<strong>SUNWAY</strong> M <strong>XS</strong><br />

QUICK START GUIDE<br />

Carry out the ground connection of the inverter before carrying out any electrical connection. The <strong>SUNWAY</strong> M <strong>XS</strong> is<br />

supplied with a three-wire cable for the connection to the grid. First connect the yellow-green wire to the ground of the<br />

electrical system external to the inverter. The yellow-green wire is internally connected to the Protective Earth of the<br />

circuit.<br />

CONNECTION TO THE GRID<br />

Connect the <strong>SUNWAY</strong> M <strong>XS</strong> to the grid using the snap-in connectors supplied with the product. Connect the line (L),<br />

neutral (N) and protective earth (PE).<br />

DANGER<br />

Always remove voltage before operating on the grid.<br />

CAUTION<br />

PROTECTION AGAINST DIFFERENTIAL CURRENT – The inverters of the <strong>SUNWAY</strong> M <strong>XS</strong> series are compatible with<br />

external RCDs of type A according to the regulations in force, because, by construction, they cannot generate DC<br />

differential currents, even under single fault conditions.<br />

Always install a MCCB to protect the electric circuit. The minimum trip threshold of the RCD shall be 100 mA for every<br />

inverter installed.<br />

WIRING DIAGRAM<br />

10/30