CAMINI, CANNE FUMARIE E CONDOTTI INTUBATI<br />
www. impiantitalia .it R<strong>08</strong> 91<br />
<strong>La</strong> <strong>norma</strong> <strong>UNI</strong>-<strong>CIG</strong> <strong>UNI</strong> <strong>CIG</strong> <strong>7129</strong>/<strong>08</strong><br />
CAMINI, CANNE FUMARIE E CONDOTTI INTUBATI<br />
Camini singoli - Requisiti generali<br />
I camini singoli devono essere installati rispettando le seguenti indicazioni:<br />
- avere andamento prevalentemente verticale ed essere privi di qualsiasi strozzatura<br />
per tutta la loro lunghezza;<br />
- avere non più di due cambiamenti di direzione con un angolo d’inclinazione non<br />
maggiore di 30°.<br />
Nel caso di angoli con inclinazione maggiore di 30°ma non<br />
maggiore di 45°è necessario effettuare un calcolo di verifica del corretto<br />
funzionamento utilizzando le norme vigenti;<br />