<strong>SUNWAY</strong> M <strong>XS</strong><br />
QUICK START GUIDE<br />
Carry out the ground connection of the inverter before carrying out any electrical connection. The <strong>SUNWAY</strong> M <strong>XS</strong> is<br />
supplied with a three-wire cable for the connection to the grid. First connect the yellow-green wire to the ground of the<br />
electrical system external to the inverter. The yellow-green wire is internally connected to the Protective Earth of the<br />
circuit.<br />
CONNECTION TO THE GRID<br />
Connect the <strong>SUNWAY</strong> M <strong>XS</strong> to the grid using the snap-in connectors supplied with the product. Connect the line (L),<br />
neutral (N) and protective earth (PE).<br />
DANGER<br />
Always remove voltage before operating on the grid.<br />
CAUTION<br />
PROTECTION AGAINST DIFFERENTIAL CURRENT – The inverters of the <strong>SUNWAY</strong> M <strong>XS</strong> series are compatible with<br />
external RCDs of type A according to the regulations in force, because, by construction, they cannot generate DC<br />
differential currents, even under single fault conditions.<br />
Always install a MCCB to protect the electric circuit. The minimum trip threshold of the RCD shall be 100 mA for every<br />
inverter installed.<br />
WIRING DIAGRAM<br />