E72936<br />
Technische gegevens Selectiviteitstabellen<br />
Stroom<br />
opwaarts<br />
<strong>Schneider</strong> <strong>Electric</strong><br />
Masterpact M, NT/NW (EIT thermische curve) stroomopwaarts<br />
van een <strong>Fupact</strong><br />
De Masterpact vermogensschakelaar is uitgerust met een Micrologic 5.0 - 6.0 - 7.0<br />
P/H beveiliging met de volgende instellingen:<br />
v LT thermische instelling: EIT curve met Tr = 24 seconden<br />
v ST magnetische instelling: instantaneous OFF / Tsd = 0,4 seconden<br />
Masterpact NT H1 / NW H1/H2/H3<br />
Micrologic 2.0-5.0-6.0-7.0 A/P/H<br />
NT08 NT08 NT08 NT08 NT08 NT08 NT08 NT08 NT10 NT12 NT16<br />
H1 H1 H1 H1 H1 H1 H1 H1 H1 H1 H1<br />
NW08 NW08 NW08 NW08 NW08 NW08 NW08 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW50 NW63<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2<br />
N1<br />
H1/H2 H1/H2<br />
H3<br />
H1/H2<br />
H3<br />
H1/H2<br />
H3<br />
H1/H2<br />
H3<br />
H1/H2 H1/H2<br />
Rating<br />
(A)<br />
400 400 400 630 800 800 800 800 1000 1200 1600 2000 2500 3200 4000 5000 6300<br />
Ir<br />
setting<br />
160 200 240 315 400 480 630 800 1000 1200 1600 2000 2500 3200 4000 5000 6300<br />
Stroom 32 T T T T T T T T T T T T T T T T T<br />
afwaarts 40 T T T T T T T T T T T T T T T T T<br />
gG/aM<br />
smelt<br />
patroon<br />
MERLIN GERIN<br />
masterp act II<br />
NX 08 HA10<br />
Ui 1000V Uimp 12kV<br />
Ue (V)<br />
690<br />
50kA/1s<br />
IEC 947-2 50/60Hz<br />
EN 60947-2<br />
UTE VDE BS CEI UNE AS NBMA<br />
O<br />
OFF<br />
test<br />
I ON<br />
50 T T T T T T T T T T T T T T T T T<br />
63 T T T T T T T T T T T T T T T T T<br />
80 T T T T T T T T T T T T T T T T<br />
100 T T T T T T T T T T T T T T T<br />
125 T T T T T T T T T T T T T T<br />
160 T T T T T T T T T T T T T<br />
200 T T T T T T T T T T T T<br />
250 T T T T T T T T T T T<br />
315 T T T T T T T T T T<br />
355 T T T T T T T T T<br />
400 T T T T T T T T T<br />
500 T T T T T T T T<br />
630 T T T T T T T<br />
800 T T T T T T<br />
1000 T T T T T<br />
1250 T T T T<br />
Opmerking:<br />
b Voor Masterpact vermogensschakelaars van 2500A en hoger, met identieke instellingen, geldt totale selectiviteit.<br />
Tabel sleutel Vermogensschakelaar karakteristieken<br />
T Totale selectiviteit NT08 tot 16 NW08 tot NW16 NW20 tot NW40 NW40b tot NW63<br />
16 Selectiviteit limiet in kA H1 / Icu = Icw = 42 kA N1 / Icu = Icw = 42 kA H1 / Icu = Icw = 65 kA H1 / Icu = Icw = 100 kA<br />
Geen selectiviteit L1 / Icu=150 kA Icw = 10 kA H1 / Icu = Icw = 65 kA H2 / Icu = 100 Icw = 85 kA H2 / Icu = 150 Icw = 100 kA<br />
H2 / Icu = 100 Icw = 85 kA H3 / Icu = 150 Icw = 65 kA<br />
NW08 tot NW20<br />
L1 / Icu=150 kA Icw = 30 kA<br />