CAVI ALLARME- ALARM CABLES

CAVI ALLARME- ALARM CABLES

CAVI ALLARME- ALARM CABLES

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SCHERMATURA con copertura al 100%<br />

La schermatura è formata da:<br />

- nastro accoppiato di alluminio/poliestere 9/12<br />

micron<br />

- filo di drenaggio in rame stagnato<br />

- nastro poliestere da 12 micron applicato sul cavo<br />

secondo le norme CEI 46-5.<br />

La guaina esterna in PVC del tipo RZ di colore bianca,<br />

azzurra, rossa o grigia è flessibile e non propagante<br />

incendio secondo le norme CEI 20/22 II Edizione.<br />

CAVo <strong>ALLARME</strong> GR2<br />

Per le sue caratteristiche costruttive, a seguito di test<br />

superati positivamente, tale cavo è in “grado 2” con<br />

un isolamento di 250 V.<br />

CAVo <strong>ALLARME</strong> GR3<br />

Sezione/Size<br />

0,50 mmq n° 16 Ø 0,20 mm in rame rosso (red copper)<br />

0,75 mmq<br />

n° 24 Ø 0,20 mm in rame rosso (red copper)<br />

1,00 mmq<br />

n° 32 Ø 0,20 mm in rame rosso (red copper)<br />

1,50 mmq<br />

0,22 mmq<br />

GUAINA ESTERNA<br />

Per la sua costruzione particolare (con guaina esterna<br />

maggiorata), questo cavo è di “tipo grado 3” e quindi utilizzabile<br />

per un collocamento interno in canaline, anche<br />

in presenza di altri cavi, con un isolamento di 450 V.<br />

CAVo <strong>ALLARME</strong> GR4<br />

Caratteristiche tecniche • Technical characteristics<br />

Per la sua costruzione particolare (con doppia guaina esterna<br />

maggiorata), questo cavo è di “tipo grado 4” e quindi utilizzabile<br />

sia per un collocamento interno in canaline, anche<br />

in presenza di altri cavi, sia all’esterno essendo conforme alle<br />

norme CEI 64,8 IV edizione con un isolamento di 750 V.<br />

CoNDUTToRI<br />

I conduttori unipolari costituenti i fili di alimentazione (0,50-<br />

0,75-1,00 -1,50) sono isolati in PVC tipo R2 e superano la<br />

prova di tensione prevista dalle norme CEI 20-20 ossia: 5<br />

primi a 6000 Vcc a secco senza screpolature dell’isolante.<br />

I fili di segnalamento (0,22) sono isolati in PVC tipo R2 e<br />

superano la prova di tensione prevista dalle norme CEI<br />

20-20 ossia: 5 primi a 1000 Vcc a secco senza screpolature<br />

dell’isolante.<br />

Fili/Wires<br />

n° 48 Ø 0,20 mm in rame rosso (red copper)<br />

n° 07 Ø 0,20 mm in rame rosso (red copper)<br />

Diametro<br />

Diameter mm<br />

1,50<br />

1,80<br />

2,00<br />

2,40<br />

1,00<br />

Resistenza elettrrica<br />

MAX<br />

Electr. resist. Ohm/Km<br />

8/10 n° 1 Ø 8/10 mm in rame rosso (red copper) 1,40 42<br />

GuAiNA/SHEATH<br />

100% SHIELDING covering<br />

Shielding is made by:<br />

- coupled ribbon of aluminium / polyester 9/12 micron<br />

- drainage wire in tinned copper braid conductor<br />

- ribbon of polyester of 12 micron stuck on joined cable<br />

according to CEI 46-5 regulations.<br />

External jacket white, blue, red or grey is made by<br />

flexible PVC type RZ and not spreading fire according<br />

to CEI 20/22 - II Edition regulations.<br />

<strong>ALARM</strong> CABLE GR2 TYPE<br />

Owing to its making features, following to good results in<br />

tests, this cable is “GR2” with insulation of 250 V.<br />

<strong>ALARM</strong> CABLE GR3 TYPE<br />

EXTERNAL JACKET<br />

Owing to its particular making (with oversize external<br />

jacket), this cable is “Type GR3”, it can be put inside channels<br />

even with other cables with insulation of 450 V.<br />

<strong>ALARM</strong> CABLE GR4 TYPE<br />

Owing to its particular making (with double oversize<br />

external jacket), this cable is “Type GR4”, it can be<br />

put inside channels even with other cables and<br />

outdoor, according to CEI 64.8 regulations with an<br />

insulation of 750 V.<br />

UNIPOLAR WIRES<br />

Unipolar feeding wires (0,50-0,75-1,00-1,50) are insulated<br />

in PVC type R2. They pass the test of voltage according to<br />

CEI 20-20 regulations: 5 minutes with 6000 V. in dry direct<br />

current without any crack of insulation covering.<br />

Unipolar signal wires (0,22) are insulated in PVC type R2.<br />

They pass the test of voltage according to CEI 20-20 regulations:<br />

5 minutes with 1000 V. in dry direct current without<br />

any crack of insulation covering.<br />

sCherMO ALLuMiNiO/pOLiestere<br />

ALUMINIUM/POLYESTER SHIELD<br />

FiLO tAGLiAGuAiNA<br />

RIP CORD<br />

NAstrO pOLiestere<br />

RIBBON OF POLYESTER<br />

39<br />

26<br />

20<br />

14<br />

99<br />

FiLO dreNAGGiO<br />

iN rAMe stAGNAtO COrdAtO<br />

DRAINAGE WIRE<br />

IN TINNER COPPER-BRAID<br />

FiLi di<br />

seGNALe<br />

SIGNAL<br />

WIRES<br />

FiLi di<br />

ALiMeNtAziONe<br />

FEEDING WIRES