<strong>Guide</strong> <strong>d'installation</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, <strong>application</strong> <strong>A217</strong> / <strong>A317</strong>2.5.4 Raccordements électriques, 24 Vca, alimentation, pompes, vannes motorisées, etc.Application <strong>A217</strong>.1Danfoss87H2086.10Borne Description Charge max.1615Alarme4 (2) A/24 Vca*14 Phase pour la régulation des pompes13 K3 Pompe de circulation ECS ON/OFF 4 (2) A/24 Vca*12 Ne pas utiliser11 K1 Pompe de charge/chauffage ECS ON/OFF 4 (2) A/24 Vca*10 Tension d'alimentation 24 Vca - (N)9 Tension d'alimentation 24 Vca - (L)8 M1 Phase pour sortie de la vanne de régulation motorisée7 M1 Vanne de régulation motorisée - ouverture 1 A/24 Vca6 M1 Vanne de régulation motorisée - fermeture 1 A/24 Vca5 Ne pas utiliser4 Ne pas utiliser3 Ne pas utiliser* Contacts de relais : 4 A pour la charge ohmique, 2 A pour la charge inductiveCavaliers établis d'usine :5 à 8, 9 à 14, L à 5 et L à 9, N à 10Section de câble : 0.5 à 1.5 mm²De mauvais raccordements sont susceptibles d'endommager lessorties électroniques.Deux câbles de 1.5 mm² max. peuvent être insérés dans chaque borne.34 DEN-SMT/DK VI.LG.U2.04 Danfoss District Energy