PT. PLN (PERSERO) UNIT INDUK PEMBANGKITAN DAN PENYALURAN KALIMANTAN
JL.Panglima Batur Barat No. 1 Banjarbaru, Kalimantan Selatan
SETELAN RELAY PROTEKSI BAY LINE
Lokasi GI : GI MARABAHAN
Line Bay To : MARABAHAN-KAYUTANGI 1
Update :
06 Juni 2022
1 . Relay Terpasang
DISTANCE
Merk
Type
MICOM
P443
OCR
Merk
Type
DI BUAT OLEH
S/N
S/N
2 . INPUT CT/PT
PT LINE DISTANCE
CT BU OCR
PRIMER 150,000 V
PRIMER 1200
A
ADITYA BUDI SUHARSONO
SEKUNDER 100 V CT LINE DISTANCE SEKUNDER 1 A
ENG PROTEKSI & CATU DAYA
RASIO
PRIMER 1200
SEKUNDER 1
RASIO 1200
1500 RASIO 1200
A
A
DI PERIKSA OLEH
3. NILAI SETTING PROTEKSI
SETTING DISTANCE
Zone 1
Zone 2
Zone 3
Terlampir
Terlampir
Terlampir
HANIF ARIFIANSYAH F
AMN PROTEKSI & CATU DAYA
DI SETUJUI OLEH
I. Parameter Setting OCR/GFR
NILAI PRIMER
NILAI SEKUNDER
I> 1200
A I> 1
A
TMS 0.20
SI TMS 0.20
SI
I>>
BLOCK SETTING I>>
BLOCK ERVIN SAPUTRA
SETTING OCR GFR
TD
BLOCK INPUT RELAY TD
BLOCK MSB PROTEKSI & METERING
I0> 240 A (Nilai I0> 0.2
A
TMS 0.39 SI Sekunder) TMS 0.39 SI
DI SAH KAN OLEH
I0>>
BLOCK
I0>>
BLOCK
TD
BLOCK
TD
BLOCK
SI= Standard Inverse
JULI SEMBIRING
SRM TRANSMISI UIKL KAL
06/06/2022 Micom Marabahan bay Kayutangi rev 2022 06 06 Page 1
PT. PLN (PERSERO) UNIT INDUK PEMBANGKITAN DAN PENYALURAN KALIMANTAN
JL.Panglima Batur Barat No. 1 Banjarbaru, Kalimantan Selatan
ID Line = 209
Substation = GI MARABAHAN
Line To = GI KAYUTANGI
Line Bay Description = MARABAHAN-KAYUTANGI 1
Conductor = ACSR 240 - Double
Voltage Level = 150 kV
Frequency 50 Hz
Line Data Rekomendasi Eksisting
Line Length
= 31.54 km
R1' /km
= 0.059 Ω Primary
JX1' /km
= 0.281 Ω Primary
R0' /km
= 0.212 Ω Primary
JX0' /km
= 0.859 Ω Primary
Z1' /km
= 0.287 Ω Primary
Z0' /km
= 0.885 Ω Primary
R1' Total
= 1.875 Ω Primary
JX1' Total
= 8.861 Ω Primary
R0' Total
= 6.682 Ω Primary
JX0' Total
= 27.087 Ω Primary
Z1' Total
= 9.057 Ω Primary
Z0' Total
= 27.899 0.1 Ω Primary
Z1 Angle
= 78 ⁰ (Degree)
Z0 Angle
= 76 ⁰ (Degree)
RE/RL
= 0.854
XE/XL
= 0.686
RM/RL
= 0.854
XM/XL
= 0.686
KN
= 0.693
R0-R1 = 4.807
X0-X1 = 18.226
Z0-Z1 Mag = 18.849
Z0-Z1 Angle = 75
KZ0 Res Comp = 0.694
KZ0 Angle = -2.827
Z1 Mutual
Z0 Mutual
Z0/Z1 Mag
Z0/Z1 Angle
Z0 M / Z1 Mag
Z0 M / Z1 Angle
CCC
Maximum Load Of Line in Ohm
X Trafo remote substation
R ground fault for Z3
R phase fault for Z1
R phase fault for Z2
R phase fault for Z3
CT Primary Main
CT Secondary Main
CT Ratio Main
CT Primary Back Up
CT Secondary Back Up
CT Ratio Back Up
VT Primary
VT Secondary
VT Ratio
Ratio CT / VT
Synchrocheck Max Volt Diff
Short Circuit Level Max
Short Circuit Level Min
Maximum Load Export give angle betwwen sources
Z1 PP
Z1 PE
Z2 PP
Z2 PE
Z3 PP
Z3 PE
PARAMETER SETTING DISTANCE
= 4.529
= 13.949
