottenplåten
ANSLUTNING AV KÖLD- ELLER VÄRMEBÄRARLEDNINGAR<br />
- Fläktkonvektorn är försedd med oisolerade anslutningar för in- och utgående rörledningar. På batteriets<br />
högsta punkt finns en avluftningsventil monterad. Tryck på ventilen för att avlufta batteriet.<br />
- En 3-vägs magnetventil eller reglerventil krävs för att stänga av eller reglera vätskeflödet till enheten.<br />
- Svarta stålrör, kopparrör, PVC-rör eller polyetenrör kan användas. Material måste väljas med hänsyn<br />
till typ av vätska mm.<br />
- Alla köldbärarledningar och anslutningar måste isoleras mot kondens med syntetiskt cellgummi typ<br />
Armaflex eller liknande.<br />
- Använd ej invändigt nedsmutsade rör eller skadade rör och rördelar till inst<strong>alla</strong>tionen.<br />
- Vissa huvudkomponeneter är nödvändiga att montera i rörsystemet för att öka kapaciteten och förenkla<br />
vid service, t ex avstängningsventiler, injusteringsventiler, filter, silar, 2- eller 3-vägsventiler mm.<br />
- Tänk på rörledningarnas termiska expansion. Montera dem med erforderliga fixeringar och fästdon<br />
som tillåter att de kan expandera och dra ihop sig.<br />
KONDENSVATTENAVLOPP (Vid kyldrift)<br />
Fläktkonvektor<br />
Rörklamma<br />
RÄTT FEL<br />
TÄTHETSPROVNING AV KONDENSVATTENAVLOPPET<br />
Fyll på vatten<br />
Flexibel slang<br />
Kondensvattenledning<br />
• För en bra avrinning bör kondensvattenledningen<br />
luta i strömningsriktningen.<br />
• Undvik bakfall på ledningen.<br />
• Undvik uppåtgående böjar.<br />
• Var försiktig vid inkopplingen av kondensvattenledningen<br />
till enheten så<br />
att anslutningen inte skadas.<br />
• Ytterdiameter för kondensvattenanslutningens<br />
flexibla slang är 20 mm.<br />
• För att förhindra kondensvatten att<br />
droppa från kondensvattenledningen<br />
ska ledningen isoleras med minst<br />
8 mm syntetiskt cellgummi eller<br />
liknande.<br />
• Anslut den inkommande rörledningen<br />
till den flexibla slangen.<br />
• Fyll ledningen från andra änden av<br />
slangen och kontrollera om den läcker.<br />
• När kontrollen är klar ska den flexibla<br />
slangen fästas även på enhetens<br />
kondensvattenanslutning.<br />
OBS! Enheterna har ingen inbyggd pump för kondensvattnet. En separat pump måste<br />
monteras om självfall till ett avlopp ej kan fås för kondensvattenledningen.<br />
51
ELEKTRISKA ANSLUTNINGAR<br />
Nedanstående elschema visar endast ett principiellt förslag till elektrisk inkoppling. Utförandet kan<br />
ändras beroende på typ av vätskekylaggregat, rörsystemets utformning, elektriska föreskrifter, styr-<br />
och reglertekniska orsaker, om det avser kylning eller värmning samt egna önskemål.<br />
Fläktkonvektor 1<br />
COMP L N<br />
3wv<br />
x1<br />
Vätsakekylaggregat<br />
MODELL RCM 20DW - RCM 50DW<br />
Fläktkonvektor 2<br />
COMP L N<br />
3wv<br />
ALLMÄNNA KONTROLLER<br />
x2<br />
52<br />
3wv<br />
Fläktkonvektor 3<br />
COMP L N<br />
3wv<br />
x3<br />
3-vägs magnetventil<br />
x1, x2, x3 Relä (240V, 10A)<br />
Den elektriska inkoppling av en fläktkonvektor måste följa gällande föreskrifter och bestämmelser.<br />
Kontrollera alltid följande punkter:<br />
1) att enheterna är riktigt och säkert infästade och är i rätt läge.<br />
2) att inga läckor finns i anslutningar och rörledningar.<br />
3) att elinst<strong>alla</strong>tionen är utförd enligt gällande föreskrifter.<br />
4) att kondensvattenavrinningen fungerar. Häll lite vatten på droppfatets västra sida och se om det<br />
rinner ut på den högra sidan.<br />
OBSERVERA!<br />
- Dessa anvisningar avser endast de angivna <strong>modeller</strong>na av fläktkonvektorer. För inst<strong>alla</strong>tionen av<br />
vätskekylaggregat, värmesystem mm, hänvisas till gällande anvisningar för de enheterna.<br />
- Inst<strong>alla</strong>tion och inkoppling av enheterna kan variera beroende på valt vätskekylaggregat, värmesystem<br />
och på systemutformningen.<br />
- Inst<strong>alla</strong>tionen ska utföras av kompetenta personer med erfarenhet av denna typ av produkt.<br />
R<br />
S<br />
T<br />
N
FÖRSTA FÖRBEREDELSER<br />
