Uitwendige diameters voor vereenvoudigde of<br />
half CLV-overdruksystemen<br />
<strong>Tzerra</strong> 24c <strong>Tzerra</strong> 28c <strong>Tzerra</strong> 39c<br />
Aantal<br />
verdiepingen<br />
d f<br />
[mm]<br />
d a<br />
[mm]<br />
d f<br />
[mm]<br />
d a<br />
[mm]<br />
d f<br />
[mm]<br />
d a<br />
[mm]<br />
2 80 ** 80 ** 80 **<br />
3 80 ** 80 ** 100 **<br />
4 90 ** 100 ** 110 **<br />
5 100 ** 110 ** 130 **<br />
6 110 ** 115 ** 140 **<br />
7 115 ** 130 ** 150 **<br />
8 130 ** 140 ** 160 **<br />
9 130 ** 140 ** 160 **<br />
10 140 ** 150 ** 170 **<br />
11 150 ** 160 ** 180 **<br />
12 150 ** 160 ** 190 **<br />
13 160 ** 170 ** 195 **<br />
14 170 ** 180 ** 200 **<br />
15 170 ** 180 ** 210 **<br />
16 180 ** 185 ** 215 **<br />
17 180 ** 190 ** 220 **<br />
18 185 **<br />
19<br />
20<br />
tabel 33 Afmetingen vereenvoudigde CLVoverdruksystemen<strong>Tzerra</strong><br />
24c, 28c en 39c<br />
Legenda:<br />
= te veel trek. Neem voor deze verdiepinghoogtes<br />
contact op met Sales Support.<br />
d f<br />
:<br />
d a<br />
:**<br />
diameter rookgasafvoerkanaal [mm]<br />
luchttoevoer per toestel uit de gevel (=in principe<br />
aansluitdiameter toestel)<br />
5 Toestel in CLV overdrukmode<br />