= 3.080
= -1.909 ⁰ (Degree)
= 0.000
= 0.000
= 1290 Ampere
= 72.169 Ω Primary / phase
= 90 Ω Primary
= 46.188 Ω Primary
= 12.516 Ω Primary
= 20.934 Ω Primary
= 34.641 Ω Primary
= 1200 Ampere
= 1 Ampere
= 1200
= 1200 Ampere
= 1 Ampere
= 1200
= 150000 Volt
= 100 Volt
= 1500
= 0.8
= 10%
= 3826
= 3437
= 36
= 80% 0 s
= 80% 0 s
= 134% 0.4 s
= 134% 0.4 s
= 221% 1.2 s
= 221% 1.2 s
06/06/2022 Micom Marabahan bay Kayutangi rev 2022 06 06 Page 2
PT. PLN (PERSERO) UNIT INDUK PEMBANGKITAN DAN PENYALURAN KALIMANTAN
JL.Panglima Batur Barat No. 1 Banjarbaru, Kalimantan Selatan
II. Parameter Setting LCD (Not Available)
CT AND VT RATIOS
0A.01 Main VT Primary = 150 kV
0A.02 Main VT Sec'y = 100 V
0A.03 C/S VT Primary = 150 kV
0A.04 C/S VT Secondary = 100 V
0A.07 Phase CT Primary = 1200 A
0A.08 Phase CT Sec'y = 1 A
0A.0D MComp CT Primary = 1200 A
0A.0E MComp CT Sec'y = 1 A
0A.0F C/S Input = B-N
0A.10 Main VT Location = Line
III. Parameter Setting Triger Rekaman Gangguan
RECORD CONTROL
0B.04 Alarm Event = Enabled
0B.05 Relay O/P Event = Enabled
0B.06 Opto Input Event = Enabled
0B.07 General Event = Enabled
0B.08 Fault Rec Event = Enabled
0B.09 Maint Rec Event = Enabled
0B.0A Protection Event = Enabled
DISTURB RECORDER
0C.01 Duration = 3.000 s
0C.02 TriggerPosition = 0.333 %
0C.03 TriggerMode = Single
0C.04 AnalogChannel1 = VA
0C.05 AnalogChannel2 = VB
0C.06 AnalogChannel3 = VC
0C.07 AnalogChannel4 = IA
0C.08 AnalogChannel5 = IB
0C.09 AnalogChannel6 = IC
0C.0A AnalogChannel7 = IN
0C.0B AnalogChannel8 = IN Sensitif
0C.0C DigitalInput1 = Any Start
0C.0D Input1Trigger = Trigger L/H
0C.0E DigitalInput2 = Any Trip
0C.0F Input2Trigger = Trigger L/H
0C.10 DigitalInput3 = Z1 Trip
0C.11 Input3Trigger = Trigger L/H
0C.12 DigitalInput4 = Z2 Trip
0C.13 Input4Trigger = Trigger L/H
0C.14 DigitalInput5 = Z3 Trip
0C.15 Input5Trigger = Trigger L/H
0C.16 DigitalInput6 = Z1 Start
0C.17 Input6Trigger = Trigger L/H
0C.18 DigitalInput7 = Z2 Start
0C.19 Input7Trigger = Trigger L/H
0C.1A DigitalInput8 = Z3 Start
0C.1B Input8Trigger = Trigger L/H
0C.1C DigitalInput9 = Dist Chanel Send
0C.1D Input9Trigger = Triger L/H
0C.1E DigitalInput10 = DIST Sig. Send
0C.1F Input10Trigger = Trigger L/H
0C.20 DigitalInput11 = DIST. Chan Recv
0C.21 Input11Trigger = Trigger L/H
0C.22 DigitalInput12 = SOTF/TOR Trip
0C.23 Input12Trigger = Trigger L/H
0C.24 DigitalInput13 = CB Aux A (52-A)
0C.25 Input13Trigger = Trigger L/H
0C.26 DigitalInput14 = CB Aux B (52-A)
0C.27 Input14Trigger = Trigger L/H
0C.28 DigitalInput15 = CB Aux C (52-A)
0C.29 Input15Trigger = Trigger L/H
0C.2A DigitalInput16 = A/R 1P In Prog
0C.2B Input16Trigger = Trigger L/H
0C.2C DigitalInput17 = I A/R 3p In Pr.