• Den elektriska matningen samt el- / rörinst<strong>alla</strong>tioner ska följa gällande föreskrifter och bestämmelser.<br />
• Spänningen får inte variera mer än ±10% av nominell spänning. Elmatningen får inte innehålla<br />
några svetstransformatorer, eftersom de orsakar stora störningar och ostabilitet i elnätet.<br />
• Montera enheten på en plats som är lämplig för rördragning och elinst<strong>alla</strong>tion.<br />
• Enheten ska monteras så att luften från enheten kan få fritt flöde ut och spridas i rummet, och inte<br />
hindras av belysningsarmaturer, balkar mm. Inte heller returluften in till enheten får hindras.<br />
• Minimimått för fritt utrymme runt en enhet framgår av nedanstående ritning.<br />
• För att förhindra att vibrationer och ljudstörningar ska uppstå, måste underlaget i vilket takkassetten<br />
ska fästas vara så starkt att det klarar en vikt fyra gånger vikten av den enhet som ska monteras.<br />
• Inst<strong>alla</strong>tionsplatsen i undertaket måste vara i våg, och fri höjd ovan undertak måste vara 350 mm<br />
eller mer.<br />
INSTALLATION<br />
INSTALLATION ACK - CW/AW<br />
890 el. 600 mm (öppning i undertak )<br />
790 el. 538 mm<br />
Takkassett 820 mm<br />
Kassett<br />
Takkassett 820 mm<br />
620,5 el. 505 mm (pendlar)<br />
890 el. 600 mm (öppning i undertak )<br />
Pil för riktning av<br />
RÖR-ledningar<br />
Varning<br />
Skarpa kanter och batteriets flänsar utgör potentiell risk för skärskador. Undvik direktkontakt med dem.<br />
Min 1,0 m<br />
Hinder<br />
Max 3,0 m<br />
Golv<br />
Min 0,5 m Min 0,5 m<br />
53<br />
Min 0,5 m<br />
• Enheten ska ej monteras i närheten av aggregat<br />
för uppvärmning (vid kyla) eller befuktning.<br />
Undvik att montera den nära entredörrar.<br />
• Mät och märk ut infästningspunkterna för<br />
pendlarna. Borra hålen för pendlarnas infästningar<br />
i taket och montera pendlarna.<br />
• Inst<strong>alla</strong>tionsmallen kan ändras beroende på<br />
inverkan av temperatur och luftfuktighet.<br />
Kontrollera alltid måtten på plats.<br />
• Måtten på inst<strong>alla</strong>tionsmallen motsvarar den<br />
öppning som krävs för enheten i undertaket.<br />
• Montera inst<strong>alla</strong>tionsmallen för enheten<br />
innan arbetet med undertaket påbörjas.<br />
OBSERVERA! Gå igenom borrningen i taket med <strong>alla</strong> berörda parter innan arbetet påbörjas.<br />
Balk<br />
Max 0,3 m
UPPHÄNGNING<br />
Fläktkonvektor<br />
54<br />
35 mm<br />
Undertaksskiva<br />
• Kontrollera att delningen för upphängningspendlarna är enligt dimensionsritningen.<br />
• Lyft upp enheten och häng den i pendlarna med hjälp av muttrar och brickor.<br />
• Justera höjden mellan enhetens underkant och underkant på undertaket. Måttet ska<br />
vara 35 mm.<br />
• Kontrollera med ett vattenpass eller liknande att takkasetten är monterad i våg.<br />
Dra fast bultar och muttrar för att förhindra att enheten vibrerar och faller ned.<br />
• Öppna upp undertakspanelerna runt den yttre kanten av inst<strong>alla</strong>tionsmallen.<br />
KONDENSVATTENAVLOPP<br />
Fläktkonvektor<br />
Rörklamma<br />
RÄTT FEL<br />
TÄTHETSPROVNING AV KONDENSVATTENAVLOPPET<br />
Fyll på vatten<br />
Flexibel slang<br />
Kondensvattenledning<br />
• För en bra avrinning bör kondensvattenledningen<br />
luta i strömningsriktningen.<br />
• Undvik bakfall på ledningen.<br />
• Undvik uppåtgående böjar.<br />
• Var försiktig vid inkopplingen av kondensvattenledningen<br />
till enheten så<br />
att anslutningen inte skadas.<br />
• Ytterdiameter för kondensvattenanslutningens<br />
flexibla slang är 20 mm.<br />
• För att förhindra kondensvatten att<br />
droppa från kondensvattenledningen<br />
ska ledningen isoleras med minst<br />
8 mm syntetiskt cellgummi eller<br />
liknande.<br />
• Anslut den inkommande rörledningen<br />
till den flexibla slangen.<br />
• Fyll ledningen från andra änden av<br />
slangen och kontrollera om den läcker.<br />
• När kontrollen är klar ska den flexibla<br />
slangen fästas även på enhetens<br />
kondensvattenanslutning.<br />
OBS! Enheterna har en inbyggd pump för kondensvattnet. Installera enheterna i våg<br />
för att förhindra kondensvattenläckage och kondens runt utblåsningsgallret.
