09.04.2020 Views

Pre-Feasibility Study - Technical Anlysis Kazakhistan 2018-03-16 total1.2(Fort Merlice)(1)

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5.1.1 Nominal heating requirements

The heating demands of a greenhouse are determined by its configuration and type. In this Technical Analysis,

we provide a quantification of the energy requirements for the greenhouse configuration being considered for

your location (KUBO Contract OW 4444).

The energy calculations assume:

• A glass roof and wall cover

• A single energy-saving screen

• A heat demand based on Delta-T and including dehumidification and activation of the crop

• A Natural Gas energy conversion efficiency equal to 90% of that of the Netherlands: 28.49 MJ/m 3

o Based on our prior experience in Kazakhstan (i.e. KZ Greenhouse)

Ultra-Clima ® Greenhouse with lights

The energy requirement of the considered Ultra-Clima® greenhouse for heating (only) in Mega Joule per square

meter [MJ/m 2 ] was estimated to be: 1319.8 MJ/m 2 . The results from the calculations have been visualized in

Figures 5 and 6. Figure 5 presents the energy requirements for heating the greenhouse in MJ/m 2 for each

month of the year, with a breakdown between the various sources of heat to the greenhouse environment (i.e.

Lights, Pipe rail, or AHU). Figure 6 presents the energy sources for heating the greenhouse in MJ/m 2 for each

month of the year, with a breakdown between the primary sources of heat (Boiler or Cogen) consuming natural

gas.

Figure 5: Ultra Clima® heating energy requirements

• AHU 675,4 MJ/m 2

• Light heat 456,9 MJ/m 2

• Pipe rail: 189,4 MJ/m 2

• Total: 1319,8 MJ/m 2

Figure 6: Ultra Clima® heating energy input

• Boiler: 13,9 m 3 /m 2

• Cogen: 88,8 m 3 /m 2

• Total: 96,8 m 3 /m 2

Date: 16 March 2018

Technical Analysis

13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!