14.12.2022 Views

pdfcoffee.com_hvacsimplifiedpdf-pdf-free

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

HVAC Fundamentals: Refrigeration

ized theoretical values for R-134a and should be less

than the corresponding theoretical values of

Equations 2.1 and 2.2, which assume both an “ideal”

refrigerant and reversible processes. Thus, the values

computed using Equations 2.1 and 2.2 should be greater

than those found using Equation 2.3c and 2.4c for the

same evaporating and condensing temperatures.

Operating Characteristics of

Real Vapor Compression Cycles

A familiarity with this process and the values generated

in the preceding discussion is valuable even though

the process is idealized. Limits are set and the system

designer can determine the relative importance of operating

conditions and component selection that will have

the greatest impact on total system optimization. However,

there are a number of constraints that limit the

capacity and efficiency of actual vapor compression

cycles. Several are listed here:

• Refrigerant enters the compressor as a superheated

vapor to protect it from damage by liquid refrigerant

(it is essentially incompressible and may

remove oil from bearing surfaces). Therefore, the

inlet gas density will be slightly lower compared to

saturated vapor, thereby reducing mass flow rate

and compressor capacity.

• There are pressure drops (across ports, valves, and

mufflers), friction in the compressor and fluid, and

heat generated by the compressor drive. Thus, the

pressure difference from inlet to outlet will be

greater than ideal, and entropy will be generated

since the processes are irreversible.

• There is pressure drop and internal heat generation

through the condenser with a corresponding change

in saturation temperature as the pressure changes.

• Condensers are heat exchangers of finite size and

will operate at temperatures elevated above the idealized

condensing temperatures.

• The refrigerant must be subcooled several degrees

below the saturation temperature to ensure the

refrigerant is 100% liquid since the performance of

many expansion devices is compromised by the

presence of vapor.

• Heat transfer and entropy generation are encountered

when refrigerant passes through real expansion

devices.

• Evaporators are heat exchangers of finite size and

will operate at temperatures below the idealized

evaporation temperatures.

• The evaporation temperature in many cases must be

suppressed to low values to meet the needs of the

application (ice making, dehumidification, etc.).

• Many alternative refrigerants are zeotropic mixtures

that do not behave as a pure substance. Thus, condensation

and evaporation saturation temperatures

change (glide) with phase concentration. This typically

results in lower system efficiency and/or

larger heat exchanger size.

Figure 2.3 is a p-h diagram that demonstrates the

impact of a number of these constraints.

Figure 2.3 P-h process diagram of a real vapor compression cycle (ASHRAE 2005).

9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!