INSTALLATION AV FRONTPANELEN<br />
• Frontpanelens ram kan monteras endast i en riktning som bestäms utifrån riktningen på rörledningarnas<br />
anslutning. På frontpanelens ram sitter en skylt med en pil som indikerar rörens<br />
riktning i förhållande till ramen.<br />
• Ta bort inst<strong>alla</strong>tionsmallen innan frontpanelen monteras.<br />
• Öppna returluftgallret genom att dra spärrhakarna bakåt. Ta bort gallret och luftfiltret från<br />
ramen.<br />
• Montera fronpanelens ram på enheten med fyra skruvar. Se till att anslutningen blir tät så<br />
att inget luftläckage uppstår.<br />
• Anslut kontrollkabeln och kabeln från luftriktarnas motor till enheten.<br />
Från<br />
frontpanelen<br />
ÖPPNA<br />
OBS! Var noga med att det blir en tät anslutning mellan enheten och frontpanelen. Luftläckage<br />
kan leda till kondens med droppande vatten samt störande ljud som följd.<br />
Tilluft<br />
Kontrollkabel<br />
Kabel till<br />
luftriktarnas motor<br />
Aggregat<br />
Undertaksskiva<br />
Frontpanel<br />
55<br />
Luftläckage<br />
Kontrollpanel<br />
Tilluft<br />
RÄTT FEL<br />
SKRUVAR<br />
Luftläckage<br />
Undertaksskiva<br />
Frontpanel
RETURLUFTGALLER<br />
• Se till att luftfiltret är riktigt fastsatt i returluftgallret<br />
innan gallret monteras.<br />
• Sätt fast returluftgallret och dess filter i frontpanelens<br />
ram.<br />
• Returluftgallret kan monteras i valfri riktning.<br />
När det monteras bör man ta hänsyn till<br />
undertakets utformning och gallrets funktion.<br />
• Om enheten ska utrustas med ett joniseringsfilter<br />
(extra tillbehör), måste detta filter<br />
monteras på luftfiltret innan gallret monteras.<br />
• Fäst joniseringsfiltret på luftfiltret med den<br />
svarta sidan uppåt och den vita sidan nedåt.<br />
• Sätt försiktigt fast joniseringsfiltrets filterram.<br />
FILTERRAM<br />
(TILLBEHÖR)<br />
JONISERINGSFILTER<br />
(TILLBEHÖR)<br />
LUFTFILTER<br />
(STANDARD)<br />
VENTILATIONSKANALER<br />
Enheterna är försedda med "knock-out" hål för anslutning av korta kanaler för intags- och utblåsningsluft.<br />
Observera att anslutningen av en kanal för utblåsningsluften är möjlig endast på ena sidan.<br />
Användning av en extra kanal med ett tilluftdon för utblåsningsluften förbättrar luftdistributionen när<br />
det finns ett hinder (t ex en belysningsarmatur) i vägen, eller i ett avlångt eller L-format rum. De kan<br />
också användas för att samtidigt betjäna två rum.<br />
Möjliga riktningar för anslutning av kanaler för intags- och utblåsningsluft<br />
Utblåsningsluft<br />
Luftintag<br />
Utblåsningsluft Utblåsningsluft<br />
Dimensioner på "knock-out" öppningar<br />
119 90<br />
10 50 50 50 50 50 10<br />
115 20 115<br />
20<br />
70<br />
20<br />
109<br />
Utblåsningsluft<br />
"Knock-out" öppningar för utblåsningsluft "Knock-out" öppning för intagsluft<br />
SÄTTA IGEN EN UTBLÅSNINGSÖPPNING<br />
Ø100<br />
Ø140<br />
Observera!<br />
• Kanalerna måste vara täta så att<br />
inget luftläckage uppstår.<br />
• För att undvika att kondens bildas<br />
på kanalen för inblåsningsluft<br />
måste kanalen isoleras.<br />
• Håll inblandningen av uteluft under<br />
20% av totala luftmängden.<br />
Det är nödvändigt att installera<br />
en hjälpfläkt för uteluften.<br />
- Det är möjligt att sätta igen en av de fyra utblåsningsöppningarna. Fler igensatta öppningar kan orsaka en<br />
dålig funktion. Demontera frontpanelen och sätt fast tätningsmaterialet i den öppning som ska sättas igen.<br />
- Om den korta öppningen ska sättas igen kan tätningsmaterialet kapas till lämplig längd.<br />
- Skjut in tätningsmaterialet ca 10 mm bakom undersidan av enheten, så att det inte kommer i kontakt med<br />
gallret. Var noga med att inte skjuta in tätningsmaterialet längre in än ca 10 mm.<br />
56
ANSLUTNING AV KÖLD- ELLER VÄRMEBÄRARLEDNINGAR<br />
- Fläktkonvektorn är försedd med oisolerade anslutningar för in- och utgående rörledningar. På batteriets<br />
högsta punkt finns en avluftningsventil monterad. Tryck på ventilen för att avlufta batteriet.<br />
- En 3-vägs magnetventil eller reglerventil krävs för att stänga av eller reglera vätskeflödet till enheten.<br />
- Svarta stålrör, kopparrör, PVC-rör eller polyetenrör kan användas. Material måste väljas med hänsyn<br />
till typ av vätska mm.<br />
- Alla köldbärarledningar och anslutningar måste isoleras mot kondens med syntetiskt cellgummi typ<br />
Armaflex eller liknande.<br />
- Använd ej invändigt nedsmutsade rör eller skadade rör och rördelar till inst<strong>alla</strong>tionen.<br />
- Vissa huvudkomponeneter är nödvändiga att montera i rörsystemet för en god funktion och för att förenkla<br />
vid service, t ex avstängningsventiler, injusteringsventiler, filter, silar, 2- eller 3-vägsventiler mm.<br />
- Tänk på rörledningarnas termiska expansion. Montera dem med erforderliga fixeringar och fästdon<br />
