3.3.37. REF1TC Restricted Earth Fault Torque Control (<strong>SEL</strong>ogic)Este ajuste define o controle de torque para a função REF.REF1TC: <strong>SEL</strong>ogic Equation.AJUSTESREF1TC = 13.3.38. 50REF1P REF1 Current Sensitivity Level (Per Unit)Este ajuste define a corrente de sensibilidade da função REF.50REF1P: 0,05 – 3,00 pu. MAX ( INOMn CTRn)50REF1P 0,05 ( CTRN1 INOMN1)Onde:MAX(INOMn x CTRn) = RTC da função REF = 120 x 5CTRN1 x INOMN1 = RTC do lado estrela do transformador = 120 x 5120 550REF1P 0,05 0, 05 pu120 5 AJUSTES50REF1P = 0,05Rodovia Campinas Mogi-Mirim (SP-340), Km 118,50 Prédio 11 – Campinas-SP CEP 13086-902 Tel: (19) 3515 2000home-page: www.selinc.com.br Fax: (19) 3515 2011CNPJ: 03.837.858/0001-01 Insc. Estadual: 244.668.694.11671/247