0C.2D Input17Trigger = Trigger L/H
0C.2E DigitalInput18 = I A/R Reclaim
0C.2F Input18Trigger = Trigger L/H
0C.30 DigitalInput19 = I A/R Close
0C.31 Input19Trigger = Trigger L/H
0C.32 DigitalInput20 = BAR
0C.33 Input20Trigger = Trigger L/H
0C.2E DigitalInput21 = AR Lockout Shot>
0C.2F Input21Trigger = Trigger L/H
0C.30 DigitalInput22 = A/R Lockout
0C.31 Input22Trigger = Trigger L/H
0C.32 DigitalInput23 = Check Synch. OK
0C.33 Input23Trigger = Trigger L/H
06/06/2022 Micom Marabahan bay Kayutangi rev 2022 06 06 Page 3
MEASURE'T SETUP
0D.02 Local Values = Primary
0D.03 Remote Values = Primary
0D.04 Measurement Ref = VA
0D.05 Measurement Mode = 0.000
0D.06 Demand Interval = 30.00 min
Roll Sub Periode
30.00 min
0D.07 Distance Unit = Kilometres
0D.08 Fault Location = Distance
IV. Parameter Setting Distance Zone 1, Zone 2 & Zone 3
30.01 GROUP 1 Line Setting
30.02 Line Length = 31.54 km
30.04 Line Impedance = 7.25 Ohm
30.05 Line Angle = 78 deg
30.06 GROUP 1 Zone Setting
Z1 Phase Reach = 5.67 ohm
Z1 Phase Angle = 78 degree
R1Ph Resistive = 10.01 ohm
Z1 Tilt Top Line = 0.000
Z1 Sensit. Iph>1 = 50 mA
Z2 Phase Reach = 9.49 ohm
Z2 Phase Angle = 78 degree
R2Ph resistive = 16.75 ohm
Z2 Tilt Top Line = 0.000
Z2 Sensit. Iph>1 = 50 mA
Z3 Phase Reach = 15.70 ohm
Z3 Phase Angle = 78 degree
R3Ph Resistive = 27.71 ohm
Z3 Tilt Top Line = 0.000
Z3 Sensit. Iph>1 = 50.000 mA
Ground Distance =
Z1 Gnd Reach = 5.67 ohm
Z1 Phase Angle = 76 degree
Z1 Dynamic Tilt = Disabled
Z1 Tilt Top Line = 0.000
KZn 1 Res Comp = 0.694
KZn 1 Res Angle = -2.827
R1 Gnd Resistive = 36.950 ohm
Z1 Sensitive Ignd>1 = 50 mA
Z2 Gnd Reach = 9.49 ohm
Z2 Phase Angle = 76 degree
Z2 Dynamic Tilt = Disabled
Z2 Tilt Top Line = 0.000
KZn 2 Res Comp = 0.694
KZn 2 Res Angle = -2.827
R2 Gnd Resistive = 36.950 ohm
Z2 Sensitive Ignd>1 = 50 mA
Z3 Gnd Reach = 15.70 ohm
Z3 Phase Angle = 76 degree
Z3 Dynamic Tilt = Disabled
Z3 Tilt Top Line = 0.000
KZn 3 Res Comp = 0.694
KZn 3 Res Angle = -2.827
R3 Gnd Resistive = 36.950 ohm
Z3 Sensitive Ignd>1 = 50.000 mA
SCHME LOGIC
Basic Scheme Mode = Standard Scheme
Zone 1 Tripping = Ph & Gnd
tz1 ph Delay = 0 s s
tz1 gnd Delay = 0 s s
Zone 2 Tripping = Ph & Gnd
tz2 ph Delay = 0.4 s s
tz2 gnd Delay = 0.4 s s
Zone 3 Tripping = Ph & Gnd
tz3 ph Delay = 1.2 s s
tz3 gnd Delay = 1.2 s s
Zone P Tripping = Disabled
tzP ph Delay = Disabled
tzP gnd Delay = Disabled
Zone 4 Tripping = Disabled
tz4 ph Delay = Disabled
tz4 gnd Delay = Disabled
AIDED SCHEME 1 =
Aid 1 selection = PUR
Aid 1 Distance = Ph & Gnd
Aid 1 Distance delay = 0.000
AIDED SCHEME 1 =
Aid 2 selection = Programmable
Aid 2 Distance = Disabled
Aid 2 DEF Status = Enable
Aid 2 DEF Polarising = Zero Sequence
Aid 2 DEF Char Angle = -60.000 deg
Aid 2 Vnpol Set = 2.309
Aid 2 DEF FWD set = 100.000 mA
Aid 2 DEF REV set = 25.000 mA