som tillåter att de kan expandera och dra ihop sig.<br />
ELEKTRISKA ANSLUTNINGAR<br />
Nedanstående elschema visar endast ett principiellt förslag till elektrisk inkoppling. Utförandet kan<br />
ändras beroende på typ av vätskekylaggregat, rörsystemets utformning, elektriska föreskrifter, styroch<br />
reglertekniska orsaker, om det avser kylning eller värmning samt egna önskemål.<br />
Fläktkonvektor 1<br />
COMP L N<br />
3wv<br />
x1<br />
Vätsakekylaggregat<br />
MODELL ACK 20AW - ACK 50AW<br />
Fläktkonvektor 2<br />
COMP L N<br />
3wv<br />
ALLMÄNNA KONTROLLER<br />
x2<br />
3wv 3-vägs magnetventil<br />
x1, x2, x3 Relä (240V, 10A)<br />
57<br />
Fläktkonvektor 3<br />
COMP L N<br />
Den elektriska inkoppling av en fläktkonvektor måste följa gällande föreskrifter och bestämmelser.<br />
Kontrollera alltid följande punkter:<br />
1) att fläktkonvektorerna är riktigt och säkert infästade och är i rätt läge.<br />
2) att inga läckor finns i anslutningar och rörledningar.<br />
3) att elinst<strong>alla</strong>tionen är utförd enligt gällande föreskrifter.<br />
4) att kondensvattenavrinningen fungerar. Häll lite vatten på droppfatets västra sida och se om det<br />
rinner ut på den högra sidan.<br />
OBSERVERA!<br />
- Dessa anvisningar avser endast de angivna <strong>modeller</strong>na av fläktkonvektorer. För inst<strong>alla</strong>tionen av<br />
vätskekylaggregat, värmesystem mm, hänvisas till gällande anvisningar för de enheterna.<br />
- Inst<strong>alla</strong>tion och inkoppling av enheterna kan variera beroende på valt vätskekylaggregat, värmesystem<br />
och på systemutformningen.<br />
- Inst<strong>alla</strong>tionen ska utföras av kompetenta personer med erfarenhet av denna typ av produkt.<br />
3wv<br />
x3<br />
R<br />
S T<br />
N
Inomhusdel<br />
INSTALLATION ACC - CW<br />
Vattenledningar<br />
INSTALLATION AV INOMHUSDELEN<br />
- Den elektriska matningen samt el- och rörinst<strong>alla</strong>tioner ska följa gällande föreskrifter och bestämmelser.<br />
- Enheten ska monteras så att luften ifrån enheten kan få fritt flöde ut och spridas i rummet, och inte hindras<br />
av belysningsarmaturer, balkar mm. Inte heller returluften in till enheten får hindras.<br />
- Använd medföljande upphängnings-konsoler vid montaget.<br />
- Försäkra dig om att taket är starkt nog att upprätthålla aggregatets vikt.<br />
Center mått för upphängning. Montera enligt anvisning för optimalt luftflöde och<br />
utrymme för service.<br />
58<br />
Chiller<br />
CHILLER<br />
ACC 10CW 15CW 20CW 25CW 28CW 30CW 38CW 40CW 50CW 60CW<br />
A (mm) 741 881 1041 1176 959 956 1264 1076 1326 1526<br />
L (mm) 225 225 225 225 339 266 401 266 266 266<br />
ELEKTRISKA ANSLUTNINGAR<br />
AC C 10C W - AC C 25C W<br />
MODELL C C 10C W C C 15C W C C 20C W C C 25C W<br />
Spänningsområde 220V - 240V / 1Ph / 50Hz + ! or 208V - 230V / 1Ph / 60Hz + !<br />
Rekommenderad avsäkring A 10 10 10 10<br />
Kabeldimension matning mm 2 1.5 1.5 1.5 2.5<br />
Antal kardeler 3 3 3 3<br />
Kabeldimension manöver mm 2 1.5 1.5 1.5 1.5<br />
Antal kardeler 3 3 3 3<br />
10 mm<br />
10 mm<br />
E nglish
AC C 28C W - AC C 60C W<br />
MODELL C C 28 / 30C W C C 38 / 40 C W C C 50C W C C 60C W<br />
Spänningsområde 220V - 240V / 1Ph / 50Hz + ! or 208V - 230V / 1Ph / 60Hz + !<br />
Rekommenderad avsäkring A 16 16 16 16<br />
Kabeldimension matning mm 2 2.5 2.5 2.5 2.5<br />
Antal kardeler 3 3 3 3<br />
Kabeldimension manöver mm 2 1.5 1.5 1.5 1.5<br />
Antal kardeler 3 3 3 3<br />
VIKTIGT: Tabellen är rekommendationer ifrån leverantören. I första hand så ska nationella<br />
och lokala regler och rekommendationer följas.<br />
C hiller<br />
Gate Valve<br />
RÖRANSLUTNINGAR<br />
- Fläktkonvektorn är försedd med oisolerade anslutningar för in- och utgående rörledningar. På batteriets högsta punkt<br />
finns en avluftningsventil monterad. Tryck på ventilen för att avlufta batteriet.<br />
- En 3-vägs magnetventil eller reglerventil krävs för att stänga av eller reglera vätskeflödet till enheten.<br />
- Svarta stålrör, kopparrör, PVC-rör eller polyetenrör kan användas. Material måste väljas med hänsyn till typ av vätska mm.<br />
- Alla köldbärarledningar och anslutningar måste isoleras mot kondens med syntetiskt cellgummi typ armaflex eller liknande.<br />
- Använd ej invändigt nedsmutsade rör eller skadade rör och rördelar till inst<strong>alla</strong>tionen.<br />
- Vissa huvudkomponeneter är nödvändiga att montera i rörsystemet för en god funktion och för att förenkla vid service,<br />
t ex avstängningsventiler, injusteringsventiler, filter, silar, 2- eller 3-vägsventiler mm.<br />
Gate Valve Three Way Valve<br />
FCU<br />
59<br />
Gate Valve<br />
Gate Valve<br />
Two Way Valve<br />
FCU<br />
Gate Valve<br />
Gate Valve<br />
G ood C ontrolling B ad C ontrolling Worst C ontrolling<br />
