3.- Equipment description<br />
Alarm station<br />
Mute/reset button<br />
Mutes the alarm or deletes saved alarms<br />
Pre-alarm jumper<br />
It allows activating pre-alarm detection.<br />
Before using this option, make sure that<br />
regulations allow for only two alarm levels.<br />
Pre-alarm enabled<br />
Pre-alarm disabled<br />
VISUAL ALARM<br />
DETECTOR STATUS<br />
POWER SUPPLY STATUS<br />
ACOUSTIC ALARM<br />
PRE-ALARM JUMPER<br />
MUTE/RESET BUTTON<br />
When using the ammoniac (<strong>AKO</strong>-52213) or CO 2 (<strong>AKO</strong>-52215) detector, the pre-alarm must be<br />
enabled.<br />
Gas detector <strong>AKO</strong>-52211/12/13/14<br />
Delay switch<br />
It delays the activation of alarms detected in the station.<br />
The detector status indicators will indicate the alarms and<br />
pre-alarms immediately, without taking into account the<br />
delays.<br />
STATUS INDICATORS<br />
ON<br />
Without delay*<br />
ON<br />
30 sec.<br />
DELAY SWITCH<br />
*Default value<br />
ON<br />
60 sec. 120 sec.<br />
ON<br />
IMPORTANT: The delay configuration should be carried out with the station's power supply<br />
disconnected, as if not it will not work.<br />
Gas detector <strong>AKO</strong>-52215<br />
Response selector<br />
It defines the detector's type of response and affects both<br />
the reading shown on the indicator and the activation of<br />
the alarms.<br />
STATUS INDICATORS<br />
RESPONSE<br />
SELECTOR<br />
ON<br />
ON<br />
Immediate response: The detector reacts<br />
depending on the last reading obtained.*<br />
Delayed response: The detector reacts<br />
depending on the average value of the<br />
last 11 readings.<br />
CO 2 CONCENTRATION INDICATOR<br />
IN PARTS PER MILLION (ppm)<br />
1258<br />
*Default value<br />
The interval between readings is 15 seconds, regardless of the position of the selector.<br />