06/06/2022 Micom Marabahan bay Kayutangi rev 2022 06 06 Page 4
X (Ohm)
X (Ohm)
Aid 2 DEF Delay = 150.000 ms
Aid 2 DEF Trip = 1&3 pole
Aid 2 DEF Delta = Disabled
t Rev Guard = 20.000 ms
Custom time PU = 0.000 s
V. Parameter Setting Power Swing Block
PSB Status = Blocking
Zone 1 Ph PSB = Blocking
Zone 2 Ph PSB = Disabled
Zone 3 Ph PSB = Disabled
Zone P Ph PSB = Disabled
Zone 4 Ph PSB = Disabled
Zone 1 Gnd PSB = Blocking
Zone 2 Gnd PSB = Disabled
Zone 3 Gnd PSB = Disabled
Zone P Gnd PSB = Disabled
Zone 4 Gnd PSB = Disabled
WI Trip PSB = Inhibit Trip
PSB UnBlocking = Disabled
PSB Reset Delay = 200.000 ms
OST Mode = OST Disabled
Slow Swing = Enabled
VI. Parameter Setting Sinkron Cek
GROUP 1 SYSTEM CHECKS
48.03 V< Dead Line = 17.32 V
48.04 V> Live Line = 40.41 V
48.05 V< Dead Bus = 17.32 V
48.06 V> Live Bus = 40.41 V
48.07 Diff Voltage = 5.774 V
48.08 Diff Frequency = 100 mHz
48.09 Diff Phase = 15 deg
SP AR Dead Time = 1 Sec
3P AR DT Shot 1 = 1.0 Sec Masuk Pertama
3P AR DT Shot 2 = 180.0
SPAR Reclaim Time = 40.0
3PAR Reclaim Time = 40.0
AR CB Healthy Time = 5.0
AR Check Sync Time = 3600
Z1 AR = Initiate AR
Dist Aided AR = Initiate AR
Z2T AR = Block AR
Z3T AR = Block AR
DEF Aided AR = Initiate AR
TOR AR = Block AR
I>1 AR = Block AR
CB SC All = Enabled
CB SC Shot 1 = Enabled
CB SC ClsNoDly = Disable
CB SC CS1 = Enabled
CB SC CS2 = Disable
CB SC DLLB = Enabled
CB SC LLDB = Enabled
CB SC DLDB = Enabled
Z7 = 18.8 ohm
Z8 = 22.0 ohm
R7 = 44.3 ohm
R8 = 51.7 ohm
Blinder Angle = 78.1 deg
delta T = 30.0 ms
Tost = 0.0
GROUP 1 SUPERVISION
VTS mode = Measured
VTS Status = Blocking
VTS Reset mode = Auto
VTS Time delay = 5.000
VTS I> Inhibit = 5.000
VTS I2> Inhibit = 50.000
Inrush Detection = Enabled
WI Inhibit = Enabled
I0/I2 = 3.000
CTS Time Delay = 5.000
Gambar Kurva
Phase Distance
25
20
15
10
5
0
-60 -40 -20 0
-5
20 40 60
-10
-15
-20
-25
R (Omh)
Ground Distance
20
15
10
5
0
-20 0 20 40 60
-5
-10
R (Omh)
06/06/2022 Micom Marabahan bay Kayutangi rev 2022 06 06 Page 5
VII. Parameter Logic LCD/Distance
Konsep Perubahan
BLOCK LCD
COMMUNICATION LCD
FAIL/EROR
NOT
BLOCK ZONE 1
OR GATE
POWER SWING BLOCK
1. Distance Zone 1 Block Saat Communication Healthy di LCD (Not Available)
2. Distance Zone 1 Aktif Saat Communucation Failure di LCD (Not Available)
3. Power Swing Block Hanya Memblock fungsi Distance Zone 1
PT. PLN (PERSERO) UNIT INDUK PEMBANGKITAN DAN PENYALURAN KALIMANTAN
JL.Panglima Batur Barat No. 1 Banjarbaru, Kalimantan Selatan
VIII. Parameter Setting Discrepancay CB
Setting Discrepancy CB = 1,5 Sec
IX. Parameter Setting Primer Back Up OCR/GFR
I> = 1200 A
tI> = 0.20 TMS
Kurava tI> = Std Invrs
I>> = BLOCK
tI>> = BLOCK
Kurava tI>> = BLOCK
Io> = 240 A
tIo> = 0.39 TMS
Kurava tIo> = Std Invrs
Io>> = BLOCK
tIo>> = BLOCK
Kurava tIo>> = BLOCK
06/06/2022 Micom Marabahan bay Kayutangi rev 2022 06 06 Page 6