ELEKTRISKA ANSLUTNINGAR<br />
FCU 1 FCU 2 FCU 3<br />
FL FM FH TH COMP L N FL FM FH TH COMP L N FL FM FH TH COMP L N<br />
x1<br />
C C 10C W ~C C 25C W (without controller)<br />
TH TH<br />
3wv<br />
3wv<br />
x2<br />
C hiller<br />
3wv<br />
x3<br />
TH<br />
3wv<br />
x1, x2, x3 R elay (220-240V, 10A)<br />
TH Thermostat<br />
S<br />
R<br />
T<br />
S olenoid Valve for 3 way valve<br />
N<br />
FCU
COMP L N<br />
3wv<br />
FCU 1<br />
C hiller<br />
x1<br />
C C 10C W ~C C 25C W (with netware-1 controller)<br />
COMP L N<br />
3wv<br />
FCU 2<br />
x2<br />
60<br />
3wv<br />
FCU 3<br />
COMP L N<br />
3wv<br />
x3<br />
S olenoid Valve for 3 way valve<br />
x1, x2, x3 R elay (220-240V, 10A)<br />
R<br />
S T<br />
N
8. Fjärrkontroll<br />
Rätt fjärrkontroll till rätt fancoil<br />
MODELL STANDARD CONTROLLER OPTIONAL CONTROLLER<br />
AWM - GW G12 (Wireless) NETWARE3 / SLM3 (Wired)<br />
AWM 301W G8 (Wireless) NETWARE3 / SLM3 (Wired)<br />
ACK - AW / BW / CW / AWH G8 (Wireless) NETWARE3 / SLM3 (Wired)<br />
ACM - DW / CBW / EW G8 (Wireless) NETWARE3 / SLM3 (Wired)<br />
ACC - CW NETWARE3 / SLM3 (Wired) -<br />
ADB - BW Without Controller<br />
Felindikering ifrån aggregat<br />
Error Indication Cool LED 7 Segment Display<br />
Room Sensor error (short/open) Blinks 1 times E1<br />
Pipe Water Sensor Error (short/open) Blinks 2 times E2<br />
Water Pump Error Blinks 6 times E6<br />
Pipe Water Temperature Fault Blinks 5 times E5<br />
* Window Open Activated Blinks 3 times -<br />
* Antifreeze Mode Activated Blinks 7 times -<br />
* Load Shedding Activated Blinks 8 times -<br />
* Only applicable for 4-pipe system<br />
61
4<br />
6<br />
10<br />
8<br />
Part Nr.: A08019013163<br />
Trådlös fjärrkontroll - modell G8<br />
AM<br />
PM<br />
SWING<br />
AUTO<br />
CLOCK<br />
ON<br />
OFF<br />
62<br />
MIN<br />
HR FC<br />
ON TIMER SET CLR<br />
SET CLR<br />
OFF TIMER<br />
MODE<br />
SLEEP<br />
1<br />
2<br />
3<br />
7<br />
5<br />
9<br />
11<br />
12
FUNKTIONER<br />
1. Transmitter (sändare)<br />
• Sänder signalerna till den enhet som ska styras.<br />
2. Indikering av transmission<br />
• Indikerar med en blinkning att det senaste kommandot har sänts till enheten.<br />
3. Till / Från<br />
• Tryck en gång för att starta en enhet.<br />
• Tryck en gång till för att stoppa den.<br />
4. Temperaturinställning<br />
• Tryck på ▲ för att öka inställningsvärdet och på ▼ för att minska inställningsvärdet för den önskade<br />
rumstemperaturen.<br />
• Inställningsområdet för rumstemperaturen är 16°C till 30°C. (En specialvariant har 18°C till 30°C.)<br />
• Tryck samtidigt på de båda knapparna ▲ och ▼ för att växla temperaturvisningen mellan °C och °F.<br />
5. Arbetssätt<br />
• Tryck på knappen MODE för att välja ett av följande arbetssätt för en enhet:<br />
- Luftkonditioneringsenheter: COOL (kyla), DRY (avfuktning) och FAN (fläkt).<br />
- Värmepumpar: AUTO, COOL (kyla), DRY (avfuktning) , FAN (fläkt) och HEAT (värme).<br />
6. Inställning av fläktvarvtal<br />
• Håll knappen oavbrutet intryckt, varvid fläkthastigheterna bläddras fram i följande ordning:<br />
Low (låg) –––: Med (mellan) –––: High (hög) –––: Auto<br />
• Släpp knappen när det önskade alternativet visas i displayen.<br />
7. Turbo-funktion (extra tillbehör)<br />
• Tryck på knappen för en snabb nedkylning eller en snabb uppvärmning (endast värmepumpar).<br />
• Rumstemperaturen kommer att sjunka om enhetens arbetssätt är COOL (kyla) eller DRY (avfuktning)<br />
alternativt att öka om enhetens arbetssätt är HEAT (värme).<br />
Fläkten kommer att öka till högsta hastighet, om hastigheten inte redan är den högsta.<br />
• Temperatur och fläkt återgår till inställda värden efter 20 minuter eller om man trycker på igen.<br />
• Funktionen fungerar endast i arbetssätten COOL (kyla), DRY (avfuktning) och HEAT (värme).<br />
8. Timerfunktion - Tillslag<br />
• Tryck på SET på knappen ON TIMER för att aktivera enhetens funktion för automatiskt tillslag.<br />
• Ställ in tidpunkten för tillslaget genom att hålla knappen SET intryckt tills önskat klockslag visas.<br />
AM innebär klockslag mellan 00.00 - 12.00 och PM innebär klockslag mellan 12.00 - 24.00.<br />
• Tryck på CLR på knappen ON TIMER för att deaktivera den automatiska tillslagsfunktionen.<br />
9. Timerfunktion - Frånslag<br />
• Tryck på SET på knappen OFF TIMER för att aktivera enhetens funktion för automatiskt frånslag.<br />
• Ställ in tidpunkten för frånslaget genom att hålla knappen SET intryckt tills önskat klockslag visas.<br />
• Tryck på CLR på knappen OFF TIMER för att deaktivera den automatiska frånslagsfunktionen.<br />
10. Automatiska rörliga luftriktare (extra tillbehör)<br />
• Tryck på knappen SWING för att starta de rörliga luftriktarna.<br />
• Om man önskar att ha de rörliga luftriktarna stående i ett speciellt läge, väntar man tills de kommer<br />
