english<br />

5.1 Connection terminals<br />

If the connection or the voltage is incorrect,<br />

the motor may be damaged!<br />

Mains connection 1×230 V<br />

L<br />

N<br />

Protective conductor<br />

Line<br />

Neutral<br />

When using fault current safety switches (FI), a model that is<br />

sensitive to pulses has to be used; it must take the charging<br />

current and earthing into account when the power is switched<br />

on and be suitable for the leakage current of the pump<br />

(less than 3.5mA).<br />

The FI switches have to be marked<br />

with the symbol shown.<br />

Comment:<br />

The supply voltage has to be switched off before any work is done<br />

in the pump’s terminal boxes.<br />

Care should be taken when opening the cover<br />

for the electronics<br />

The electronics may be live for up to 10 minutes<br />

after the power has been switched off.<br />

5.2 Connection diagram<br />

L<br />

N<br />

Supply<br />

~1×230 V<br />

Back-up fuse<br />

10 A<br />

961228_00