Tasonohjaus<br />
TERMISTORIAUTOMATIIKKA<br />
PTC-anturi<br />
NIVAKT ® THM1-2<br />
PTC level control<br />
Error<br />
Sensor max<br />
Sensor min<br />
Relay<br />
THM1H<br />
THM1L<br />
THM2<br />
Stockholm - Sweden<br />
Relay is activated when sensor is in fluid.<br />
(sensor: approx. 30 sec warm up time)<br />
PTC sensor<br />
Supply<br />
230 VAC<br />
Relay<br />
black /<br />
brown<br />
blue /<br />
white<br />
Relay is activated when both sensors are dry<br />
(sensors: approx. 30 sec warm up time)<br />
NC NO C + + - -<br />
1 2 3 4 5 6 7 8 9 10 11 12<br />
PTC sensor min<br />
bridge<br />
PTC sensor max<br />
Wiring diagram TMH1L<br />
PTC min control<br />
230 VAC<br />
Relay<br />
black / brown<br />
blue / white<br />
Relay is activated when sensor is dry.<br />
(sensor: approx. 30 sec warm up time)<br />
PTC sensor<br />
Supply<br />
230 VAC<br />
Relay<br />
black /<br />
brown<br />
blue /<br />
white<br />
NC NO C + + - -<br />
1 2 3 4 5 6 7 8 9 10 11 12<br />
Supply<br />
NC NO C + + - -<br />
1 2 3 4 5 6 7 8 910 11 12<br />
Wiring diagram TMH2<br />
PTC max/min level control<br />
Wiring diagram TMH1H<br />
PTC max control<br />
112<br />
Data THM1-2<br />
Syöttöjännite: 230V,50-60Hz<br />
Releulostulo: U max<br />
250 V,<br />
I max<br />
2A (AC1= 8A)<br />
P max<br />
100W / 500VA<br />
Suojaluokka:<br />
IP30<br />
24<br />
52<br />
106<br />
THM1-2 automaattinen min. tai max. pinnanohjaus<br />
Yhteistä NIVAKT ® termistoriautomatiikalle on anturi,<br />
PTC-vastus, joka nopeasti muuttaa resistanssin<br />
jäähtyessään nesteessä.<br />
Jännite yli<br />
100 ohmin vastuksen<br />
V-<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
Periaatekaavio PTC-anturille (THM1H)<br />
paikallaan<br />
oleva rasva<br />
paikallaan oleva ilma<br />
liikkeessä oleva rasva<br />
Rele kiinni, LED sammuneena<br />
0 50 C°<br />
hälytysraja 3,5 VDC<br />
rele vedettynä,<br />
LED aktivoitu<br />
Wiring diagram TMH2<br />
PTC max/min level control<br />
Supply<br />
NC NO C + + - -<br />
1 2 3 4 5 6 7 8 9 10 11 12<br />
230 VAC<br />
Relay<br />
PTC sensor max<br />
black / brown<br />
blue / white<br />
Wiring diagram TMH1H<br />
PTC max control<br />
NC NO C + + - -<br />
1 2 3 4 5 6 7 8 910 11 12<br />
Supply<br />
230 VAC<br />
Relay<br />
PTC sensor<br />
black /<br />
brown<br />
blue /<br />
white<br />
Relay is activated when sensor is dry.<br />
(sensor: approx. 30 sec warm up time)<br />
Wiring diagram TMH1L<br />
PTC min control<br />
NC NO C + + - -<br />
1 2 3 4 5 6 7 8 9 10 11 12<br />
Supply<br />
230 VAC<br />
Relay<br />
PTC sensor<br />
black /<br />
brown<br />
bridge<br />
blue /<br />
white<br />
Relay is activated when sensor is in fluid.<br />
(sensor: approx. 30 sec warm up time)<br />
PTC sensor min<br />
Relay is activated when both sensors are dry<br />
(sensors: approx. 30 sec warm up time)<br />
THM2 max-min säätö.<br />
Valodiodi ilmaisee vedetyn releen<br />
kun molemmat termistorit ovat<br />
lämpimät.<br />
Rele irroittaa kun molemmat anturit<br />
ovat jäähtyneet nesteessä.<br />
THM1H ylä pinnan seuranta:<br />
Hälytystaso n. 3,5V, valodiodi ilmaisee<br />
vedetyn releen, = normaali olotila<br />
ilmatilassa n. 1 min. lämpenemisen<br />
jälkeen. Irroittava rele ylä pinnassa<br />
kuten oikosulku tai katkos johtimessa.<br />
THM1L ala pinnan seuranta:<br />
Hälytystaso n. 4,5V, valodiodi<br />
ilmaisee vedetyn releen,= normaali<br />
olotila nesteessä.<br />
Irroittava rele ala pinnalla tai katkos<br />
johtimessa.<br />