dit och trycker ännu en gång på knappen varvid de stannar.<br />
11. Nattändring av temperaturen<br />
• Tryck på knappen SLEEP för att aktivera nattändringsfunktionen.<br />
• Detta är en energibesparande funktion. När en enhet är i kyldrift<br />
kommer den inställda rumstemperaturen öka med 0,5°C efter en<br />
halvtimme, öka med 1°C efter en timme och öka med 2°C efter<br />
två timmar. Denna funktion gör att ett rum inte kyls ner i onödan<br />
när det inte används.<br />
• När en värmepump är i värmedrift kommer inställd rumstemperatur<br />
att sänkas med 0,5°C efter en halvtimme, sänkas med 1°C efter<br />
en timme och sänkas med 2°C efter två timmar. Denna funktion<br />
gör att ett rum inte värms upp i onödan när det inte används.<br />
• Nattändringsfunktionen kopplas bort genom att trycka ännu en gång på knappen SLEEP.<br />
12. Ställa klockan<br />
• Tryck på + vid knappen CLOCK för att ändra klockans visade tid framåt.<br />
• Tryck på - vid knappen CLOCK för att ändra klockans visade tid bakåt.<br />
63<br />
+2 C<br />
+1 C<br />
- 1 C<br />
- 2 C<br />
0 0.5 1 1.5 2
FASTSÄTTNING I HÅLLAREN<br />
• Sätt upp fjärrkontrollens hållare på väggen med hjälp av de medföljande skruvarna.<br />
Hållaren bör om möjligt placeras så att enheten kan ta emot signalerna från<br />
fjärrkontrollen.<br />
• Fjärrkontrollen placeras i hållaren genom att placera den ovanför hållaren och<br />
sedan skjuta ner den.<br />
• Fjärrkontrollen tas ur hållaren<br />
genom att dra den rakt upp.<br />
AM<br />
PM<br />
AUTO<br />
ON<br />
OFF<br />
MIN<br />
HR FC<br />
SÄTTA I BATTERIER<br />
• Ta bort bakre locket genom att trycka ned det vid pilen och dra i pilens riktning.<br />
• Sätt i två batterier. Försäkra er om att riktningen på polerna + och – blir de rätta.<br />
• Sätt tillbaka locket och kontrollera displayen.<br />
Ta ur batterierna och sätt i dem igen om displayen<br />
inte skulle tändas. Hjälper inte det - byt batterier.<br />
OBSERVERA! Om displayen lyser svagt, eller<br />
om en enhet inte tar emot de<br />
skickade signalerna, måste<br />
batterierna bytas.<br />
64<br />
AM<br />
PM<br />
AUTO<br />
ON<br />
OFF<br />
MIN<br />
HR FC
3<br />
8<br />
14<br />
6<br />
7<br />
G12 Fjärrkontroll<br />
Key Function Actions<br />
RECALL PRESS ONCE for P1 & TWICE FOR P2<br />
PRESS & HOLD BUTTON for 3s to<br />
INITATE PERSONALISED SETTING<br />
PROGRAM<br />
SELECT P1 OR P2<br />
SET INDIVIDUAL SETTINGS eg.<br />
MODE, SET TEMP or FAN SPEED<br />
LEAVE for 4s to SAVE<br />
REAL TIME<br />
CLOCK CLOCK<br />
(RTC)<br />
PRESS & HOLD BUTTON for 2s to<br />
ACTIVATE<br />
PRESS '+' or '-' to DESIRED TIME<br />
LEAVE for 4s to SAVE<br />
1<br />
2<br />
4<br />
13<br />
9<br />
12<br />
11<br />
5<br />
10<br />
Part No.: A08019020512 OM-G12-0104
BESKRIVNING<br />
1. Transmitter.<br />
Överför inställda eller ändrade data till innedelen.<br />
2. Indikering av sändning.<br />
Blinkar för att bekräfta att data sänts till innedelen.<br />
3. ON / OFF Knapp.<br />
Tryck en gång för att starta aggregatet.<br />
Tryck igen för att stoppa aggregatet.<br />
4. Temperaturinställning.<br />
För att öka inställningsvärdet på den önskade rumstemperatruren trycker<br />
man på den uppåtriktade pilen och för att minska inställningsvärdet<br />
trycker man på den nedåtriktade pilen.<br />
Inställningsområdet är 16°C till 30°C. (Vissa specialvarianter har<br />
inställningsområde 20°C till 30°C.)<br />
Tryck in båda piltangenterna samtidigt för att ändra från °C till °F.<br />
5. Arbetssätt<br />
Tryck på knappen MODE för att välja ett av följande arbetsätt för<br />
aggregatet.<br />
COOL: I detta läge startar aggregatet i kyldrift, kompressorn startas<br />
och stoppas med termostatfunktionen.<br />
DRY: Vid hög luftfuktighet kan detta läge användas för att torka luften .<br />
Så länge rumstemperaturen är mer än två grader över<br />
termostatfunktionen inställda börvärde kommer aggregatet<br />
fungera som i arbetsätt COOL. När rumstemperaturen är mindre<br />
än två grader över börvärdet träder arbetsätt DRY i funktion. I<br />
detta arbetsätt kommer inomhusdelens fläkt alltid att vara i drift<br />
på lägsta hastighet. Kompressorns drift styrs av<br />
termostatfuntionen.<br />
FAN: I detta läge är endast inomhusdelens fläkt i drift.<br />
6. Fläkthastigheter<br />
Genom att trycka på knappen FAN kommer fläkthastigheterna att<br />
ändras i följande ordning:<br />
Low (Låg) - Med (Mellan) - High (Hög) - Auto<br />
Stoppa knapptryckning när önskat alternativ visas i displayen.<br />
66
7. Turbo<br />
Temperatur och fläkt återgår till inställda värden efter 20 minuter eller om<br />
man trycker påknappen ännu en gång. Funktionen fungerar i arbetssätten<br />
COOL (kyla) och DRY (avfuktning). Tryck på knappen för en snabb nedkylning.<br />
Fläkten kommer att öka till högsta hastighet, om hastigheten inte redan är<br />
