AXW smart - Biral
AXW smart - Biral
AXW smart - Biral
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
54<br />
english<br />
5.1 Connection terminals<br />
If the connection or the voltage is incorrect,<br />
the motor may be damaged!<br />
Mains connection 1×230 V<br />
L<br />
N<br />
Protective conductor<br />
Line<br />
Neutral<br />
When using fault current safety switches (FI), a model that is<br />
sensitive to pulses has to be used; it must take the charging<br />
current and earthing into account when the power is switched<br />
on and be suitable for the leakage current of the pump<br />
(less than 3.5mA).<br />
The FI switches have to be marked<br />
with the symbol shown.<br />
Comment:<br />
The supply voltage has to be switched off before any work is done<br />
in the pump’s terminal boxes.<br />
Care should be taken when opening the cover<br />
for the electronics<br />
The electronics may be live for up to 10 minutes<br />
after the power has been switched off.<br />
5.2 Connection diagram<br />
L<br />
N<br />
Supply<br />
~1×230 V<br />
Back-up fuse<br />
10 A<br />
961228_00