7.- Warnings<br />

ŸDetectors measure gas concentration in a point, if the gas leak does not reach the detector, the alarm will<br />

not activate.<br />

ŸDetectors cannot supervise areas, and if perimeter supervision is required, several detectors should be<br />

installed surrounding the area to be supervised.<br />

ŸThoroughly studying the location of the detector/s is recommended, bearing in mind the areas most sensitive to<br />

suffering leaks, the type of gas used, the size and shape of the room, the air flows, the maintenance work, etc.<br />

ŸThe detectors described have been designed to detect gas concentrations capable of affecting the<br />

environmental conditions of the room (movement of oxygen), and the detection of small coolant leaks is not<br />

guaranteed.<br />

8.- Technical data<br />

<strong>AKO</strong>-52210<br />

Power supply ........................................................................................................................90-260 V~ 50/60 Hz<br />

Maximum input power ................................................................................................................................10 VA<br />

No. of inputs.......................................................................................................................................................1<br />

Compatibility of inputs..................................................................................................Only <strong>AKO</strong>-5221x detectors<br />

Alarm / pre-alarm relay ...........................................................................................SPDT 230 Vac, 16 A, cos j =1<br />

Working ambient temperature ..........................................................................................................0 ºC to 50 ºC<br />

Storage ambient temperature ........................................................................................................-30 ºC to 70 ºC<br />

Protection degree .........................................................................................................................................IP 40<br />

Installation category ....................................................................................................................II s/ EN 61010-1<br />

Pollution degree ..........................................................................................................................II s/ EN 61010-1<br />

Double isolation between power supply, secondary circuit and relay output.<br />

Sound power..........................................................................................................................90 dB(A) at 1 metre<br />

EMC Standard.......................................................................................................................................EN 61000<br />

<strong>AKO</strong>-5221x<br />

Power supply..................................................................................................................................15 Vdc ±3 Vdc<br />

Consumption Typical <strong>AKO</strong>-52211/12/13/14 .....................................................................................75 mA<br />

<strong>AKO</strong>-52215......................................................................................................30 mA<br />

Maximum <strong>AKO</strong>-52211/12/13/14 ...................................................................................100 mA<br />

<strong>AKO</strong>-52215......................................................................................................50 mA<br />

Working ambient temperature.......................................................................................................-20 ºC to 50 ºC<br />

Storage ambient temperature ........................................................................................................-20 ºC to 60 ºC<br />

Range of maximum allowed humidity .............................................................5 - 85% RH (without condensation)<br />

Protection degree .........................................................................................................................................IP 40<br />

Sensor type<br />

<strong>AKO</strong>-52211/12/13/14 ........................................................Sn02 (Metal Oxide Semiconductor)<br />

<strong>AKO</strong>-52215.............................................................NDIR (Non-Dispersive Infrared Technology)<br />

Display range (<strong>AKO</strong>-52215)............................................................................................................0 - 9999 ppm<br />

Life...................................................................................Depending on the temperature and humidity conditions<br />

EMC Standard.......................................................................................................................................EN 61000<br />