den högsta.<br />
8. Timerfunktion tillslag<br />
Tryck på SET på knappen ON TIMER för att aktivera funktionen för<br />
automatiskt tillslag. Ställ in tidpunkten för tillslaget genom att hålla SET<br />
intryckt tills önskat klockslag visas. AM innebär klockslag mellan 00.00 -<br />
12.00 och PM klockslag mellan 12.00 - 24.00. Tryck på CLR på knappen CLR<br />
för att deaktivera den automatiska tillslagsfunktionen.<br />
9. Timerfunktion frånslag<br />
Tryck på SET på knappen OFF TIMER för att aktivera funktionen för<br />
automatiskt frånslag.Ställ in tidpunkten för tillslaget genom att hålla SET<br />
intryckt tills önskat klockslag visas.AM innebär klockslag mellan 00.00 -<br />
12.00 och PM klockslag mellan 12.00 - 24.00.Tryck på CLR på knappen för<br />
att deaktivera den automatiska funktionen.<br />
10. Automatisk rörliga luftriktare (tillbehör)<br />
Tryck på knappen SWING för att starta de rörliga luftriktarna. Om man<br />
önskar att ha de rörliga luftriktarna stående i ett speciellt läge, väntar man<br />
tills de kommer dit och trycker ännu en gång på knappen SWING varvid de<br />
stannar.<br />
11. Nattändring av temperaturen (SLEEP) +2 C<br />
Tryck på knappen SLEEP för att aktivera<br />
+1 C<br />
nattändringsfunktionen.<br />
Detta är en energibesparande funktion. När<br />
aggregatet är i arbetsätt COOL kommer den - 1 C<br />
inställda rumstemperaturen att öka med<br />
- 2 C<br />
0,5°C efter en halvtimme. öka med 1°C efter<br />
67<br />
0 0.5 1 1.5 2<br />
12. Ställa klockan<br />
Tryck på + eller - på knappen CLOCK för att ändra<br />
klockans inställning.<br />
13. Personlig inställning<br />
Håll knappen intryckt i 3 sekunder, symbolen kommer då att blinka, vid<br />
ytterligare tryckning växlar visning att växla mellan och .<br />
Ställ sedan in önskad inställning med fjärrkontrollen och lämna kontrollen i<br />
4 sekunder för att spara inställningen. Tryck en gång på för att aktivera<br />
inställning P1, ytterligare en gång för att växla mellan P1 och P2
MONTERING PÅ VÄGG<br />
INSTALLATION AV<br />
BATTERIER
NETWARE 3 trådbunden fjärrkontroll<br />
Display<br />
D<br />
F<br />
H<br />
A : Fläkthastighet<br />
· Visar vilken fläkthastighet som är vald (Auto, high,medium eller low).<br />
B : Driftläge<br />
· Visar vilket driftläge som är valt (Auto, dry, cool, heat eller fan).<br />
C : Sleep funktionen<br />
· Visar om sleep funktionen är aktiverad.<br />
D : Felmeddelande<br />
· Visar error vid fel.<br />
E : Swing funktionen<br />
· Visar när swing funktionen är aktiv.<br />
F : Knapplås<br />
· Visar key lock när knapplåset är aktiverat.<br />
G : °C eller °F<br />
· Visar om temperaturen mäts i °C eller °F.<br />
H : Klockan och ON/OFF-tider<br />
· Visar vad klockan är och inställda ON/OFF-tider.<br />
I : On / Off Status<br />
· Lampa visar ON eller OFF status<br />
J : Rumstemperatur eller inställt börvärde<br />
· Visar rumstemperatur eller inställt börvärde.<br />
Andra funktioner<br />
· Batteri back up för att spara senaste inställningar vid strömavbrott.<br />
För 7-dagars programmvara, används batteri back up för att spara senast inställda värden.<br />
I kontroller utan batteri back up så sparas senast inställda värdei E-promet på aggregatet kretskort.<br />
· Larm<br />
Visar fel kod om ett fel uppstår. Se innedelens felkoder.<br />
A B C<br />
69<br />
E<br />
G<br />
J<br />
I
O<br />
P<br />
Q<br />
Funktion<br />
° °<br />
°<br />
K : Driftlampa<br />
L:On/Off<br />
• Starta :<br />
Om aggregatet är avstängt, tryck på ON/OFF-knappen. Driftlampan tänds och aggregatet startar.<br />
• Stoppa :<br />
Om aggregatet är i drift, tryck på ON/OFF-knappen. Driftlampan slocknar och aggregatet stoppar.<br />
M : Ställa in börvärde<br />
• Tryck på pil upp knappen för att ställa in önskad rumstemperatur. Genom att trycka på upp eller nerpil<br />
en gång ändras värdet 1°C (eller 1°F).<br />
• Temperaturområdet är 16 - 30°C (eller 60 - 85°F).<br />
• I fläktdrift kan inte temperaturen ställas in.<br />
• Tryck in upp och ner-pil samtidigt för att skifta mellan °C och °F. .<br />
• När set temp knappen trycks ner visas inställt börvärde i 5 sekunder och återgår sen för att visa<br />
rumstemperaturen.<br />
N : Driftval<br />
• Tryck på MODE knappen för att välja mellan cool, heat, dry och fan. I displayen visas vilken<br />
drift som är vald.<br />
O : Fläkthastighet<br />
• Tryck på FAN knappen för att välja fläkthastighet mellan auto, high, medium och low.<br />
P : Swing funktionen<br />
• Tryck på swing knappen för att köra luftrikaren i en svepande rörelse.<br />
Q : Sleep funktionen<br />
• Tryck på sleep knappen för att aktivera sleep funktionen och spara energi.<br />
70<br />
K<br />
N<br />
L<br />
M
S<br />
R<br />
X<br />
Z<br />
Y<br />
R : Timer active<br />
S : Visar aktuell tid<br />
T : Driftslampa<br />
