Vridsektordon SG 05.1 - SG 12.1 AUMATIC AC 01.1 ... - FS Data
Vridsektordon SG 05.1 - SG 12.1 AUMATIC AC 01.1 ... - FS Data
Vridsektordon SG 05.1 - SG 12.1 AUMATIC AC 01.1 ... - FS Data
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Vridsektordon</strong> <strong>SG</strong> <strong>05.1</strong> – <strong>SG</strong> <strong>12.1</strong><br />
Driftinstruktion <strong>AUMATIC</strong> <strong>AC</strong> <strong>01.1</strong><br />
Undergrupp Parameter<br />
namn<br />
Under<br />
meny<br />
Standard<br />
värde<br />
min/<br />
max<br />
Värdetext Anmärkning<br />
M1G MODBUS 2 2) BAUD RATE M1GX1 5 0 300 BAUD<br />
1 600 BAUD<br />
2 1200 BAUD<br />
3 2400 BAUD<br />
4 4800 BAUD<br />
5 9600 BAUD<br />
6 19200 BAUD<br />
7 38400 BAUD<br />
MODBUS 2: Baudrate val<br />
PARITY M1GX2 1 0 NO,<br />
2 STOPBITS<br />
1 EVEN,<br />
1 STOPBIT<br />
2 ODD,<br />
1 STOPBIT<br />
MODBUS 2: Parity val<br />
CONNECT-CONTOL<br />
TIME<br />
M1G03 3,0 0,1<br />
25,5<br />
MODBUS 2: Anslutning övervakningstid<br />
(i s)<br />
SLAVE ADDRESS M1GX4 247 1<br />
247<br />
MODBUS 2: Slaveadress<br />
REDUNDANCY M1GX5 0 0 OFF MODBUS 2: Redundan<br />
1 ON, TX: <strong>AC</strong>TIVE<br />
CHANNEL<br />
2 ON, TX: BOTH<br />
CHANNELS<br />
suppförande<br />
CHANNEL CHECK<br />
TIME<br />
M1GX6 5,0 0,0<br />
25,5<br />
MODBUS 2: Kanalväxeltid (i s)<br />
T-OFF<br />
PROC.IMG.OUT<br />
M1G07 0,3 1<br />
255<br />
MODBUS 2: Dödtid processbild<br />
output (i s)<br />
SIZE OF<br />
PROC.IMG.OUT<br />
SIZE OF<br />
PROC.IMG.IN<br />
1) Endast för ställdon med PROFIBUS-DP 2) Endast för ställdon med MODBUS<br />
M1G08 6 0 MODBUS 2: Processbildens längd<br />
output<br />
64<br />
M1G09 18 0 MODBUS 2: Processbildens längd<br />
input<br />
64<br />
43