U : Knapplås<br />
• Denna funktion hindrar att barn eller obehöriga ändrar inställningar.<br />
• För att aktivera knapplåset tryck 3 gånger på MINUTE knappen. Nu visas KEY LOCK i<br />
displayen.<br />
• Även om knapplåset är aktiverat så kan ON/OFF och FAN knapparna användas.<br />
• För att avaktivera knapplåset, tryck 3 gånger på MINUTE knappen.<br />
V : Minute<br />
• När kontrollen står i SET CLOCK eller SET TIMER, tryck på MINUTE knappen för att ändra<br />
minuter.<br />
W : Hour<br />
• När kontrollen står i SET CLOCK eller SET TIMER, tryck på HOUR knappen för att ändra<br />
timmar.<br />
X : Day<br />
• När kontrollen står i SET CLOCK eller SET TIMER, tryck på DAY knappen för att ändra dagar.<br />
Y : Clock<br />
• Tryck på CLOCK knappen för aktivera klockinställning, CLOCK SET visas i displayen.<br />
• Tryck en gång till för att avaktivera klockinställningen.<br />
• När klockinställningen är aktiverad så kan du ändra tid och dag genom att trycka på DAY, HOUR<br />
och MINUTE knapparna.<br />
Z : Aktivera timer<br />
• Om 7 dagars timer är inställt, så kommer TIMER ACTIVE visas i displayen.<br />
• För att ta bort timer inställningen, tryck in HOLD knappen i 2-3 sekunder till TIMER ACTIVE<br />
försvinner från displayen.<br />
• För att återuppta timer inställningarna, tryck in HOLD knappen i 2-3 sekunder till TIMER ACTIVE<br />
visas i displayen.<br />
71<br />
T<br />
W<br />
U<br />
V
SLM3 trådbunden fjärrkontroll<br />
8<br />
9<br />
2<br />
5<br />
1. “ON/OFF” knapp<br />
• Tryck på ON/OFF för att starta aggregatet.<br />
• Tryck igen för att stoppa aggregatet.<br />
2. Börvärdes inställning<br />
• Ställer in önskad rumstemperatur.<br />
• Tryck på pil knapparna för att öka eller sänka<br />
börvärdet. Temperaturområde är 16 - 30 °C<br />
(60-85°F).<br />
3. driftval<br />
• Tryck på MODE knappen för att välja<br />
driftsätt.<br />
- Endast luftkonditionering:<br />
COOL, FAN, DRY<br />
- Värmepump:<br />
COOL, FAN, DRY, HEAT<br />
TEMP<br />
TIMER<br />
4. Fläkthastighet<br />
• Tryck på FAN knappen till önskad fläkthastighet<br />
är vald.<br />
5. Timer.<br />
• Tryck på TIMER knappen för att välja efter hur<br />
många timmars drift aggregatet ska slå av (inom<br />
området 1-15 timmar).<br />
AUTO<br />
HIGH<br />
MED<br />
LOW<br />
SENSOR<br />
COOL<br />
DRY FAN<br />
FAN<br />
HEAT DRY<br />
HEAT<br />
FAN<br />
SWING<br />
SLM3<br />
ON/OFF<br />
MODE<br />
SLEEP<br />
72<br />
4<br />
1<br />
3<br />
6<br />
7<br />
4<br />
7<br />
5<br />
FAN ON/OFF<br />
SWING<br />
TEMP<br />
SLEEP<br />
TIMER MODE<br />
AC5300 (TILLVAL)<br />
6. “Sleep” funktionen<br />
• Tryck på SLEEP knappen för att aktivera<br />
funktionen. Sleep funktionen kan endast<br />
aktiveras i kyla eller värme-drift(COOL eller<br />
HEAT-mode). När den aktiveras i kyldrift så<br />
ökar den inställda temperaturen 0,5°C efter<br />
30 minuter, 1 °C efter 1 timmeoch 2 °C efter<br />
2 timmar.<br />
Om sleep funktionen aktiveras under värmedrift<br />
så sjunker den inställda temperaturen0,5°C efter<br />
30 minuter, 1 °C efter 1 timmeoch 2 °C efter<br />
2 timmar.<br />
7. Svep funktionen<br />
• Tryck på SWING knappen för aktivera den<br />
automatiska svep funktionen.<br />
8. Sensor<br />
• IR-mottagare för att ta imot signal från<br />
trådlös fjärrkontroll.<br />
9. Display<br />
• För visning av inställd temperatur (i °C)<br />
och timer inställningen (i timmar)<br />
10. IR-transmitter<br />
• Skickar signal till aggregatet.<br />
10<br />
1<br />
2<br />
6<br />
3
INSTALLATION AV LCD FJÄRRKONTROLL<br />
STEG FÖR STEG GUIDE<br />
i) Använd en skruvmejsel och öppna LCD fjärrkontrollens hölje, så att du har en underdel och en överdel.<br />
För att göra detta, trycker du in skruvmejselen i springan i underkanten och drar försiktigt utåt.<br />
ii) Skruva fast underdelen i väggen med de två medföljande skruvarna. Stick sedan in fyrledaren (från<br />
aggregatet) genom hålet i underdelen, som visas här nedan.<br />
iii) Koppla in de tre trådarna på överdelens plintar på baksidan.<br />
iv) Välj endast kyla eller värmepump genom att ställa in switcharna.<br />
v) Sätt tillbaka överdelen på underdelen genom att haka i de två hakarna i överkant, vik ner överdelen<br />
och "klicka" på den i underkant.<br />
Springa i underkant<br />
för att kunna skilja<br />
över- och underdel<br />
Inkoppling på<br />
överdelens baksida.<br />
Inställning av switchar för val av drift.<br />
2 x skruv<br />
LCD Fjärrkontroll<br />
(överdel)<br />
SWITCH FUNKTION INSTÄLLNING<br />
JH & JD RESERV JH-OFF, JD-OFF<br />
COOL, DRY, FAN JH-OFF, JD-ON<br />
COOL, DRY, FAN, HEAT JH-ON, JD-OFF<br />
RTC INGEN REALTIDS-KLOCKA RTC-OFF<br />
REALTIDS-KLOCKA RTC-ON<br />
NO DRY INGEN DRY FUNKTION NO DRY-ON<br />
DRY FUNCTION NO DRY-OFF<br />
73<br />
LCD fjärrkontroll<br />
undersida<br />
Koppling till<br />
aggregat<br />
Kabel